499.01 300 ITEM 499 CONCRETE —GENERAL
499.01 Description
499.02 Materials
499.03 Concrete Mix Design
499.04 Adjustments and Controls
499.05 Equipment
499.06 Handling, Measuring, and Batching Materials
499.07 Batch Plant Tickets
499.08 Mixing Concrete
499.01 Description. This specification consists of proportioning requirements
for portland cement concrete mix designs, mixing, adjustments and controls , and batch plant requirements for portland cement concrete.
499.02 Materials. Furnish materials conforming to:
Portland cement ............................. 701.01, 701.02, 701.04 ........................ 701.05 and 701.09 or blended cement[1] Micro -silica ................................ ............................ 701.10 Slag cement ................................ ............................ 701.11 Fly ash ................................ ................................ .... 701.13 Fine aggregate [2][3] ................................ ................. 703.02 Coarse aggregate[3] ................................ ... 703.02, 703.13[4] Recycled Concrete Aggregate (RCA) ..... Supplement 1117 Air-entraining admixture ................................ ........ 705.10 Chemical admixture for concrete[5] ........................ 705.12 Carbonate micro-fines ................................ ............ 705.27 [1] If blended cement is used, provide mill certification of all the cement and pozzolanic components and final product for approval by the Office of Materials Management [2] 703.02 natural sand or sand manufactured from stone as specified in Item 703.02.A.3 is required in 255, 256, 451, 452, 526, and 511 deck slabs. [3] Aggregates may be standard gradation sizes from 703.02 and Table 703.01 -1 or they may be a modified gradation defined with the mix design submittal and certified by the Office of Materials Management under Supplement 1069. [4] Applies only to 305, 451 and 452 concrete. [5] Admixtures shall contain no more than 50 parts per million chloride ions by weight of cement except for Type C accelerating admixtures or calcium chloride for Q C-FS only Use water for concrete mixing free from sewage, oil, acid, strong alkalis, vegetable matter, clay, and loam. Potable water is satisfactory for use in concrete. Non-potable water will meet the requirements of ASTM C1602. Water from a reclaiming system will contain no more than 0.06% chlorides. Test the non -potable water monthly and maintain data verifying that the water meets the requirements. Provide the data at the Engineer’s request.
499.03 Concrete Mix Designs . Develop concrete mix designs w ith 1 -inch
maximum nominal size coarse aggregate according to ACI 301, Section 4 meeting the requirements of Table 499.03 -1. Limit the pozzolan and carbonate micro -fines content of any mix design according to Table 499.03 -2 and Table 499.03 -3. The design air for concrete with 1 -inch nominal maximum size aggregate is 7%. Develop concrete mix designs per this specification and Supplement 1126. 499.03 301 Only use mix designs accepted by the Department and issued a JMF number. TABLE 499.03 -1 CONCR ETE MIX D ESIGN REQUIREMENTS Quantities per Cubic Yard (Cubic Meter) Provide Concrete with 7±2% Air Content Class Design Strength psi (MPa) Permeability [1] Maximum (Coulombs) Cementitious Content [2] Minimum. lbs (kg) Aggregate Requirements QC 1 4,000 (28.0) at 28 days 2,000 520 (236) Well -Graded QC 1P[9] 4,000 (28.0) at 28 days 2,000 520 (236) Well -Graded QC 2 4,500 (31.0) at 28 days 1,500 520 (236) Well -Graded QC 3 Special As per plan 1,500 or as per plan 520 (236) or as per plan Well -Graded or as per plan QC 4 Mass Concrete 4,000 (28.0) or as per plan [3] 2,000 or as per plan 470 (213) [4] [5] or as per plan Well -Graded or as per plan QC 5 [8] 4500 (31.0) at 28 days N/A 520 (236) 1 inch or 3/8-inch nominal maximum size QC SCC 4500 (31.0) at 28 days 1,500 or as per plan 520 (236) Well -Graded, 1 inch or 3/8-inch nominal size or as per plan QC MS See Supplement 1126 N/A 800 (363) 1-inch nominal maximum size QC FS See Supplement 1126 N/A 900 (408) 1-inch nominal maximum size QC Misc. [6] 4,000 (28.0) at 28 days N/A 550[7] (249) 1-inch nominal maximum size [1] AASHTO T277 Modified. [2] Cementitious Content includes cement and pozzolan denoted as Cm. [3] Strength for Mass Concrete (QC 4) may be tested at either 28 or 56 days. [4] Do not use Type III cement or accelerating admixtures in mass concrete. [5] The maximum fly ash or slag cement content may be increased up to 50%. [6] For QC Misc. mixes only –Water/Cementitious ratio limited to 0.50 maximum. [7] Cement or a combination of cement and up to15% fly ash or up to 30% slag cement . [8] For QC 5 mixes with 3/8 -inch nominal size, provide an air content of 8±2%. [9] Portland cement concrete pavement mix design. Determine the permeability by testing according to AASHTO T277 except moist cure the permeability samples for 7 days at 73 °F (23 °C) followed by 21 days of moist curing at 100 °F (38 °C). Perform permeability testing at 28 days. Limit pozzolan materials as a percent of total cementitious content according to Table 499.03 -2: 499.03 302 TABLE 499.03 -2 POZZO LAN MAT ERIAL S Materials Maximum Content (%) Fly Ash 25 Slag Cement 30 Micro -Silica 10 When using multiple pozzolan materials, do not exceed the individual maximum contents above for each material. A combination of pozzolan materials may not exceed 50% of the total cementitious content by weight. Limit carbonate micro -fines as a percent of total cementitious content according to Table 499.03 -3: TABLE 499.03 -3 CARBONATE MICRO -FINE S MATERIALS Material Maximum Content (%) Carbonate Micro -Fines 20 Do not use carbonate micro -fines in Class QC 2 or QC 3 concrete.
499.04 Adjustments and Controls . Provide the following adjustments and
controls during batching and placement of the concrete:
499.05 Equipment. Use a Department approved batch plant and trucks. Provide
batching a nd mixing equipment meeting the following requirements:
499.06 Handling, Measuring, and Ba tching Materials . Do not stockpile
aggregates from different sources or different gradations together. Do not use aggregates that have become segregated or mixed with foreign material. The Engineer may direct reworking or cleaning, or may reject aggregates that have become segregated or mixed with earth or foreign material. Prior to and during batching, maintain all coarse aggregates at a uniform moisture content. For all slag aggregates or other aggregates with a reported absorption above 3.0 percent, ma intain the moisture contents at or above the ODOT -reported SSD for that aggregate as follows:
499.07 Batch Plant Tickets. Furnish a concrete ba tch plant ticket to the Engineer
for each load of concrete incorporated into the project. Provide computer generated batch tickets. At a minimum, include the information listed in Table 499.07 -1 on each ticket: 499.07 307 TABLE 499.07 -1 EVERY BATCH TICKET Name of ready -mix batch plant Batch plant No. Batch plant location Serial number of ticket Date Truck number Class of concrete JMF Number Batch time Batch size yd3 (m3) Actual weights and batch tolerance of cementitious material: Cement lb (kg) Fly ash lb (kg) Slag cement lb (kg) Micro -silica lb (kg) Other lb (kg) Actual weights and batch tolerance of aggregates: Coarse lb (kg) Intermediate lb (kg) Fine lb (kg) Carbonate Micro -Fines lb (kg) Other lb (kg) Actual weight of water and batch tolerance lb (kg) Actual volume of admixtures: Air-entrainer fl oz (mL) Superplasticizer fl oz (mL) Water -reducer fl oz (mL) Retarder fl oz (mL) Other fl oz (mL) Aggregate moisture contents: Coarse aggregate % Intermediate aggregate % Fine aggregate % Water -cementitious ratio, leaving the plant Provide the information in Table 499.07 -2 with batch tickets for each day’s first load of concrete and for each JMF. Include Table 499.07 -2 information on the batch ticket or furnish the information on a separate computer -generated or handwritten form attached to the batch ticket. Provide moisture adjustment calculations for all coarse and fine aggregate according to 499.06.C. 499.08 308 If during the co ncrete manufacturing process any of the information listed in Table 499.07 -2 changes, resubmit Table 499.07 -2 information with the first batch ticket supplied with the changed concrete. TABLE 499.07 -2 FIRST TICKET EACH DA Y, EACH JMF Cementitious Materials : Source: Grade or Type: Cement Fly ash Slag cement Micro -silica Other Admixtures Brand: Type: Air-entrainer Retarder Superplasticizer Water -reducer Other The provided concrete batch ticket information is according to ASTM C 94/C 94M, Section 14. The Engineer may require supporting data to validate the basis for furnished aggregate moisture contents.
499.08 Mixing Concrete. Use a central mix plant or in truck mixers to mix the
concrete. When using a central mix plant, mix the concrete not less than 60 seconds Begin the mixing time when all materials are in the drum and end the mixing time when discharge begins. Include transfer time in multiple drum mixer s in the mixing time. Remove the contents of an individual mixer drum before a succeeding batch is emptied into the drum. When concrete is mixed using a truck mixer for complete mixing, mix each batch of concrete at the rotation rate designated on the mixer as mixing speed for not less than 70 revolutions of the drum. Transport mixed concrete from the central mixers in truck mixers, truck agitators, or trucks having non -agitating bodies. Within 90 minutes after cement and water are combined, deliver and completely discharge concrete. When concrete is delivered in transit mixers and before discharging any of a batch, the Engineer may allow adding water within the specified water -cement ratio limits. Perform sufficient mixing, a minimum of 30 revolutions a t mixing speed, to adjust the slump and to regenerate the specified air content throughout the batch. When approved by the Engineer, the Contractor may use approved admixtures (705.12, Type F or G) for retempering the load to adjust the slump after the sta rt of 499.08 309 discharge. Mix for a minimum of 30 revolutions at mixing speed after addition of the admixture. Use admixtures containing no more than 50 parts per million chloride by weight of cement only when specified in the Contract Documents, the accepted JMF, or with the Engineer’s written permission. Ensure that the temperature of all concrete does not exceed 95 F (35 C) until incorporated into the work.