Manufactured Material (1100-1199)

1103TRAFFIC SIGNING AND MARKING

PA · 2026 Standard SpecificationsBook pages 12361240View official source ↗

1101. 06(e) 1101. 07(b) height and three mounting heights transverse distance, of not less than 20% of the bare lamp lumen output.

(f)Overhead Mount Luminaires (Underpass). Furnish as specified in Sections 1101.06(b) and (c) .

1101. 07 LUMINAIRES (HIGH -MAST LIGHTING) —Furnish open- type, cutoff luminaires complete with lamps, ballasts, associated hardware, and necessary wiring as specified in Sections 1101.06(a) , (b), and (c) , and as follows:

(a)Luminaires – HPS – (High -Mast Lighting).

• Provide with adjustable slip -fitters designed for a 2- inch tenon to allow a positioning adjustment of ±3 degrees about the tenon axis.

• Provide with a heavy -duty, porcelain- enclosed, lamp socket, with the brass shell impregnated to prevent thermal freezing with the lamp base.

• Provide a lamp- stabilizing clamp that is non asbestos -lined, heat -resistant, and stainless steel.

• Equip luminaires with ballasts, as specified in Section 1101.06(a).

• Furnish 400 W, high- pressure sodium lamps with a minimum initial output rating of 50, 000 lumen and a minimum rated life of 24, 000 hours based on 10 hours of operation per start.

• Furnish lamps that burn in a vertical (base- up) position.

• Provide luminaires with a maximum luminous intensity angle nominally 60 to 65 degrees from nadir.

• Furnish luminaires having a projected area not exceeding 3.5 square feet, an EPA not exceeding 2.0 square feet, and exerting a gravitational force not more than 75 pounds.

• Provide glare shields, when indicated.

• Furnish luminaires that provide the following nominal initial luminous intensity at the angless pecified below :

Vertical Angle

(degrees)Luminous Intensity

(candelas)

20 2,850 30 4,170 40 4,760 50 7,500 55 9,550 60 12,900 65 13,800 70 9,250* 72 1/2 7,350* 75 4,350* * These are minimum values at the respective angles. Other candelas are nominal values.

Furnish vertical luminous intensity trace data to ascertain compliance with luminous intensity distribution requirements.

(b)Luminaires – LED – (High -Mast Lighting).

1101. 07(b) 1101. 07(b)

1.Housings.

• Provide a precision cast or formed housing of minimum 96% copper -free aluminum, minimu m shell thickness of 0.050- inch, with stainless steel or zinc plated steel fastening hardware and an integral 2-inch slip -fitter, capable of adapting to the mounting tenons and adjustable for 1 1/4-inch or 2- inch mounting pipe. Provide integral die cast mounting pipe stop feature and integral levelling means.

• Provide ANSI/NEMA C136.31 Vibration Test Level 3G.

• Provide factory installed LED array thermally sealed to heat sink.

• Driver to be accessible and removable without the use of tools. Enclosure to be

Source: Pennsylvania Department of Transportation Specifications, 2026 Edition. Pages 12361240 of 1,522.