Effective with the December 2018 Letting 470 2019 Standard Spec ifications Section 652 Electrical Conduit
652.1Description
and other electrical work, and rigid nonmetallic conduit for tr affic signal detectors.
652.2Materials
652.2.1 General
652.2.2 Rigid Metallic Conduit
652.2.3 Rigid Nonmetallic Conduit
locations. Use schedule 80 ext ra-heavy wall type for locations exposed to the elements. 652.2.4 Reinforced Therm osetting Resin Conduit
to UL 2515. Ensure that wall th ickness, coupling type or method , fittings, and hanger system conform to manufacturer recommendations for installation on the outside of structures. 652.2.5 Loop Detector Conduit
attachments designed specifica lly for the conduit furnished to join and terminate PVC conduit. Use engineer-approved PVC terminal adaptor fittings to connect cast iron T-condulets to PVC conduit.
wedge-nut style covers with neoprene gaskets on cast iron condu lets.
652.3Construction 652.3.1 Installation of Conduit
652.3.1.1 General
conduit.
plans show or as the engineer directs. Inst all each run of cond uit between adjacent access points using one size for its entire length. A run is the conduit from pull box to pull box, junction box to junction box, or pull box to j unction box. If the engineer appr oves, the contractor may substitute a larger size of conduit than the contract shows for that run. Delete 652.3.1.1(3), the department no longer allows drilled and open drain hole conduit installations.
the contract specifies wire or cable, install a 12 AWG. XLP insulated, stranded, copper, 600-volt AC, wire. Provide wire 4 feet longer than the conduit run and doubl e it back at least 2 feet at each raceway access point. Anchor the tracer wire at each access point.
wire or cable, install engineer- approved threaded caps with ant i-seize compound applied to the threads.
pull box, and keep capped or plugged until installing the wire or cable. Install end bells on rigid nonmetallic conduit raceway access points before installing wir e or cable. Ream non-metallic conduits to eliminate internal sharp edges before installing end bells. Use only UL or NRTL listed adapter fittings to connect rigid nonme tallic conduit to rigid metallic conduit. 652.3.1.2 Installing Underground
depth and width sufficient to acc ommodate the outside diameter of the conduit couplings. Lay the conduit at the depth below grade t he plans show. Backfill the trench with select material passing a one-inch sieve.
Do not backfill the trench befo re inspecting the conduit. Caref ully tamp the backfill in place as specified for placing backfill in layers in 651.3 . Place at least 0.7 cubic feet of size No. 2 coarse aggregate, as specified in 501.2.5.4.5 , directly under each drainage hole.
Effective with the December 2018 Letting 471 2019 Standard Spec ifications (3) If cinders are present when laying rigid conduit, encase the c onduit in at least 2 inches of concrete, or remove for at least 12 inches below the conduit and backfill th e excavation with suitable material.
areas with damaged or missing zinc coating. Clean application a nd adjacent areas before painting. 652.3.1.3 Installing Conduit Special Underground
or other engineer-approved methods that do not disturb the exis ting overlying pavement, curb and gutter, or sidewalk. Use conduits uitable for the installation method used. Repair pavement, curb and gutter, or sidewalk that the engineer determines damaged by the installation. 652.3.1.4 Installing on Structures
outside of the structure. Unless specifically provided otherwis e, do not leave openings in the structure for subsequent conduit placement. Install engineer-approved exp ansion fittings where the conduit crosses an expansion joint in a structure. Install additional e xpansion fittings conforming to the WSEC and adjust for the ambient temperature at the time of concrete pour.
for embedded raceways.
hardware conforming to manufacturer recommendations. Use only m anufactured bends and sweeps. Do not make field bends. Ensure that the installer is certified by the manufacturer of the conduit and conforms to manufacturer recommendations for installation on th e outside of structures. Provide evidence of installer certification to the engineer before inst allation. 652.3.1.5 Constructing Loop Detector Slots
loop detector conduit, as the plans show or the engineer directs.
and removing the remainder by c hipping, or other engineer-appro ved methods. Clean the slots with jets of water and compressed air; remove dirt, dust, and debris ; and thoroughly dry before installing the detector loop cond uit. Remove and dispose of surplus material. 652.3.1.6 Installing Loop Detector Conduit
plans show.
replace damaged loop detector conduit at no expense to the department. The engineer will approve the replacement or repair method, and the resulting finished wo rk. 652.3.2 Marking and Inspecting
During this inspection, ensure that the conduit raceway is fully open for its entire length. Replace any conduit that the engineer determines is crushed, damaged, or un satisfactory.
from that conduit's centerline to a plumb line projected down from the tip of the a rrow mark is more than six inches, expose all arro w marked conduits. Destroy arro w marks not meeting the six-inch limit and remark the conduit.
652.4Measurement
Reinforced Thermosetting Resin bid items by the linear foot acc eptably completed, measured along the conduit centerlin e from the centerline of fittings or, where there are no fittings, from the free ends of the conduit. The department w ill measure enginee r-specified drain duct from a pull box to a ditch or sewer.
measured from pull box to pull box.
measured around the loop and fr om the loop to the nearest pull box.
Effective with the December 2018 Letting 472 2019 Standard Spec ifications 652.5 Payment
items: ITEM NUMBER DESCRIPTION UNIT
652.0100 -0199 Conduit Rigid Metallic (size) LF
652.0200 - 0399 Conduit Rigid Nonm etallic (schedule) (size) LF
652.0400 - 0599 Conduit Reinforced Thermosetting Resin (size) LF
652.0600 - 0699 Conduit Special (size) LF
652.0800 Conduit Loop Detector LF
652.0900 Loop Detector Slots LF
Resin, and Conduit Special bid items is full compensation for p roviding the conduit, conduit bodies, and fittings; for providing condui t hangers, clips, attachments, and fittings used to support conduit on structures; for pull wires or ropes; for expansion fittings and caps; for excavating, bedding, and backfilling, including any sand, concrete, or other required ma terials; for disposing of surplus materials; and for making inspections.
or sidewalk the contractor disturbs or damages.
directs under the 653 Pull Box bid items.
compacted backfill, surface sealer, pull wire, condulets, and c onduit fittings.
disposing of surplus material; and for cleaning the slot.
department will pay separately for tracer wires under the appropriate Electrical Wire bid items specified in 655.5 .
Effective with the December 2018 Letting 473 2019 Standard Spec ifications Section 653 Pull Boxes and Junction Boxes
653.1Description
653.2Materials
521.2 with annular corrugations.
contractor may field trim to customize pull box lengths.
locations and on 12-inch pull boxes.
mechanical connections to pu ll boxes and junction boxes.
653.3Construction
plans show using the same mater ial as the pull box. Saw extensi ons parallel to the annular ring and clamp to the pull box using a band manufactured for this purpos e. Excavate, place coarse aggregate drain material, and backfill as t he plans show. Dispose of surp lus or unsuitable material as specified under 205.3.12. Use covers stamped "WISDOT IT S" for communications pull boxes or "ELECTRIC" for other pull boxes.
show. Grounding lugs are not required in junction boxes with less than 50 volt AC.
subsurface components as required, and backfill as the plan det ails show. Dispose of surplus or unsuitable material as specified under 205.3.12 .
material similar to the surrounding material. Dispose of surplus or unsuitable material as specified under 205.3.12.
653.4Measurement
completed.
653.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
653.0100 - 0149 Pull Boxes Steel (size) EACH
50 - 0179 Pull Boxes Nonconductive (size) EACH
80 Pull Boxes Steel Communications (inch) EACH
653.0200 - 0299 Junction Boxes (size) EACH
653.0900 Adjusting Pull Boxes EACH
05 Removing Pull Boxes EACH
including grounding lugs; for aggregate, manhole frames and covers; for required pull box extensions; conduit extensions less than 10 feet long including fittings; and for excavating, backfilling, and disposing of surplus material. The department will pay separately for engineer-directed pull box drain duct under the Conduit Rigid Nonmetallic bid items as specified in 652.5 .
grounding lugs and stainless st eel mounting hardware, wiring, supports, grout, and temporary asphalt; for any pavement cutting and grouting; and for disposing of sur plus material.
materials; and for excavating, backfilling, and disposing of su rplus material.