Effective with the December 2018 Letting 307 2019 Standard Spec ifications Section 521 Corrugated Steel Culverts
521.1Description
steel apron endwalls.
521.2Materials
- Corrugated steel culvert pipe, steel apron endwalls, aluminum coated corrugated steel culvert pipe, and other components conforming to AASHTO M36. - Polymer coated corrugated steel culvert pipe and pipe arch fabricated from zinc coated sheet steel conforming to AASHTO M218. Befor e fabrication, coat the sheets on both sides with polymer protective coating grade 250/250 according to AASHTO M246. Fabricate the p ipe according to AASHTO M245.
521.3Construction
521.3.1 General
521.3.2 Coating Repair
and surrounding areas. Apply zinc-rich paint to the cleaned are a within 24 hours and before rusting or soiling occurs, to a minimum thickness of 5 mils.
coating, or with a tar base material or asphaltic mastic confor ming to AASHTO M243. 521.3.3 Handling Polymer Coated Pipe and Pipe Arch
padded supports and pad objects placed against polymer coated m aterials.
521.4Measurement
pipe in 520.4 and the Apron Endwalls bid ite ms acceptably completed as speci fied for apron endwalls in 520.4 .
521.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
521.0300 - 0699 Apron Endwalls for (type) Cross Drains Steel (s ize) (slope) EACH
521.1000 - 1399 Apron Endwalls for (type) Steel (size) EACH
521.1500 - 1899 Apron Endwalls for (type) Side Drains Steel (si ze) (slope) EACH
521.1900 Pipe Cattle Pass Corrugated Steel LF 521.3100 - 3299 Culvert Pipe Corrugated Steel (size) LF
521.3700 - 3899 Pipe Arch Corrugated Steel (size) LF
521.5100 - 5299 Culvert Pipe Corru gated Steel Polymer Coated (s ize) LF
521.5700 - 5899 Pipe Arch Polymer Coated Corrugated Steel (size ) LF
521.6100 - 6299 Culvert Pipe Corrugated Steel Alum inum Coated ( size) LF
521.6700 - 6899 Pipe Arch Corrugated Steel Aluminum Coated (siz e) LF
- Pipe, pipe arch, cattle pass, and apron endwalls bid items. - Cast-in-place concrete and alternate endwall installations. - Water for compacti on and dust control. - Excavation and foundation ba ckfill at depths greater than 6 i nches below the culvert.
Effective with the December 2018 Letting 308 2019 Standard Spec ifications Section 522 Reinforced Concrete Culverts
522.1Description
apron endwalls.
522.2Materials
follows: - Pipe: furnish the cl ass of pipe the bi d item indicates. - Cattle pass: use class III reinforced concrete pipe. Construc t walkways as the plans show using cast-in- place grade A, A-FA, A-S, A-T, A -IS, A-IP, or A-IT concrete conforming to 501 as modified in 716. For walkway concrete, provide QMP fo r class III ancillary concrete as specified in 716. - Apron endwalls: conform to class II.
follows: - Pipe: furnish the cl ass of pipe the bi d item indicates. - Apron endwalls: conform to class HE-II.
precast concrete fabricators on the department's APL . Conform to the spec ified AASHTO standard materials requirements except as follows: - Use concrete with 565 pounds or more cementitio us material pe r cubic yard. - The contractor may use cement conforming to 501.2.1 or may substitute for portl and cement a t the time of batching conforming to 501.2.6 for fly ash, 501.2.7 for slag, or 501.2.8 for other pozzolans. In either case the maximum total supplementary cementitious content is limited to 30 percent of the to tal cementitious content by weight.
522.3Construction
pipe with different wall thick nesses in the same installations unless the plans or special provisions specify otherwise.
522.4Measurement
pipe in 520.4 and the Apron Endwalls bid ite ms acceptably completed as speci fied for apron endwalls in 520.4 .
522.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
522.0100 - 0599 Culvert Pipe Reinforced Concrete (class) (size) L F
522.1000 - 1199 Apron Endwalls fo r Culvert Pipe Reinforced Conc rete (si ze) EACH
522.1500 Pipe Cattle Pass Reinforced Concrete LF
522.2300 - 2499 Culvert Pipe Rein forced Concrete Horizontal Ell iptical (class) (size) LF
522.2600 - 2699 Apron Endwalls fo r Culvert Pipe Reinforced Concrete Horizontal Elliptical (size) EACH
- Pipe, cattle pass, and apr on endwalls bid items. - Cast-in-place concrete and alte rnate endwall installations. - Water for compacti on and dust control. - Excavation and foundation ba ckfill at depths greater than 6 i nches below the culvert.