1102SIGN LIGHTING

PA · 2026 Standard Specifications✓ Full text on BuildSpecBook pages 1246–0 Save this section

Ask about Section 1102

Get a cited answer from the section text. Click the citation to check it.

One cited answer a day is free. Start a 14-day trial for unlimited, no card required.

1102.01GENERAL REQUIREMENTS—Section 1101.01

1102.02LUMINAIRES—

(a)Light Fixture. Furnish a light fixture as follows:

• LED or metal halide

• LED. As specified in Section 1101.06 and 7,500 lumens minimum.

• Aluminum mounting bracket, when specified.

• Positive door closure by use of stainless steel latches and hinges.

• Cast aluminum housing and door assembly.

• Refractor and door assembly with nonpermanent-set gasket material.

• Thermal and shock resistant borosilicate glass refractor.

• Weep holes in the lowest area of the luminaire housing bottom when mounted.

• Polished aluminum reflector.

• Conduit entries in the luminaire assembly.

• Constant-wattage ballast, either integral or remote mounted.

• Aluminum, cast aluminum, or stainless-steel enclosures for remote ballasts.

(b)Metal Halide Lamps. Furnish lamps as follows:

• 100 watt coated ceramic.

• 20,000 hours minimum rated life.

• Universal operating position.

• Rated 7,500 initial lumens minimum.

(c)Ballasts. Furnish electronic ballasts as follows:

• Fully enclosed aluminum housing.

• Power factor greater than 90%

• Lamp starting down to -22F ambient temperature and an operating case temperature up to 176F.

• Thermally protected.

• End-of-life and output short-circuit protection.

• Output frequency less than 200 Hz.

• Lamp wattage regulation less than ± 5% for a ± 10% change in rated line voltage.

(d)Fittings. Furnish:

• Washers to level and adjust the luminaires on the supports and made of the same material as the supports.

• Fittings at the entry into the luminaires made of a standard, factory-made, watertight design.

1102.03CIRCUIT BREAKERS, PANELS, AND ENCLOSURES—Furnish the following:

(a)Circuit Breakers. Section 1101.11(h)
(b)Circuit Breaker Panels. Section 1101.11(i)
(c)Enclosures. Section 1101.11(c), (d), and as follows:

Provide enclosures with dimensions that provide code clearance and wiring space for the specified control apparatus.

1102.04CONTROLS—Furnish the following controls:

(a)Photoelectric Control Device. Section 1101.11(b)
(b)Control Contactor. Magnetic control contactor, 600 V, two-pole, 60 A, with a 120 V or 240 V operating

coil.

(c)Selector Switch. Section 1101.11(g)

1102.05LIGHTNING ARRESTER—Section 1101.11(e)

1102.06JUNCTION BOXES—Section 1101.10

1102.07CABLE—Section 1101.08 and as follows:

Provide Type TC, Tray Cable, with XHHW insulation and a PVC jacket, for cable from the sign enclosure to the luminaire.

1102.08CONDUIT—Section 1101.09

1102.09MISCELLANEOUS MATERIAL—Section 1101.13 and as follows:

(a)Service Poles. Section 1101.11(a)
(b)Ground Rod. Section 1101.11(j)
(c)Guy Anchor Assembly. Section 1101.11(m)
(d)Fittings. Provide standard, factory-made, watertight fittings at enclosures, junction boxes, conduits,

and service heads.

Referenced in this section
Sections that cite this one

SIGN LIGHTING in other states

Get an email when 1102 changes

Pennsylvania revises spec sections through supplementals and new editions. We check this one every week and email you the day it changes. Free, no account.

Source: Publication 408 Highway Construction Specifications, 2026 Edition. Pages 1246–0 of 1,522. View official source ↗

Ask about this section

Scoped to Pennsylvania Publication 408 — Specifications, Section 1102 — SIGN LIGHTING. Every answer cites the section it came from, with a verification date — don’t trust a percentage, click the citation.