Effective with the December 2018 Letting 343 2019 Standard Spec ifications Section 611 Catch Basins, Manholes, and Inlets
611.1Description
structures, made of concrete, brick masonry, or concrete brick or block masonry, with necessary reinforcement, metal frames, grates and lids, including require d excavating and backfilling.
611.2Materials
Mortar ........................................................ ............................................................................................... 519.2.3 Structural steel .............................................. ............................................................................................ 506.2.2 Miscellaneous metals .......................................... ..................................................................................... 506.2.3 Trench backfill ............................................... .............................................................................................. 608.2
501 as modified in 716. Provide QMP for class III ancillary concrete as specified in 716.
and rectangular structures. Manuf acture in a plant listed under precast concrete fabricators on the department's APL. Conform to the specified AASHTO materials requirements for th e structure specified except as follows: - Use concrete with 565 pounds or more cementitio us material pe r cubic yard. - The contractor may use cement conforming to 501.2.1 or may substitute for portl and cement a t the time of batching conforming to 501.2.6 for fly ash, 501.2.7 for slag, or 501.2.8 for other pozzolans. In either case the maximum total supplementary cementitious content is limited to 30 percent of the to tal cementitious content by weight. - For wet cast use air-entrained concrete with 7.0 percent +/- 1.5 percent air content.
611.3Construction
611.3.1 General
not backfill concrete brick or bl ock masonry, bri ck masonry, or precast concrete set on mortar beds until at least 3 days after completing the unit.
subject to revisions necessary to fit field conditions. The eng ineer may increase o r decrease the depth of catch basins, manholes, or in lets in order to adjust their i nlet or discharge elevations.
conforming to 608.2 .
manufacturer's recommended method . Do not dry stack adjustment rings. 611.3.2 Connections
type, and class as the sewer pipe, sewers, and conduit to which connections are made and that they conform to the same pertinent requirements.
wall and extend the pipe throug h the walls and beyond the outsi de surfaces of the walls a sufficient distance to allow for connections with conduits or sewers. Care fully construct th e masonry around them to prevent leakage around their outer surfaces.
seal around entering conduits.
Effective with the December 2018 Letting 344 2019 Standard Spec ifications 611.3.3 Frames, Grates, and Lids
otherwise as the plans show. Fi t or secure the grates and lids to the frames to eliminate rocking or chattering.
required to fit the adjoinings urfaces. If installed in concret e surfaces, set the frames or castings, and grout as necessary, as specified in 415.3.6.1 . Make sure the grates or lids are not in place while striking off and finishing the adjoining concrete.
450.3.2.9 , Place a 6-foot straightedge over the centerline of each frame parallel to the direction of traffic at the completion of the paving. Make a measurement at each side of the frame, average the 2 measurements. If this average is g reater than 5/8 inch, reset the frame to the correct plane and elevation. If this average is 5/8 inch or less but greater than 3/8 inch, the department will allow the frame to remain in place.
straightedge and average them. 611.3.4 Steps
611.3.5 Reconstructing Catch Basins, Manholes, and Inlets
the required lines and elevations the plans show, including the salvaging and resetting of existing covers, unless the contract provi des for new covers or other sa lvaged covers.
involved. 611.3.6 Covers for Catch Basins, Manholes, and Inlets 611.3.6.1 General
complete installation to the required elevation.
bid items, use covers stamped with "WISDOT COMMUNICATIONS" as t he plans show. 611.3.6.2 New Covers
grates, or lids, as the plans show, on both new and existing st ructures. 611.3.6.3 Salvaged Covers
way that prevents damaging the covers. If the contractor damages covers through its own operations then the contractor shall repl ace them at no expense to the department.
611.3.7 Adjusting Catch Basin, Manhole, and Inlet Covers
the required elevation. Remove the existing fixture, adjust the top of the existing stru cture, and reinstall the fixture. Support the fixture on a collar of concrete, brick masonry, concrete bri ck or block masonry, a precast concrete grade riser ring, or a grade adjustment ring from the department's APL, constructed to hold the covers firmly in place.
resurfacing projects, if the engineer allows, by using engineer -approved adjustment castings designed for the purpose.
beyond the shimming or grade adjus tment device, is a reconstruction and the contractor must comply with 611 for reconstruction of catch basins, manholes, and inle ts. 611.3.8 Clean Out
inlets, or similar structures c onstructed or reconstructed unde r the contract bef ore the engineer will accept the work. Remove materials in all of these structures de posited or lodged due to the contractor’s operations.
Effective with the December 2018 Letting 345 2019 Standard Spec ifications 611.4 Measurement
completed.
611.5Payment
611.5.1 General
items: ITEM NUMBER DESCRIPTION UNIT
611.0410 Reconstructing Catch Basins EACH
20 Reconstructing Manholes EACH
30 Reconstructing Inlets EACH
611.0500 - 0599 Manhole Covers (type) EACH
611.0600 - 0699 Inlet Covers (type) EACH
611.1000 - 1999 Catch Basins (dimensions) EACH
611.2000 - 2099 Manholes (dimensions) EACH
611.2100 - 2199 Manholes Comm unications (dimensions) EACH
611.2500 - 2699 Manholes Variable (type) (dimensions) EACH
611.3000 - 3499 Inlets (dimensions) EACH
611.3900 - 3999 Inlets Median (number of grates) EACH
611.8105 Adjusting Catch Basin Covers EACH
10 Adjusting Manhole Covers EACH
15 Adjusting Inlet Covers EACH
611.9705 Salvaged Manhole Covers EACH
10 Salvaged Inlet Covers EACH
611.5.2 Catch Basins, Manholes, and Inlets
materials, including masonry, c onduit and sewer connections, st eps, and other fittings; for excavating, backfilling, disposing of surplus material, and for cleaning ou t and restoring the work site; except that the department will pay for covers , including frames, grates an d lids separately.
manholes, or inlets constructed to depths not greater than one foot above or below the elevations, the plans show. Catch basins, manholes, or inlets that the engineer orders constructed to depths greater than one foot above or below the el evations the plans show as s pecified for extra work in 109.4 . 611.5.3 Reconstructing Catch Basins, Manholes, and Inlets
compensation for providing required materials, including masonr y and fittings; for salvaging and reinstalling existing covers, inc luding frames, grates, or lids ; for necessary excavation, backfilling, disposing of surplus material, and for cleaning out and restori ng the work site. 611.5.4 Manhole Covers and Inlet Covers
salvaging the existing covers; and for providing new covers, in cluding frames, grates or lids, and other required materials and for installing and adjusting each cover. Old covers removed remain the municipality's property. 611.5.5 Adjusting Catch Basin, Manhole, and Inlet Covers
full compensation for providing required materials, exclusive o f frames, grates, or lids available and designated for adjusting; and for removing, reinstalling and ad justing the covers. The contractor shall replace covers rendered unusabl e by the contractor’s operations , at no expense to the department. 611.5.6 Salvaged Manhole Covers and Inlet Covers
the existing cover including frames, grates, or lids; for cleaning, transporting, and s toring; for installing and adjusting; and for providing other required materials.
Effective with the December 2018 Letting 346 2019 Standard Spec ifications Section 612 Underdrains
612.1Description
designated pipes or drainage devices, and backfilling the trenc hes.
612.2Materials
612.2.1 General
unless the plans show or the spec ial provisions specify unperfo rated pipe.
here in 612.2 under the Pipe Under drain or Pipe Underdrain Unpe rforated bid items. 612.2.2 Corrugated Steel Pipe
perforations conforming to cla ss I. Use sheets not less than 0. 052 inch thick for 6- inch underdrains or 0.064 inch for 8-inch to 21-inch, inclusive, diameter underdrains.
approved wedging, clamping, or othe r fasteners, instead of bolts. 612.2.3 (Vacant) 612.2.4 Corrugated Aluminum Alloy Pipe
Use a sheet not less than 0.060 inch thick. Provide perforations conforming to the requirements for class I.
approved wedging, clamping, or othe r fasteners, instead of bolts. 612.2.5 Corrugated Polyethylene Drainage Pipe
and AASHTO M294, type CP with class 2 perforations. 612.2.6 Polyvinyl Chloride Drainage Pipe
612.2.7 Acrylonitrile-Butadiene-Styrene Drainage Pipe
do not apply the requirements fo r joint tightness. Use pipe per forated according to AASHTO M278, if perforated pipe is required. 612.2.8 Geotextile
polyethylene, or polyvinylidene chloride. Do not use slit film woven fabrics for th is work. The fabric must conform to the following requirements: TEST METHOD VALUE[1] Minimum grab tensile strength ASTM D4632 35 lb Apparent opening size ASTM D4751 No. 30 - 200 Minimum permittivity ___ 1.35 s-1 [1] All numerical values represent m inimum/maximum average roll values (i.e., the aver age of minimum test results on any roll in a lot sho uld conform to or exceed the mi nimum values in the table).
heat-bonded, resin -bonded, or combinati ons of these 3 types. Us e woven fabrics constructed from monofilament or multifilament yarns.
using geotextile wraps constructed from woven or non-woven fabr ic then tightly wrap and securely fix to the pipe.
612.2.9 Reinforced Concrete Apron Endwalls for Underdrain