753.0 3 Light Poles .
a.Anchor Bases . Anchor bases shall consist of a one -piece aluminum casting conforming to the requirements of ASTM B26 or ASTM B108, Alloy SG70A -T6, 356 -T6.
b.Pole Shafts . Pole shafts shall be fabricated from tapered one -piece seamless aluminum tubes conforming to the requirements of ASTM B221, Alloy 6063 -T6, Alloy 6061 -T6, or Alloy 6005 - T5. The minimum wall thickness shall be 0.125 inch for mounting heights of less than 20 feet and 0.188 inch for mounting heights of 20 feet or more.
c.Pole Caps . Pole caps shall consi st of a one -piece aluminum casting conforming to the requirements of ASTM B26 or ASTM B108 , Alloy SG70A -T6, 356 -T6. 7-133 753.0 4 BRACKE T ARMS .
a.Bracket Arms, Aluminum . Single member bracket arms and the main member of truss -type arms shall be fabricated from seamless aluminum tube conforming to the requirements of ASTM B221, Alloy 6063 -T6 or Alloy 6061 -T6. Other members of truss -type arms shall conform to the requireme nts of ASTM B221, Alloy 6063 -T6. All screws, nuts, bolts and other hardware for mounting bracket arms to the light pole shall be stainless steel, unless otherwise specified.
b.Bracket Arms, Steel . Components of single member and truss -type bracket arms s hall be fabricated from standard steel pipe meeting the requirements of ASTM A53 or ASTM A501 .
753.0 6 HIGHWA Y ILLUMINATIO N CONDUCTO R CABLE . Highway illumination conductor cables
shall be conductors of stranded, soft -drawn copper with a moisture and heat resistant therm oplastic insulation. Cables shall be rated for 600 volt service at 167°F for either dry or wet locations. The single conductors shall conform to the requirements of the National Electrical Code for the intended wire use and existing field conditions. The w ire size shall be such that no more than a 3% voltage drop will occur anywhere in the secondary circuit. All wiring shall be color -coded. All conductors within the streetlight pole and bracket a rm shall be No. 10 AWG stranded copper wire. Street lighting conductors within strain poles or mast arm poles shall also be No. 10 AWG stranded copper wire. UF cable will be allowed in the bottom of the pole below the handhole.
754.0 1 OPTICS . Optics shall be beads or elements incorporated into pavement markings to produce
reflectorized pavement markings. Optics shall be one of the products listed on the Agency’s Approved Product s List for the respective material specification and shall meet t he following requirements :
a.Optics, Type I . Type I optics shall be standard optics consisting of glass beads free from carbon residue. Type I o ptics shall conform to the requirements of AASHTO M 247, Type 1, except as modified below.
1.Roundness . Roundness shall be a minimum of 80% true spheres, as determined in accordance with ASTM D1155 .
2.Moisture Resistance . Optics shall be moisture resistant in accordance with AASHTO M 247.
3.Chemical Resistance . Optics shall be resistant to hyd rochloric acid, water, calcium chloride, and sodium sulfide in accordance with Federal Specification TT -B-1325 , Section 4.3.
b.Optics, Type II . Type II o ptics shall be modified optics consisting of virgin glass beads or a mixture of virgin glass beads an d direct melt glass beads, with a maximum of 50% direct melt glass beads. All glass beads shall be free from carbon residue. Type II optics shall conform to the requirements of AASHTO M 247 , Type 2, Type 3, Type 4, or Type 5, except as modified below.
1.Roundness . Roundness shall be a minimum of 80% true spheres, as determined in accordance with ASTM D1155 .
2.Refractive Index . a. The r efractive index shall be 1.5 to 1.7, inclusive, as determined in accordance with AASHTO T 346 ; or b. The r efractive ind ex shall be above 1.7 with all beads above the No. 18 (1.00 mm) sieve having an average hardness of C70.5 as determined in accordance with the Rockwell C scale method, with a minimum sampling of 100 glass beads.
3.Moisture Resistance . Optics shall be moisture resistant in accordance with AASHTO M 247.
4.Chemical Resistance . Optics shall be resistant to hydrochloric acid, water, calcium chloride, and sodium sulfide in accordance with Federal Specification TT -B-1325 , Section 4.3.
Source: Vermont Standard Specifications for Construction, 2024 Edition. Pages 1284–1285 of 1,380.