Effective with the December 2018 Letting 361 2019 Standard Spec ifications Section 616 Property and Right-of-Way Fence
616.1Description
616.2Materials
616.2.1 General
Preservatives and pres ervative tr eatment ...................... ............................................................................. 507.2 Structural Steel and mi scellaneous metals ..................... ............................................................................. 506.2
except the engineer may waive t he requirements for proportionin g by weight, and may allow alternate mixers or mixing methods. Pro vide QMP for class III ancillary c oncrete as specified in 716. 616.2.2 Woven Wire Fence Materials 616.2.2.1 Woven Wire Fabric
horizontal wires shall be 9-gauge . This fabric shall have 10 li ne wires, a nominal height of 47 inches, and conform to the design the plans show. Run the vertical stay wires from top to bottom line wires, at 6 inch nominal spacing.
may use one of the following: - Zinc-coated steel conformi ng to AASHTO M279 class 3. - Aluminum-coated steel conforming to ASTM A116 .
616.2.2.2 Barbed Wire
spaced not more than 5 inches a part and conforming to AASHTO M2 80. If the plans or special provisions do not designate a sp ecific type of barbed wire, the contractor may use one of the following: - Type Z zinc-coated steel. - Type ZA zinc-5 percent alumi num-mischmetal alloy coated steel . - Type A aluminum coated steel.
616.2.2.3 Smooth Wire
class 3. 616.2.2.4 Braces
channel section braces conforming to ASTM A123. Use a type, minimum size, and minimum weight conforming to one of the following: - Welded or seamless st eel pipe, nominal 1.90 inches outside di ameter, weighing 2.72 pounds per linear foot. - Steel tubing, 1.75 inches outsi de diameter, 3.13 pounds per l inear foot. - Steel angle section, nominal 1 3 /4 x 1 3/4 x 1/4 inch, 2.77 p ounds per linear foot. - Steel channel section, nominal 3 inches, 4.1 pounds per linea r foot. - Other engineer-appr oved steel sections.
posts. Furnish fittings, bolts, nuts, washers or other hardware conforming to ASTM A123. 616.2.2.5 Staples
616.2.2.6 Posts
posts and offset blocks.
Effective with the December 2018 Letting 362 2019 Standard Spec ifications (2) The posts shall conform to the dimensions the plans show with a tolerance of plus 2 inches for length, and a diameter at the top or sma ll end, after peeling, 4 1/2 in ches or greater for line posts and 6 inches or greater for corner, b racer, or vertical angle posts.
not use posts with butt rot exc eeding 5 percent of butt area. E nsure post tops are sound, except a 7 inch cedar post may have one pipe or heart rot 3/8 inch or smal ler in diameter. Posts shall not have excessive checking or a one-way sweep greater than 3 inches, or short kinks. Posts may have a winding twist unless unsightly and excessive. All knots shall b e sound.
the posts required under the cont ract may have the maximum crook or the maximum butt rot. The engineer will have sufficient gr ounds to reject posts that contain other defects of any kind that give a post an unsightly appearance.
and inner bark to the white wood co mpletely removed by shaving or by other effective means. Trim knots closely and saw both ends of the post square. If setting the posts by driving, then the larger end may have a blunt point. After peeling, trimming, and cutting to required length, preservative treat the posts by the pressure process specified in 507.2.2.6 , except the preservative m inimum retention is 6 pounds per cubic foot of wood for creosote-coal tar solution or pentachlorophenol solution. 616.2.3 Chain Link Fence Materials 616.2.3.1 General
and braces. Furnish metal parts as follows: - Use aluminum-coated steel fenc e fabric conforming to AASHTO M 181 type II. - Use steel tension wire confor ming to AASHTO M181 type I zinc- coated or type II aluminum-coated. - Use hot-dipped zinc-coated st eel posts, rails, and braces con forming to ASTM F1043 .[1] - Use hot-dipped zinc-coated st eel, or malleable iron hardware, and fittings conforming to ASTM F1043 .[1] [1] The contractor may substitute zinc - 5 percent aluminum-mischm etal alloy conforming to ASTM B750 (type C coating) for hot-dipped zinc (type A coating) specified here in 616.2.3 if applied at t he same rate as the hot- dipped zinc coating.
contract. Make all posts, hardw are, and fittings used on the co ntract the same kind, unless specified otherwise. 616.2.3.2 Fence Fabric
selvages knuckled. Ensure the furn ished fence fabric is the sam e nominal height as the designated fence height. 616.2.3.3 Posts
- Group IA round steel pipe with a type A coating. - Group II roll-formed steel C-sections with a type A coating. 616.2.3.4 Post Tops
Ensure ornamental tops are of department-approved design, made of metal, have a flanged base that fits snugly over top and around ou tside of post, and is securel y fastened in place. Provide the base of each line post top with an openi ng for passage and support of t he top tension wire.
instead of and ornamental post top. 616.2.3.5 Bracing
follows: - Group IA round steel pipe with a type A coating. - Group II roll-formed steel C -sections with a type A.
terminal, corner, intersection , or intermediate braced posts to the first adjacent line post, and fasten
Effective with the December 2018 Letting 363 2019 Standard Spec ifications them securely to the posts with suitable connectors. Use zinc c oated 3/8 inch round steel rods equipped with a threaded take-up adapter for diagonal truss rods. 616.2.3.6 Pipe Fittings
616.2.3.7 Fabric Fasteners
for securing the fence fabric to H column line posts. User 9-gauge zinc coated steel or 0.179-inch diameter aluminum tie wires as fasteners for securing the fence to posts or top tension wires and braces. Use tie wires not smalle r than 12-gauge zinc coated ste el, or 0.149-inch diameter aluminum wire, as fasteners for securi ng to bottom tension wires. 616.2.3.8 Tension Bars
616.2.3.9 Gates
gates.
616.3Construction
616.3.1 General
fencing before starting other it ems of work under contract for these areas, or provide a temporary fence to exclude the livestock.
construction, within approximately 12 inches along each side of the fence line, as specified for clearing and grubbing in 201.3 . If the contractor cuts trees or stumps close enough to the ground to prevent interference with correct fenc e erection, the engineer will not require grubbing of the stumps.
show or the engineer directs otherwise. Where the engineer dire cts or allows the contractor to leave trees on the fence line, deviate the fence line past the tree a s the plans show.
616.3.2 Woven Wire Fence 616.3.2.1 General
all end, corner, pull, and vertical angle posts at the locations staked or where the engineer designates. 616.3.2.2 Placing Posts
the wire side. Unless the planss how otherwise, set line posts at as uniform spacing as possible under local conditions, but the spacing shall not exceed 16 feet center to center of posts. Set additional posts, as required, at abrupt chan ges in grade. Excavate post h oles to the required depth. If the contractor encounters rock, emp loy necessary drilling, blasting , or other means of excavation. Use suitable material for backfill, and place and compact in layers around the post until firmly embedded, plumb, and true to alignment.
as the plan details show. Use a double strand of 9-gauge zinc-c oated, smooth wire for wire guying and stretch between posts as the plans show. Wrap the wire around t he posts and staple. Twist the strands of wire taut. Place ver tical angle post assemblies at g rade change points of more than 2 feet between consecutive posts that r esult in a wire uplift on the p osts.
if placing in concrete. If driving posts, drive them plumb, to the required depth and alignment, and with adequate lateral stability. Remov e and replace with a sound pos t any post not conforming to the above requirements, or damaged below cut-off during driving. 616.3.2.3 Placing Wire
ground, but not more than 4 inches above the ground at the posts, except on abrupt grade changes as
Effective with the December 2018 Letting 364 2019 Standard Spec ifications the plans show. Place one line of barbed wire above the woven wire, as the plans show, and staple the wire at each post.
around the post and tying the wi re back on itself with not less than 1 1/2 twists tightly wrapped with tools designed for the purpose, and supplement with staples dri ven into the posts. Stretch the wire until no slack exists, longitudi nal wires are tight, and approx imately 50 percent of the factory fabricated fence crimp is removed. Apply tension with an engineer-approved stretcher designed to produce a uniform tension in each wire.
intermediate wires. Use additional staples if necessary. Stagge r the vertical alignment of staples slightly and do not place para llel with the wood grain. Drive t he staples tight at all pull, angle, end, and corner posts, and double staple the wire if required. Drive the staples firmly at other line posts but loose enough to allow lateral movement of the wire. Make splices in the fencing at posts or between posts to the engineer’s satisfaction.
616.3.3 Chain Link Fence 616.3.3.1 General
on driven unbraced metal line posts. 616.3.3.2 Setting Posts
spacing as local conditions a llow. Space posts, center to cente r, according to the following situations as follows: - On a tangent or on a curve of 500 feet or more radius; space posts at no more than 10 feet. - On a curve of from 200 to 500 feet radius, space posts at no more than 8 feet. - On a curve of from 100 to 200 feet radius, space posts at no more than 6 feet. - On a curve of less than 100 feet radius, space posts at no mo re than 5 feet.
without abrupt changes. Conform to the general contour of the t errain.
more in the horizontal alignmen t. Set an intersection post in l ine with an intersecting chain link fence, and brace with the adjacent post of the intersecting fence.
change in the fence line grade o f greater than 9 percent that r esults in wire uplift on the post.
and grout as the plan details sh ow. Use a non-shrink grout conf orming to 506.3.30 for bearings and anchorages. Thoroughly ram the gr out into the sleeve anchor while the post is in place. Allow the grout to cure at least 48 hours before stretching the chain link fabr ic.
asphaltic or other engineer-appro ved material. Ensure this coating is firmly set before placing the posts.
slightly away from the post. Locate the footing to allow centering of the post. Backfill the top of the footing with topsoil or other suitable material.
the excavation. Remove rock or other obstructions encountered i n the excavation to the required depth.
Keep the form in place until the concrete cures for at least 24 hours. After removi ng the form, backfill the footing with suitable mate rial. Ensure the backfill material has the correct moisture content for compacting and place and compact in layers.
placing the top and bottom tension wires.
Effective with the December 2018 Letting 365 2019 Standard Spec ifications (12) Place an intermediate braced post midway between end posts and corner posts if t he fence run is more than 1000 feet, but not m ore than 2000 feet. For fence run s greater than 2000 feet, make the maximum spacing of intermediate braced posts 1000 feet.
required depth and alignment, and with adequate lateral stabili ty. Remove and repl ace any post that fails to conform to the above requirements, or that the contrac tor damages during driving, with an undamaged post. In unstable soils, increase the length of drive n posts by multiples of 2 feet, as the engineer directs, to increas e the stability of the post. 616.3.3.3 Erecting Fence Fabric
the tension wires securely to each end, corner, intersection, o r intermediate braced post. Fasten the tension wires to each line post.
and secured to the post with clam ps and bolt. Stretch the fabri c with engineer-approved stretching equipment to remove all slack. Secure the stretched fabric to l ine posts, braces, and tension wires with specified fabric fasteners. Place fabric fasteners on line posts at no greater than 14 inch centers; and on braces and tension wires a t no greater than 18 inch centers. Repeat stretching operations at approximately every 100 feet for each run of fence.
the splice is neat and secure. 616.3.3.4 Gates
616.3.3.5 Salvaged Chain Link Fence
hardware without damaging the par ts. Replace contractor-damaged parts and provide all other materials, including concrete, r equired to re-erect the fence. Dispose of all surplus materials.
616.3.4 (Vacant) 616.3.5 Electrical Grounds
least 8 feet long, driven vertic ally into the ground along the fence line, near a post, until approximately 6 inches extends above the grou nd. Securely clamp, bolt, or bra ze at least 3 fence wires to the ground rod. Electrically ground bar bed wire as the plans show.
than secondary feeder lines for i ndividual service, cross the fence. Install one groun d rod along the fence at the point of crossing and one 25 to 50 feet in each direction from the crossing.
ground rod on each electrically i solated section of fence, defi ned as a run with no interruptions in electrical continuity.
616.4Measurement
completed, measured from center to center of end posts, along t he fence line at the ground line. The department will dedu ct for openings.
measured from center to center o f end posts, along the top tension wire. The department will deduct for gates and other openings.
completed.
completed, measured from center to center of end posts, includi ng gates, along the top rail or tension wire. 616.5 Payment
items: ITEM NUMBER DESCRIPTION UNIT
Effective with the December 2018 Letting 366 2019 Standard Spec ifications 616.0100 Fence Woven Wire (height) LF
616.0200 - 0299 Fence Ch ain Link (height) LF
616.0329 Gates Chain Link (width) EACH
616.0400 - 0499 Fence Chain Link Salvaged (height) LF
the right-of-way.
the fence line; for excavating; fo r setting posts including pla cing concrete; for erecting and tensioning all fencing components; for installing grounds; and for removin g and disposing of all debris, excess excavation, and surplus materials.
soils at no additional cost to the department.
existing fence materials; for re-erecting gates; for replacing all contractor-damaged parts; and for providing all other materials r equired to re-erect the fence.
Effective with the December 2018 Letting 367 2019 Standard Spec ifications Section 617 Hauling
617.1Description
617.2 (Vacant)
617.3Construction
site in an engineer-approved v ehicle. The engineer may approve any size or type of vehicle for hauling provided that vehicle conforms to the following:
being hauled.
structures as necessary to reach the work site from the materia l source. Also, maintain, repair, and restore previously constructed pr ivate roads, bridges, culverts , and structures used to pre-hauling condition. 617.4 Measurement
department will determine the total quantity for payment by mul tiplying the number of cubic yards hauled and placed in each zone by the mile number of the zone. The department will determine mile zones along the shortest and mo st practicable line of haul from the loading point to and along the project. The department will only measure hauling of materials specifically included in a Hauling bid item.
617.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
617.0100 Hauling (material) CYMI
the contract specifies otherwise, costs associated with private roads, bridges, culverts, and structures used to haul material under this bid item.
Hauling materials not specifically included in a Hauling bid item is also incidental to related work.