SECTION 639 — Strain Poles for Overhead Signs

and Signal Assemblies

639.1General Description

This work includes furnishing and erecting overhead sign and signal support strain poles and steel wire strand cable according to this specification and the plans. Make concrete or steel strain poles at any one location within the project from the same material unless the plans designate a particular type for that location. Use timber strain poles only where designated on the plans. 639.1.01 Definitions General Provisions 101 through 150. 639.1.02 Related References

A.Standard Specifications
SECTION 500 — Concrete Structures
SECTION 636 — Highway Signs
SECTION 852 — Miscellaneous Steel Materials
SECTION 861 — Piling and Round Timber
SECTION 863 — Preservative Treatment of Timber Products
SECTION 865 — Manufacture of Prestressed Concrete Bridge Members
SECTION 915 — Mast Arm Assemblies
B.Referenced Documents

ASTM A 27 / A 27 M ATSM A 36 / A 36 M ASTM A 123 / A 123 M ASTM A 153 / A 153 M ASTM A 242 M ASTM A 595 ASTM A 709 (A 709 M) AASHTO LRFD Specifications for Structural Supports for Highway Signs, Luminaires, and Traffic Signals, with interims 639.1.03 Submittals Submit to the Engineer shop drawings for steel and prestressed concrete strain poles for review and approval. Submission should be made electronically in a portable document format (pdf) and include an index. Format all drawings to fit 11 in. x 17 in. (279 mm x 432 mm) paper. Present calculations to fit 8.5 in. x 11 in. (216 mm x 297 mm) paper. The submission shall be prepared and stamped by the Design Engineer who shall be registered as a Professional Engineer in the State of Georgia. 1125 1125 1125 1125 1125

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies

The Engineer will distribute submitted documents to the Bridge Engineer (SLTS@dot.ga.gov) for review and provide the State Traffic Operations Engineer with a copy of the transmittal letter. For installations governed only by a permit, and not a GDOT contract, drawing and calculation submission should be made directly to the Bridge Engineer with a copy to the District Permit Engineer. Design Strain poles shall be designed to the following wind speeds using a 1700 Mean Recurrence Interval (MRI) for the listed counties: • 150 mph: Bryan, Camden, Chatham, Effingham, Glynn, Liberty, McIntosh • 140 mph: Brantley, Bulloch, Charlton, Evans, Long, Screven, Tattnall, Wayne • 130 mph: Appling, Bacon, Brooks, Burke, Candler, Clay, Clinch, Decatur, Early, Echols, Emanuel, Grady, Jeff Davis, Jenkins, Lowndes, Miller, Pierce, Seminole, Thomas, Toombs, Ware • 120 mph: For all counties not listed above Strain poles shall be designed using the following criteria: • Fatigue Category 1 • Truck induced gusts included (required only for mast arm poles) • Galloping included (required only for mast arm poles)

639.2Materials

Ensure that materials meet the requirements of the following Specifications: Material Section Class A Concrete 500 Class B Concrete 500 Class AAA Concrete 500 Timber Poles 861.2.02 Seasoning and Preservative Treatment 863.2.01 Steel Wire Strand Cable 915.2.02 Guys and Anchors Per Plans 1126 1126 1126 1126 1126

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies
A.Steel Strain Poles

Use shafts for steel strain poles fabricated of steel that conforms to one or more of the following: • ASTM A 242/A 242 M • ASTM A 709 Grade 50W (A 709 M Grade 345W) • ASTM A 595 • AISI 1015 • AISI 1020 • SAE: 1015 Ensure that the steel characteristics or strength do not change significantly from welding.

1.Shaft

Use the appropriate shape of shaft which is a continuous taper and is constructed of corrosion resistant steel, unless otherwise specified, to the dimensions required for the specified classification type. Form the shaft from one piece with one electrically welded longitudinal joint and no intermediate horizontal joints.

2.Pole

Use a pole with a mill certified yield strength of at least 48,000 psi (331 MPa). After forming and welding the pole, the shaft may be longitudinally cold rolled under enough pressure to flatten the shaft to conform to the required yield strength. For Type IV steel strain poles, ensure that the wall thickness is at least 3 gauge or 0.25 in. (6 mm).

3.Traffic Signal Strain Poles

Assemble traffic signal strain poles as follows:

a.Weld a handhole assembly, curved on the front to follow the contour of the pole, into the shaft near

the base.

b.Include a tapped hole on the handhole reinforcing frame to accommodate the grounding lug.
c.Secure the cover to the frame using at least two screws.
d.Weld a J-hook wire support inside near the top of the shaft for the poles.
e.If an overhead power source is shown, use a clamp and clevis device to connect the wire to the pole and

provide a weatherproof wire inlet close to the attachment. Conceal the other wiring to and from the controllers within the pole. For traffic signal strain poles with mounted controller cabinets, provide a 2 in. (50 mm) half coupling wire inlet to mount the controller cabinet on the designated pole. Ensure that the location where cable enters the wire inlets at the top of the traffic signal strainpoles has a neat design and appearance. Do not use junction boxes at the top of poles to facilitate cable entrances.

4.Grounding

Provide a 0.5 in (13 mm) approved grounding connector in the shaft. Equip the top of the shaft with a removable cap held securely in place. Hot-dip galvanize the shaft according to ASTM A 123/A 123 M unless otherwise specified.

5.Base

Secure to the lower end of the shaft a one-piece cast steel base or a one-piece flat plate base that meets the requirements of ASTM A 27, Grade 65-35/A27 M Grade 450-240, or A 36/ A 36 M, as required.

a.Ensure that the base, after welding, develops the full strength of the adjacent shaft section to

resist bending.

b.Attach the base to the concrete foundation with four bolts according to this subsection.
c.Provide four removable cast or pressed steel ornamental covers with each base and attach it to the base.

1127 1127 1127 1127 1127

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies
6.Anchor Bolts

Furnish each pole with four anchor bolts of the size required in the manufacturer’s Shop Drawings. Ensure that the anchor bolts meet the requirements of Subsection 852.2.02. Galvanize the threaded portions according to ASTM A 153/A 153 M and the Plan details.

B.Prestressed Concrete Strain Poles

Use shafts for these poles that comply with Subsection 865.2.01.B, except give the poles a steel trowel finish on the unformed side and any required pointing to eliminate air and water holes left by the steel forms. Use Class AAA concrete. Use a marking tool to identify the pole class and height or cast it with a die in the front face of the pole to produce letters and numbers at least 2 in. (50 mm) high and wide.

C.Miscellaneous Hardware

Use hardware for steel and concrete strain poles with these features:

1.The steel required to fabricate other structural components is weldable and conforms physically and

chemically to applicable ASTM specifications.

2.Nuts, bolts, and screws conform to these diameter requirements:

• If diameters are less than 0.5 in. (13 mm), the hardware is passivated stainless steel that meets the requirements of AISI 300, commercial grade. • If diameters are 0.5 in. (13 mm) and larger, the hardware conforms to ASTM physical and chemical qualifications that ensure strength commensurate with the parts being connected. Galvanize the hardware according to ASTM A 153/A 153 M.

3.Use galvanized steel ground rods 5/8 in. (16 mm) diameter, ± 1/16 in., (± 1.6 mm) and 8 ft. (2.4 m) long unless

otherwise specified. Ensure that galvanizing has a coating of at least 2 oz/ft.² (610 g/m²) according to ASTM A 153/A 153 M.

D.Strain Poles for ATMS Applications

Provide poles for supporting CCTV, VDS, and microwave radar detection devices that meet the following design specifications: • Limited to a live horizontal deflection at the top equal to or less than 1% of pole height in a 50 mph wind, with a design load of four static cameras and one movable camera. • Torsional deflection limited to a 1 degree, maximum. Install mounting brackets, as illustrated on the plans, which are galvanized steel and are compatible with the mounting design of the specified cameras and pan/tilt devices and are affixed to the pole to prohibit rotation. Install all wiring internal up to the camera mounting bracket with no external conduit on the pole. Provide a weatherproof wiring access point or handhole on the pole. 639.2.01 Delivery, Storage, and Handling General Provisions 101 through 150.

639.3Construction Requirements

639.3.01 Personnel General Provisions 101 through 150. 639.3.02 Equipment General Provisions 101 through 150. 639.3.03 Preparation General Provisions 101 through 150. 1128 1128 1128 1128 1128

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies

639.3.04 Fabrication General Provisions 101 through 150. 639.3.05 Construction

A.Timber Poles

Construct the following according to the plan:

1.Excavate the hole to the proper diameter and depth.
2.Erect the pole to an out-of-plumb position with its base resting on the bottom of the hole.

Hold the pole in its out-of-plumb position until the cavity around the pole is filled with Class B or better concrete and is set and cured for at least 7 days. Then, apply tension to the pole.

B.Steel Poles

Construct the foundations for steel poles as follows:

1.Excavate a hole the size and depth shown on the plans. Remove and dispose of excavated material as

directed by the Engineer.

2.Place the specified type and size anchor bolts according to the pole manufacturer’s recommendations. Hold

these securely by a template to ensure proper position in the completed foundation. NOTE: Never attempt to realign the anchor bolts after pouring the foundation.

3.Place conduits in foundations, orient them to accommodate service cables, and securely hold them to avoid

displacement.

4.Pour Class A concrete into the excavated area to the following depths:
a.First pour against undisturbed earth up to 4 in. (100 mm) below the finished ground line.
b.Then, using an approved form, continue to pour to the finished top of the foundation elevation,

as specified.

5.Chamfer the top and formed portions of the foundation edges.
6.Give a Type III finish to all portions of the foundation above finished grade down to at least 2 in. (50 mm)

below finished grade, according to Subsection 500.3.05.AB.4, Type III—Special Surface Coating Finish.

C.Prestressed Concrete Poles

Drill round holes or dig square holes for prestressed concrete poles.

1.Do not disturb the natural ground adjacent to the foundation more than necessary to construct the foundation.
2.Excavate to the lines and elevations shown on the Plans or established by the Engineer.
a.Dispose of the excavated materials as directed.
b.Regrade and grass the disturbed areas to match the contiguous area.
3.Backfill according to the Plans. Furnish and place Class A concrete, as required, according to the applicable

portions of Section 500 and Plan details.

4.When leaving lifting eyes or loops on the pole to facilitate handling and erecting, burn them off and patch

them after erecting.

D.Ground Rods

Install ground rods for steel and prestressed concrete strain poles adjacent to the strain pole base as follows:

1.Vertically drive the single ground rods 8 ft. (2.4 m) long until the top of the rod is at least 12 in. (300 mm) below

the finished ground.

2.Use ground rod clamps to attach a length of No. . 6 AWG solid copper wire to the ground rod. Connect the

wire to the grounding nut of the strain pole base.

3.When penetration cannot be obtained in the above steps, place three parallel ground rods at least 6 ft. (1.8 m)

center-to-center in a horizontal pattern and at least 12 in. (300 mm) below the finished ground. 11291129112911291129

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies

Join the rods and connect them to the grounding nut of the pole base with No. 6 AWG solid copper wire and

ground rod clamps.

E.Rake

Use the proper rake to erect the pole so that the pole will be plumb after the load is applied.

F.Erecting Cable

Follow these steps to erect the cable:

1.Install the top cable 6 in. (150 mm) from the top of the pole, unless otherwise indicated on the plans.
2.Install the bottom cable no more than 5 ft. (1.5 m) from the top of the pole according to plan details.
3.Secure the cable to each pole as shown on the Plans. Use preformed cable grips instead of cable clamps,

if necessary.

4.Apply enough tension to pull timber poles toward each other past the plumb position by one degree.

639.3.06 Quality Acceptance

General Provisions 101 through 150.

639.3.07 Contractor Warranty and Maintenance

General Provisions 101 through 150.

639.4Measurement

Highway signs are measured and paid for under Section 636.

A.Treated Timber Poles

Treated timber poles of the class and length specified are measured by the number of units installed, including

guys, anchors, and hardware.

B.Steel Cable

Steel cable of the specified size are measured by the linear foot (meter), complete in place.

C.Steel Strain Poles

Steel strain poles are classified and measured for payment by each unit and by type according to the

following table:

Type Span Length

I Less than 60 ft. (18 m)

II 60 to 95 ft. (18 m to 29 m)

III Greater than 95 ft. (29 m)

IV Traffic signal strain pole

D.Prestressed Concrete Strain Poles

Prestressed concrete strain poles are measured for payment by each unit and pole type as specified in the

above table.

639.4.01 Limits

General Provisions 101 through 150. 11301130113011301130

SECTION 639 — Strain Poles for Overhead Signs and Signal Assemblies

639.5Payment

A.Treated Timber Poles

Treated timber poles of the class and length specified will be paid for at the Contract Price bid per each. Payment

is full compensation for poles, concrete encasements, excavation for pole and anchor holes, temporary pole

alignment, bracing, guys, and items to complete the Work.

B.Steel Strain Poles

Steel strain poles of the type specified, complete in place and accepted, including foundation, backfill, erection,

and necessary re-grassing will be paid for at the Contract Unit price bid for each pole of each type.

C.Prestressed Concrete Strain Poles

Prestressed concrete strain poles of the type specified, complete in place and accepted, including foundation,

backfill, erection, and necessary re-grassing will be paid for at the Contract Unit Price bid for each pole of

each type.

When neither concrete nor steel strain poles are specified, either type is acceptable. Measurement is specified in

Subsections 639.4.C. or 639.4.D. The payment item is Strain Poles, Type___.

D.Steel Cable

Steel cable complete in place and accepted will be paid for at the Contract Unit Price bid per linear foot (meter) of

each specified diameter. Payment is full compensation for furnishing and erecting the cable and for providing

hardware including thimbles, but not hardware that is a part of the pole.

Payment will be made under:

Item No. 639 Treated timber pole class___, __ ft. (m) Per each

Item No. 639 Steel strain pole, type____ Per each

Item No. 639 Prestressed concrete strain pole, type___ Per each

Item No. 639 Strain Poles, Type___ Per each

Item No. 639 Steel strand wire cable___in. (mm) Per linear foot (meter)

639.5.01 Adjustments

General Provisions 101 through 150.. 1131 1131 1131 1131 1131