SECTION 939 — Communications and Electronic Equipment
939.1General Description
Furnish, install, test, and provide warranty and training for communications and electronic equipment and materials as specified herein and shown in the Contract documents. 939.1.01 Definitions, Acronyms, and Abbreviations
A.Definitions
1.Field Cabinet, Type 1: a modification of the JC Standard ITS Cabinet Housing #2.
2.Field Cabinet, Type 2: JC Standard ITS Cabinet Housing #2.
3.Field Cabinet, Type 3: JC Standard ITS Cabinet Housing #1.
4.Field Cabinet, Type 4: JC Standard ITS Cabinet Housing #3.
5.Field Switch, Type A: Layer 2, minimum 6 copper ports and 2 SFP 1 Gbps fiber ports.
6.Field Switch, Type B: Layer 2, minimum 6 copper ports and 3 SFP 1 Gbps fiber ports.
7.Field Switch, Type C: Layer 2, minimum 1 copper port and 7 SFP 1 Gbps fiber ports.
8.Field Switch, Type D: Layer 2 or 3 upgradeable, minimum 4 copper ports and 4 dual-purpose
1 Gbps ports.
9.Field Switch, Type E: Layer 2 or 3 upgradeable, minimum 8 copper ports and 4 dual-purpose
1 Gbps ports.
10.Routing Switch, Hub, Type A: Layer 3, minimum 48 ports at 1G/10G/25 Gbps SFP+ and 6 ports at 40G/
100 Gbps QSFP28.
11.Routing Switch, Hub, Type B: Layer 3, minimum 48 ports at 10/100/1 Gbps copper and 4 ports at
1 Gbps SFP.
12.SFP Fiber Module, Type 1: LX optics for shorter distances.
13.SFP Fiber Module, Type 2: ZX optics for longer distances.
14.Security Lock: an electronic lock system that controls access to a field cabinet, and the cylinder can retrofit
existing field cabinet mechanical lock hardware.
B.Acronyms and Abbreviations
Refer to Sections 101.01 and 942.1.01.B for a list of acronyms, abbreviations, and terminology used in this section. 939.1.02 Related References
1.Refer to Section 942.1.02.B for a list of standards and documents referenced in this section.
939.1.03 Submittals Refer to Section 942.1.04 for submittal requirements. Requirements for communications and electronic equipment materials are specified herein.
939.2Materials
939.2.01 General
A.Comply with ISO 9001 or Six Sigma quality manufacturing requirements.
B.Provide only equipment and materials that are new and of like kind and function provided by one
manufacturer, using the same model, part number, revision, and firmware as shown and specified in the Contract documents. 939.2.02 Field Switch Requirements
A.General
1.Provide one or more of the field switch types listed in Table 1 as specified in the Contract documents.
Table 1 – Field Switch Types Type Layer Capability Ethernet Port Configuration Type A Layer 2 Minimum 8 ports total including 2 Gigabit-Ethernet SFP ports and 6 10/100Base-T/TX ports Type B Layer 2 Minimum 9 ports total including 3 Gigabit-Ethernet SFP ports and 6 10/100Base-T/TX ports Type C Layer 2 Minimum 8 ports total including 7 Gigabit-Ethernet SFP ports and 1 10/100Base-T/TX port Type D Layer 2 or Layer 3 upgradeable Minimum 8 ports total including 4 dual-purpose uplink or downlink ports that can be used for 10/100/1000BASE-T/TX ports or 100/1000 Mbps SFP ports, and 4 10/100/1000Base-T/TX ports Type E Layer 2 or Layer 3 upgradeable Minimum 12 ports total including: 4 dual-purpose uplink or downlink ports that can be used for 10/100/1000Base-T/TX ports or 100/1000 Mbps SFP ports, and 8 10/100/1000Base-T/TX ports
2.Provide field and routing switches that are compatible with the existing GDOT network by support of
features and implementation of common standards that enable switches to work together and minimize integration effort. 1961
SECTION 939 — Communications and Electronic Equipment
3.Provide field switches with the following interfaces:
a.Provide fiber ports with 1000BaseSFP slot or 100/1000BaseSFP slot.
b.Provide 10/100Base-T(X) or 10/100/1000Base-T(TX) RJ-45 ports with auto negotiation speed and capable
of being manually set to half-duplex or full-duplex.
c.Provide console port along with any adapter cables as needed and approved by the Department.
d.Provide LED indicators including power on/off and network status per port (transmit, receive, link,
and speed).
4.Provide field switch that can operate with non-blocking, store and forward, switching at full wire speed.
5.Provide field switch that supports detecting and shutting down one-way link failures using auto-negotiation.
6.Provide field switch with a minimum MTBF of 200,000 hours using Telcordia SR-332, Method 1, Case 3 or
MIL-HDBK-217F standards.
7.Provide field switch that complies with IEEE 802.3 for 10Base-T standard specifications.
8.Provide field switch that complies with IEEE 802.3u for 100Base-T(X) standard specifications.
9.Provide field switch that complies with IEEE 802.3ab for 1000Base-T(X) standard specifications.
10.Provide field switch that complies with IEEE 802.3z for 1000Base-X standard specifications.
C.Network Capabilities and Features
1.Provide field switch that supports multicast with IGMP v1/v2/v3 snooping and IGMP-filtering.
2.Provide field switch that complies with IEEE 802.3x (Flow Control) standard.
3.Provide field switch that complies with IEEE 802.1p (Class of Service or Priority Queuing) standard.
4.Provide field switch that complies with IEEE 802.1Q (VLAN tagging) standard per port.
5.Provide field switch that complies with IEEE 802.1D (Spanning Tree Protocol) and IEEE 802.1w (Rapid
Spanning Tree Protocol) standards.
6.Provide field switch that complies with IEEE 802.3ad (Link Aggregation or Port Trunk) standard for a minimum
of two groups of four ports.
D.Security
1.Provide field switch that can be configured for static MAC address access.
2.Provide field switch that can disable automatic address learning per ports; known hereinafter as Secure Port.
Secure Ports only forward statically configured MAC addresses.
3.Provide field switch that can trap and provide an alarm upon any unauthorized MAC address and shutdown.
Require administrator to manually reset the port before communications are permitted.
4.Provide field switch that complies with IEEE 802.1X Port Access Authentication.
5.Provide field switch that supports HTTP and HTTPS.
6.Provide field switch that supports SSL.
1962
SECTION 939 — Communications and Electronic Equipment
E.Network Management
1.Provide network management capabilities that are compatible with the existing GDOT network management
consisting of Cisco Prime centralized enterprise management software supporting remote management.
2.Provide field switch that is password manageable with a minimum of one read-only profile and one full
administration profile.
3.Provide field switch that fully implements SNMP v1/v2/v3.
4.Provide field switch that implements LLDP as defined in IEEE 802.1ab (Station and Media Access Control
Connectivity Discovery).
5.Provide field switch that fully implements RMON I statistics, history, alarms, and events objects.
6.Provide field switch that can mirror any port to any other port within the field switch.
7.Provide field switch that can be managed remotely by an enterprise software/program for configuration,
reporting, updates, and monitoring of alarms.
8.Provide field switch with environment monitoring capabilities.
9.Provide management capabilities via a serial maintenance/console serial port (local) and over the
network (remote).
10.Provide field switch that supports HTTP (Embedded Web Server) with SSL.
11.Provide field switch that fully implements RFC 783 (TFTP) to allow remote firmware upgrades.
F.Additional Requirements for Field Switch Types D and E
1.Provide, in the quantity specified in the Contract documents, Gigabit-Ethernet Combo ports, where each
Gigabit-Ethernet Combo port is defined as a single interface that can be used as a 10/100/1000Base-T/TX ports or 100/1000Base SFP GBIC socket.
2.Provide a card slot for a field removable SD read-write memory card (included) that can store switch operating
system modules and switch configuration modules and is addressable/manageable from the switch’s management interface and built-in memory system.
3.Provide field switch that can boot from and load configuration from the removable memory card slot or from
the built-in memory, as defined by the user.
4.Provide field switch that allows push/pull of switch operating system modules and switch configuration
settings from the GDOT network management system.
5.Provide field switch that can convert from Layer 2 to Layer 3 switch and routing protocols, as specified in
Section 939.2.03, with only a change in the switch operating system or license.
G.Mechanical and Cabling
1.Provide field switches that are capable of rack mounting and DIN rail panel mounting. Rack-mounted DIN rails
may be installed if cabinet space is available. Shelf mounting is not permitted.
2.Provide hardware and materials for mounting the field switch within the field cabinet.
3.Provide rubber dust caps or covers with insertion and removal handles that completely seal the port opening
for unused copper and SFP ports.
4.Provide field switch with a fan-less (no fan) design.
1963
SECTION 939 — Communications and Electronic Equipment
H.Electrical
1.Provide field switch that is capable of operating over minimum input voltage range of 108 VAC to 132 VAC at
50/60 Hz (±5%, maximum).
2.Provide field switch with power conversion as specified herein and provide regulation necessary to support
electronics operation.
3.Provide field switch that complies with IEC EN 61000-4-5 surge immunity for network equipment.
4.Provide power transformers with a “fastening mechanism.” No plug-in types are permitted. Corded
transformers shall be mountable with neatly secured power cords.
I.Environmental
1.Provide hardened field switch including power supply that comply with NEMA TS 2 Sections 2.1.7, 2.1.8, and
2.1.9 temperature, humidity, vibration, and shock testing requirements.
2.Comply with FCC Part 15 emission standard and FCC Public Notice 2019-01.
939.2.03 Routing Switch Requirements
A.General
1.Provide one or more of the routing switch types listed in Table 2 as specified in the Contract documents.
Table 2 – Routing Switch Types Type Layer Capability Ethernet Port Configuration Type A Layer 3 Providing a minimum 48 1/10/25 Gbps SFP+ ports + 6 40/100 Gbps QSFP28 uplink ports per switch Type B Layer 3 Providing a minimum 48 10/100/1000 Ethernet copper ports + 4 SFP 1 Gbps ports per switch, stackable
2.Provide routing switches that are compatible with the existing GDOT routing network consisting of Cisco
Nexus 93180YC-FX Layer 3 routing switch (Type A) and Cisco Catalyst 2960XR Layer 3 routing switch (Type B) that can be managed by the Department’s existing network management software.
3.Populate routing switch with optical SFPs meeting the minimum SFP requirements in Section 939.2.04 and as
required in the Contract documents.
4.Provide routing switch with a minimum MTBF of 200,000 hours using Telcordia SR-332, latest version, or
MIL-HDBK-217J standards.
5.Provide routing switches for up to 4,096 VLANs.
6.. Provide routing switch where modules are hot-swappable.
7.Provide routing switch that can be EIA 19 in (483 mm) rack mounted (one rack unit per routing switch, typical).
B.Network Standards and Protocols
1.Provide network that supports Layer 2 and 2+ protocols specified in Section 939.2.02.
2.Provide network that supports additional network Layer 3 protocols as follows:
a.IPv4 and IPv6.
b.Full implementation of IGMP v1/v2/v3.
c.TACACS Plus (+).
1964
SECTION 939 — Communications and Electronic Equipment
d.RADIUS protocol.
e.Full implementation of RIP.
f.Full support for BGP.
g.Full implementation of OSPF protocol.
h.Full implementation of GMRP.
i.Full implementation of GVRP.
j.Full implementation of PIM Sparse Mode.
k.Full implementation of VRRP.
C.Mechanical and Cabling
1.Provide routing switches that are rack mountable.
2.Provide hardware and materials for mounting within the equipment rack that are corrosion resistant.
3.Provide rubber dust caps or covers with insertion and removal handles that completely seal the port opening
for unused copper and SFP/QSFP ports.
D.Electrical
1.Provide field switch that can operate over a minimum input voltage range of 108 VAC to 132 VAC at 50/60 Hz
(±5%, maximum).
2.Provide field switch that complies with IEC EN 61000-4-5 surge immunity testing requirements.
3.Provide routing switch with dual redundant power supplies and fans, N+1 configuration, hot swappable, and
configured for 120 VAC service.
E.Environmental
1.Provide routing switch with power supply that meets following minimum ambient temperature and humidity
requirements:
a.Temperature range from +23°F through +113°F (−5°C to +45°C).
b.Relative humidity from 10% through 95%, noncondensing.
c.Comply with NEMA TS 2 Sections 2.1.8 and 2.1.9 vibration and shock testing requirements.
2.Comply with FCC Part 15 emission standard and FCC Public Notice 2019-01.
1965
SECTION 939 — Communications and Electronic Equipment
939.2.04 SFP Fiber Module Requirements
A.General
1.Provide SM, dual-fiber SFPs with LC connectors.
2.Provide the following types of full duplex, SFP fiber optical modules as shown in the Contract documents or
as required:
a.Type 1: LX/LH optics for single-mode fiber that is >6.2 miles (10 km) in length (under ideal conditions).
b.Type 2: ZX optics for single-mode fiber that is >43 miles (70 km) in length (under ideal conditions).
3.Provide SFPs that comply with IEEE 802.3x, 1000Base-LX/LH and 1000Base-ZX standards.
4.Provide fiber optic patch cords as specified in Section 935.2.01.G with integral optical attenuators if required
for optical power control per the field switch manufacturer’s recommendations.
5.Provide SFPs that are 100% compatible with the field switch or network device in which the SFP is inserted,
including any serial number or other identifying information. Only demonstrated proven SFPs that do not
require non-default, switch configuration settings are permitted.
6.Provide SFPs that are hot-swappable.
7.Provide SFP that operates as its own switched port.
8.Provide a quantity of fiber optic patch cords that matches the number of populated SFP ports on the field
switch, in accordance with Section 935.2.01.G, with ST connectors on one end (at the FPP/FDU) and an LC
connector on the other end (at the field switch).
B.Environmental
Provide SFPs with extended temperature capabilities meeting the following minimum requirements:
1.Ambient temperature range from +23°F through +185°F (−5°C through +85°C).
2.Relative humidity from 10% through 95%, non-condensing.
939.2.05 Network Patch Cord Requirements
C.General
1.Provide field switch patch cords that meet ANSI/TIA requirements for Category 6, four-pair unshielded twisted
pair cabling with stranded conductors and RJ-45 connectors.
2.Provide network patch cords that are factory assembled, connectorized, and certified by the manufacturer to
meet the performance standards specified herein.
3.Provide network patch cords that comply with TIA-568-C.2 and UL 444 standards.
4.Provide network patch cords with eight (four STP) insulated No. 22 to No. 24 AWG, solid bare copper
conductors arranged in four color-coded twisted-pairs.
5.Provide network patch cords with modular RJ-45 male connectors with eight-position non-keyed and eight
gold anodized pins.
6.Provide network patch cord connectors that incorporate mechanical cable strain relief and protective boots.
7.Provide network patch cords that characterize to 600 MHz and design margin (headroom) beyond standard
Near-End Crosstalk, Power Sum NEXT, Attenuation-to-Crosswalk Ratio, and Power Sum ACR. 1966
SECTION 939 — Communications and Electronic Equipment
8.Provide network patch cords with lengths of patching from field switch to equipment inside the field cabinet or
equipment rack without strain. Provide custom or standard lengths as required or needed based on final
equipment layout and configuration that permits future movement of equipment within the field cabinet or
equipment rack.
9.Provide network patch cord that is riser-rated.
939.2.06 Field Cabinet Requirements
A.General
1.Provide one or more of the field cabinet types listed in Table 3 as specified in the Contract documents.
Table 3 – Field Cabinet Types and Configuration
GDOT
Type
Joint Committee ITS
Cabinet Standard
Minimum Cabinet Dimension Range Number of
Doors
Height Width Depth
Type 1 Modified ITS Cabinet
Housing #2
30 in. to 36 in.
(0.76 m to 0.91 m)
23 in. to 26 in.
(0.58 m to 0.66 m)
18 in. to 24 in.
(0.46 m to 0.61 m)
Type 2 ITS Cabinet Housing #2 44 in. to 47 in.
(1.12 m to 1.20 m)
23 in. to 26 in.
(0.58 m to 0.66 m)
18 in. to 24 in.
0.46 m to 0.61 m)
Type 3 ITS Cabinet Housing #1 64 in. to 67 in.
(1.62 m to 1.70 m)
23 in. to 26 in.
(0.58 m to 0.66 m)
24 in. to 30 in.
(0.61 m to 0.76 m)
Type 4 ITS Cabinet Housing #3 64 in. to 67 in.
(1.62 m to 1.70 m)
44 in. to 46 in.
(1.12 m to 1.17 m)
24 in. to 30 in.
(0.61 m to 0.76 m)
2.Unless otherwise specified in the Contract documents or directed and approved by the Department, construct
all ITS cabinet (field cabinet) housing assemblies in conformance with this section and the JC ITS Cabinet
Standard Specifications for Roadside Cabinets. Do not include with the field cabinet housing the following:
a.Police panel and associated wiring.
b.Power distribution assembly and associated flasher units, and signal power contactor.
c.DC power distribution assembly (12 VDC and 24 VDC).
d.Input file and associated sensor units, isolator units, and serial interface unit.
e.Output file and associated auxiliary monitor unit, serial interface unit, transfer relay unit, and switch
pack unit.
f.Field cabinet monitor unit assembly.
g.Serial and control bus assemblies and wiring.
1967
SECTION 939 — Communications and Electronic Equipment
3.Mount field cabinets in the following configurations:
a.Unless otherwise specified in the Contract documents, configure Type 1 and Type 2 field cabinet housing
assemblies for pole mounting and Type 3 and Type 4 field cabinet housing assemblies for ground or
base-mounting.
b.Reinforce the holes for pole mounting with metal plates of adequate size and strength welded
longitudinally across the inside depth of the field cabinet.
c.Where ground or base-mounting of field cabinets is specified, make the field cabinet bottom open and
provide an approved concrete pad for mounting the field cabinet along with technician pad in front and
back of cabinet doors and base mounting adapter, in accordance with Section 647 and the standard
detail drawings.
B.Field Cabinet Components
1.Equip all field cabinet housings with the standard EIA 19 in (483 mm) rack cage as described in the JC ITS
Cabinet Standard Specifications and as follows:
a.Do not use unistruts or other rail types.
b.For Types 1, 2 and 3, equip field cabinet housings with the standard EIA 19 in. (483 mm) rack cage.
c.For Type 4, equip field cabinet housings with two standard EIA 19 in. (483 mm) rack cages.
2.Provide field cabinet with side mounting panel meeting the following requirements:
a.Fabricate side mounting panels as described in the JC ITS Cabinet Standard Specifications for J Panels.
b.Do not provide pre-punched terminal block/bar or component mounting holes, except holes for mounting
the side panel to the rack cage.
c.In all field cabinet types provide one side panel on one side of each rack cage that are the full depth of the
rack cage and the rack cage height less 2 in (50 mm) at the top and bottom.
3.Provide field cabinet with cabinet shelf meeting the following requirements:
a.Provide perforated and ventilated shelf meeting the following minimum requirements:
i.Telescoping guides to allow full extension from the rack cage.
ii. Construction that supports a weight of 25 lb. (11 kg) when extended.
iii. A minimum non-slip work area measuring 12 in. (304 mm) by 12 in. (304 mm).
b.For Types 2 and 3, equip field cabinet with one cabinet-sliding internal shelf.
c.For Type 4, equip field cabinet with two sliding internal shelves.
4.Provide field cabinet with document pouch meeting the following requirements:
a.Provide a plastic documentation pouch that is side-opening, resealable, opaque, and of a heavy-duty
plastic material to store the field cabinet and equipment documentation.
b.Provide a pouch that has metal or hard-plastic reinforced holes for hanging from hooks included on the
field cabinet door.
c.Provide a pouch has the size and strength to hold 200 sheets of 8.5 in. (215 mm) by 11 in.
(279 mm) paper.
d.Provide field cabinets with metal hooks welded to the inside of the front cabinet door, for hanging the
plastic documentation pouch securely when opening and closing the front cabinet door. 1968
SECTION 939 — Communications and Electronic Equipment
5.Provide field cabinet with wiring, conductors, and terminal blocks that meet the following requirements:
a.Provide component mounting DIN rail meeting the following requirements:
i.Mount all 120 VAC service entrance, power distribution, grounding, and surge protection components
on standard DIN rails mounted on recessed rack mounted panels or on rack side panels as shown in
the standard detail drawings. Devices include terminal blocks, circuit breakers, and surge protection
devices. Other components and devices that may be DIN rail mounted include network switches,
power supplies, and PoE injectors.
ii. Provide 1.38 in. (35 mm) wide by 0.3 in. (7.5 mm) high by 0.04 in (1 mm) thick standard DIN rails
perforated and cut to length for flexible mounting.
iii. Provide DIN rail that is burr free with no sharp edges or deformation from the standard profile.
iv. Provide DIN rail that complies with IEC EN 50022 (NS35), IEC EN 60715, and DIN 46277.
v.Provide nut, bolt, and start washers to mount to panel for low resistance electrical connection.
vi. Provide an anti-corrosion paste to provide a solid and long-lasting electrical connection between the
DIN rail and the mounting panel.
b.Provide terminal blocks meeting the following requirements:
i.Use terminal blocks with voltage and current ratings greater than the voltage and current ratings of
the wires that are terminated on the blocks.
ii. Terminate conductors on terminal blocks using insulated terminal lugs large enough to accommodate
the conductor to be terminated.
iii. Terminate field wiring terminal block screws using a terminal ring lug for termination when two or
more conductors are terminated.
iv. Use metallic terminal block connection hardware and components that are non-ferrous copper or
nickel/tin-plated copper alloy or equivalent.
v.Provide terminal blocks and wires that comply with the following colors:
Black – Line
White – Neutral
Green or Green/Yellow – Ground
vi. Provide a ground terminal that is the same size and pitch as the power terminals and provides
positive electrical and mechanical connection to the mounting rail.
vii. Provide terminal blocks that comply with UL 1059.
viii. Provide terminal blocks that are capable of being DIN-rail mounted.
ix. Provide the type and quantity of terminals as shown in the Contract documents.
c.Provide service entrance terminal blocks meeting the following requirements:
i.Make the terminal block for the 120 VAC field cabinet service entrance a 0.39 in. (10 mm) single level
screw type device.
ii. Provide a terminal block that accommodates No. 18 to No. 4 AWG wiring for terminating electrical
inputs and outputs. 1969
SECTION 939 — Communications and Electronic Equipment
d.Provide distribution terminal blocks meeting the following requirements:
i.Make the terminal blocks for distribution of 120 VAC and ground a 0.24 in. (6 mm) single level screw
type located on the protected side of the power service panel assembly.
ii. Provide terminal block that accommodates No. 22 to No. 6 AWG wiring and provide in colors as
specified herein.
e.Provide circuit breakers meeting the following requirements:
i.Provide enclosed, thermal magnetic molded case circuit breakers of the types, sizes, and quantities
listed in the Contract documents.
ii. Provide a design that allows for an additional three circuit breakers.
iii. Provide two-pole (2P) breakers for 120/240 VAC and single-pole (1P) for 120 VAC single-phase
operating voltages.
iv. Provide molded case circuit breakers that comply with and are listed with UL 489.
v.Provide molded case circuit breakers that comply with NEMA AB-1.
vi. Provide circuit breakers that have the amperage rating indicated on the face of the breaker or handle.
vii. Provide circuit breakers that have a quick-make, quick-break over center toggle-type mechanism and
a position between “ON” and “OFF” when tripped automatically.
viii. Provide circuit breakers that are 120 VAC rated with a minimum symmetrical interrupting short circuit
capacity of 10 kA.
ix. Use only circuit breakers that are DIN rail mounted.
f.Provide fuses meeting the following requirements:
i.Provide DIN rail-mounted switch or disconnect type fuse holders and fuses for low voltage AC and
DC circuits in the proper capacity and configured.
ii. Provide fuse with size rating labeled on the holder or on the panel adjacent to the holder.
g.Provide end brackets and spacers meeting the following requirements:
i.Provide screw-clamp end brackets for DIN rail mounting.
ii. Provide spacers or dividers between terminal blocks and other components as shown in the Contract
documents for visual separation.
iii. Provide spacers that snap on to DIN rail that are approximately 0.20 in. (5 mm) to 0.71 in. (18 mm)
thick and match the size of the terminals they separate.
h.Provide safety cover meeting the following requirements:
i.Provide safety covers on terminal blocks to prevent contact with exposed conductors or any metallic
components. This cover will provide electrical and visual separation between terminal blocks and
other rail-mounted devices.
ii. Provide safety covers that are approximately 0.08 in. (2 mm) thick and sized to match the terminal
blocks they protect or separate.
i.Provide internal wiring meeting the following requirements:
i.Provide insulated wiring that is appropriately sized between terminal blocks and attached devices.
1970
SECTION 939 — Communications and Electronic Equipment
ii. Utilize THHN-THWN, stranded, copper wiring for internal branch circuits. Wire size shall be compliant
with the NEC.
iii. Use a minimum No. 12 AWG grounding of each SPD, or larger if recommended by the SPD
manufacturer or indicated on the Contract documents.
iv. Use insulated green wire to connect the ground wire directly to the ground terminals.
v.Do not splice together different device grounding wires including surge protectors.
j.Provide GFI service outlet meeting the following requirements:
i.Provide one duplex, NEMA 15A, 5-15R, GFI duplex receptacle (convenience service outlet) with
ground-fault circuit interrupters, box, and cover plateable to be accessed after equipment is installed
within the field cabinet.
ii. Provide a UL-listed receptacle meeting Federal Specification #W-C-596.
k.Provide a ground buss bar of copper alloy material compatible with copper wire and provide at least two
positions where a No. 2 AWG stranded copper wire can be attached.
l.Provide field cabinets that comply with the NEC and grounding and bonding requirements in Section 682
and as required and recommended by the cabinet manufacturer.
6.Provide field cabinet with surge protection meeting the following SPD requirements:
a.Provide a Type 1 SPD for the field cabinet’s main AC power input on the load side of the field cabinet
circuit breaker. Other surge protection devices are covered under individual device specifications.
b.Provide SPD that is listed per UL 1449 4th edition, Open-Type 1, or latest edition. The SPD shall be listed
by NRTL.
c.Provide SPD that meets the following minimum performance requirements:
i.Posted at UL.com under certification with 20 kA I-nominal rating.
ii. Does not exceed the VPR and MCOV requirements listed in Table 4.
Table 4 – VPR and MCOV Surge Requirements
L-N L-G N-G
VPR 800V 1,500V 1,200V
MCOV 150V 150V 150V
iii. SCCR that equals or exceeds 100 kA.
iv. Maximum surge current rating (Imax) that equals or exceeds 50 kA per mode and 100 kA per phase
(sum of L-N plus L-G).
d.Provide SPD that has no leakage current to ground.
e.Provide SPD that supports bi-directional operation.
Scoped to Georgia 2021 Standard Specifications, Section 939 — Communications and Electronic Equipment. Every answer cites the section it came from, with a verification date — don’t trust a percentage, click the citation.