Effective with the December 2018 Letting 314 2019 Standard Spec ifications Section 530 Corrugated Plastic Pipe Culverts
530.1Description
530.2Materials
conforms to the plans and as follows: - For polyethylene conform to AASHTO M294 typeS. - For polypropylene confo rm to AASHTO M330 typeS.
cross or side drains conforming to 521.2 , or aluminum apron endwalls conforming to 525 as the contract specifies. Furnish conne ctor rods, connector bands, or other devices that fit the culvert pipe corrugations and provide a tigh t connection between the culvert and endwall.
530.3Construction
530.4Measurement
specified for pipe in 520.4 .
530.5Payment
items: ITEM NUMBER DESCRIPTION UNIT
530.0100 - 0299 Culvert Pipe Corrugated Polyethylene (size) LF
530.1100 - 1299 Culvert Pipe Corru gated Polypropylene (size) LF
- Pipe bid items. - Cast-in-place concrete and alte rnate endwall installations. - Water for compacti on and dust control. - Excavation and foundation ba ckfill at depths greater than 6 i nches below the culvert.
sloped steel apron endwalls under the appropriate 521 bid items; and for aluminum apron endwalls under the appropriate 525 bid items.
Effective with the December 2018 Letting 315 2019 Standard Spec ifications Section 550 Driven Piles
550.1Description
providing test piles; driving piles; and determining required d riving resistance. This section also describes preboring or redriving.
550.2Materials
550.2.1 Steel Piles and Pile Shells
engineer directs or allows other wise. Ensure that piles have ma rks tying them to a s pecific test report, or absent marks, certi fy that all material furnished is represented by a submitted test report. Provide marks or certifications for ea ch piece of a pile fabricated fro m multiple pieces.
allows, the contractor may subst itute steel pipe or steel oil field pipe for HP piles. Use pipe with an outside diameter of 7 3/4 inches or greater, a wall thickness o f 3/8 inch or greater, and a cross- sectional area that equals or exceeds 97 per cent of the area of the HP section replaced.
steel or an engineer-approved alternate.
85,000 psi. At or before delivery , certify the pipe’s chemical composition and ensure that its carbon equivalency (CE) does not exceed 0.50 calculated as follows: CE = C+(Mn+Si+Cr+Mo+V)/6+(Ni+Cu)/15
marked to uniquely identify the load with a marking that is durable and legible. Use oil field pipe delivered in a magnetized condition for non-welded applications only. 550.2.2 Cast in Place Concrete Piles
Steel pile shells ............................................. ............................................................................................ 550.2.1 Steel shell end plates ............................................................................................................................. 506.2.2.2
or special provisions specify otherwise. Use seamless cylindrical tubes or cylindrical tubes with a straight or spiral welded seam. Revise 550.2.2(4) to require waterti ght welds for pile shell end plates.
exceed the pile outside diameter by more than 3/4 inch unless the plans show otherwise. Also ensure that shell end plate welds are watertight . 550.2.3 Precast Concrete Piles
following tolerances: Cross-sectional dimensions .................................... ............................................................... ............. +/- 1/8 inch Chamfers, miters, bevels, and radii ........................... ............................................................... .......... +/- 1/8 inch Pre-stressing st eel location .................................. ............................................................... ................ +/- 1/8 inch Length ............................................................... ....... +/- 1/8 inch per 10 feet o f length, not to exceed +/- 1 /2 inch Variation from true planeal ong the long axis ........... +/- 1 /8 inch per 10 feet of length, not to exceed +/- 1/2 inch
developed their full design strength. Support during transport at designated lifting or supporting points or provide additional support as t he fabricator recommends. Lif t at points the plans show using fabric or braided wire rope slings or other device that will not damag e the pile surface or corners. Store on supports positioned, at a minimum, at designated lifting or sup porting points.