SECTION 935 — Fiber Optic System

935.1General Description

This work includes the installation of fiber optic cable and equipment including but not limited to cable, interconnect, patch cords, FDC interconnect cables/pig tails, any cable related hardware, connectors, splices, closures, temporary systems, testing, training, or any other fiber optic product as specified on the plans, or noted in any other Section of these specifications. Provide all equipment and materials of like kind and function to be of the exact same manufacture, model, revision, firmware, etc. Provide all equipment, materials, and work in accordance with all manufacturers’ recommendations. 935.1.01 Definitions General Provisions 101 through 150. 935.1.02 Related References

A.Standard Specifications
SECTION 150 — Traffic Control
SECTION 639 — Strain Poles for Overhead Sign and Signal Assemblies
SECTION 647 — Traffic Signal Installation
SECTION 682 — Electrical Wire, Cable, and Conduit
SECTION 939 — Communication and Electronic Equipment
SECTION 940 — System Integration
B.Referenced Documents

Ensure fiber optic cable and equipment meet the requirements in the following documents:

1.Optical Fiber Standards
a.EIA/TIA-492AAAA-A, Detail Specification for 62.5 µm Core Diameter/125 µm Cladding Diameter Class IA

Graded Index Multimode Optical Fibers, Current Edition

b.EIA/TIA 492CAAB, Detail Specification for Class IVa Dispersion-Unshifted Single-mode Optical Fibers with

Low Water Peak, Current Edition

c.ITU-T G.652D, Transmission Media Characteristics, Recommendations G.650-G.659, for single-mode fibers
d.Telcordia GR-20-CORE, Generic Requirements for Optical Fiber and Cable, Current Edition
2.Fiber Optic Cable and Component Standards
a.Telcordia GR-20-CORE, Generic Requirements for Optical Fiber and Cable, Current Edition
b.EIA/TIA-598-B.3, Optical Fiber Cabling Components Standard, Current Edition
c.EIA/TIA-598-B, Optical Fiber Cable Color Coding Standard, Current Edition
d.RUS 7 CFR 1755.900, United States Department of Agriculture Rural Utilities Service (RUS) Standard

7 CFR 1755.900, Current Edition

e.Telcordia GR-326 Issue 3, Generic Requirements for Single-mode Optical Fiber Connectors, Current Edition
f.EIA/TIA-604-XX, Fiber Optic Connector Intermateability Standards (FOCIS), where XX specifies the fiber

optic connector type (i.e., ST, SC, LC, etc.), Current Edition

g.National Electrical Code Section 770

1879

SECTION 935 — Fiber Optic System
3.Fiber Optic Installation Standards and Practices
a.Building Industry Consulting Service International (BICSI) Telecommunications Distribution Methods

Manual (TDMM), Current Edition

b.BICSI Customer-owned Outside Plant Methods Manual, Current Edition
c.Society of Cable Telecommunications Engineers (SCTE), “Recommended Practices for Optical Fiber

Construction and Testing”, Current Edition

d.OSHA Regulations (Standards-29 CFR) 1910, Occupational Safety and Health Administration Standards
e.ANSI/IEEE C2 National Electrical Safety Code
f.ANSI/NFPA-70 National Electrical Code
4.Fiber Optic Measurement and Testing Standards
a.EIA Standard FOP-II, Test Condition 1
b.Telcordia GR-196-CORE (Issue 2), Generic Requirements for Optical Time Domain Reflectometer (OTDR)

– Type Equipment, Current Edition

c.Applicable Flame Tests: UL 1581 and UL 1666 (Non-Plenum Applications)
d.Applicable Flame Test UL 910 (NFPA 262-2002) (Plenum Applications)
e.EIA/TIA-526-X, Standard Test Procedures for Fiber Optic Systems, Current Edition
f.EIA/TIA-526-7 (OFSTP-7), Optical Power Loss Measurements for Installed Single-mode Fiber Cable Plant
g.EIA/TIA-526-14-A (OFSTP-14A), Optical Power Loss Measurements for Installed Multimode Fiber Cable

Plant 935.1.03 Submittals Prior to any work, obtain approval from the Engineer for the products and procedures to be used on the Project. Use only equipment and materials that meet the requirements of these minimum specifications and are on the Department’s Qualified Products List (QPL) Products appearing on the Qualified Products List (QPL) are exempt from normal submittal requirements. These products have been evaluated by the Office of Traffic Operations and have proven their capability of meeting the appropriate Georgia Department of Transportation Specification. Any of these products may be used without submitting catalogue cuts, sampling or pre-testing. The Contractor shall submit a letter to the Engineer, stating which QPL items they will use. The Engineer and/or department designee must ascertain that the construction item is the same material identified on the appropriate QPL and will acknowledge receipt of these items in the project diary or as required by the Construction Manual. Submit submittal data for test procedures, and routine maintenance procedures required for the items furnished under this specification within sixty (60) calendar days after the Notice to Proceed and prior to any installation, unless noted otherwise in the Contract Documents. Submit to the Engineer service and maintenance documentation for each item furnished under this specification. Provide two (2) bound hard copies and an electronic copy as pdf documents.

A.Cable Certification

Prior to installing any fiber optic cable on the Project, provide detailed information for the cable type, cable manufacturer, fiber content, design and installation procedure to the Engineer. Request approval by certification from an independent testing (third party) laboratory that certifies the fiber optic cable is the same as that on the Department’s QPL.

B.Aerial and Underground Splice Closures Certification:

Provide certification from an independent testing laboratory that certifies that the splice closures are identical to those on the Department’s QPL. 1880

SECTION 935 — Fiber Optic System
C.Fiber Distribution Center (FDC) Certification

Provide certification from an independent testing laboratory that certifies that the Fiber Distribution Centers provided are identical to those on the Department’s QPL

D.Fiber Optic Test Documentation

Within 60 days from the NTP, provide the date, time and location of any tests required by this specification (see 935.3.06) to the Engineer at least 72 hours before performing the test. Provide two copies of documentation of the test results to the Engineer within 5 working days of completion of the test for review and approval, or else retest the represented fiber optic cable and provide the documentation within 5 working days of the retest. Bind the test documentation and include the following:

1.OTDR Set-Up: Cable & Fiber Identification
a.Cable ID
b.Cable Location - begin and end point
c.End-to-end cable length in kilometers calculated from cable markings
d.Fiber ID, including tube and fiber color
e.Operator Name
f.Date & Time
2.OTDR Test Parameters: Information to be recorded on each trace
a.Wavelength
b.Pulse width
c.Refractory index
d.Range
e.Scale
3.Test Results
a.OTDR Test

• Total Fiber Trace distance in kilometers • Splice Loss attenuation in dB per km • Events > 0.01 dB • Trace analysis detailing all events exceeding 0.01 dB Provide OTDR traces meeting Telcordia GR-196-CORE (Issue 2) data format requirements. With advance approval by the Engineer, an alternative format may be used, providing a licensed copy of the software is provided to the Department at no additional cost to the Department. Provide all traces in electronic format to the Engineer. At a minimum, ensure the data includes: cable ID, fiber number, buffer tube, FDC port, fiber distance, test wave length, attenuation in dB per km. Obtain data requirements for each project from the Engineer.

b.Power Meter End – To – End Attenuation Test

• Perform this test on each fiber link using test procedures described in document EIA/TIA 526 sections 7 & 14A. • For each test, document length, number and type of splices and connectors • For each test, document link attenuation • Provide test data to the Engineer in Excel or compatible spreadsheet form and on a CD. 1881

SECTION 935 — Fiber Optic System
4.As-Built Documentation

The as-built documentation shall meet all requirements in the Section 940 specifications. In addition to those requirements, the as-built documents shall include final splicing and fiber allocation details for every splice location.

935.2Materials

Furnish and install all fiber optic parts, materials, components, and equipment consistent and compliant with the latest version or edition of the standards and industry practices specified in Section 935.1.02.B. If a conflict of difference exists between the requirements contained in the specified standards and practices and the requirements contained in these Specifications, use the most stringent material requirement for this contract. Notify the Engineer of any such conflicts or differences prior to procurement of materials and components.

A.Fiber Optic Cable

Ensure all fiber optic related products conform to this specification. Install, apply, inspect, and use those products in accordance with the manufacturer’s standard operating and installation procedures and this Specification. Ensure optical fiber used in both outside and inside plant cable conforms to the requirements specified herein as well as the industry standards and practices listed in Section 935.1.02. Ensure all fiber optic cable on this project comes from a currently ISO9001 certified manufacturer who is regularly engaged in the production of this material using the processes noted within this Specification. All outside plant fiber optic cable used on each individual project shall be from only one manufacturer and manufacturer production batch. Use only cable that is new (manufactured no more than eight months prior to the project Notice to Proceed) and of current design and manufacture. Ensure that single mode optical fiber used in cables meets EIA/TIA 492CAAB, Detail Specification for Class IVa Dispersion-Unshifted Single-mode Optical Fibers with Low Water Peak, Current Edition, and ITU-T G.652D, Transmission Media Characteristics, Recommendations G.650-G.659, for single-mode fibers Ensure that all optical fibers in the cable are usable fibers. The fiber optic cable type, configuration, and installation method will be detailed on the Plans, Drawings, Details, Specifications and in the pay items. Ensure cable and cable installation conforms to all requirements within the Plans and Specifications.

B.Outside Plant (OSP) Cable

This section sets forth the general standards for fabrication and design of outside plant fiber optic cable.

1.OSP Cable Construction
a.General Requirements: Ensure OSP cable is an accepted product of the United States Department of

Agriculture Rural Utilities Service (RUS) as meeting the requirements of 7 CFR 1755.900. Only use optical fibers that are placed inside a loose gel-free buffer tube.

b.Buffer Tubes: Ensure each buffer tube contains 12 fibers for all fiber optic cables unless specified

otherwise. Ensure fibers cannot adhere to the inside of the buffer tube. Ensure the fibers utilize dry water- blocking materials and construction. Ensure the fiber optic cable includes loose buffer tubes that isolate internal optical fibers from outside forces and provides protection from outside forces and provide protection from physical damage as well as water ingress and migration.

c.Cable Core: Protect the cable core with a water blocking material. Ensure water blocking material is non-

nutritive to fungus, electrically non-conductive and homogenous.

d.Strength Members: Use a central anti-buckling member consisting of a glass reinforced plastic rod to

prevent buckling of the cable. Use high tensile strength aramid, fiberglass, or a combination of aramid

and fiberglass yarns to provide tensile strength. 1882

SECTION 935 — Fiber Optic System
e.Ensure color scheme meets EIA/TIA-598-B, Color Coding of Fiber Optic Cable.
f.Cable Jacket: Include in the cable at least one ripcord under the sheath for easy sheath removal.
g.Helically strand the high tensile strength yarns evenly around the cable core.
h.Sheath all dielectric cables with medium density polyethylene. Ensure the minimum nominal jacket

thickness is 0.06 in. (1.5 mm). Apply jacketing material directly over the tensile strength members and

water-blocking compound. Ensure the polyethylene contains sufficient carbon black to provide ultraviolet

light protection and prevent the growth of fungus.

i.Ensure the jacket or sheath is free of holes, splits, and blisters.
j.Ensure the cable jacket contains no metal elements and is of a consistent thickness.
k.Marking: Mark cable jackets using the following template, unless otherwise shown in the plans:
l.Manufacturer’s Name - Optical Cable - Year - Telephone Handset Symbol – GA DOT - Description
m.For Description of Single-Mode Cable use: XXF SM where XX denotes the fiber count
n.Mark the cable length every meter, every 2 ft. if marking the cable in English units. Ensure the cable length

markings are within -0/+1% of the actual cable length.

o.Provide cable marking that is contrasting in color to the cable jacket. Provide cable marking with

character heights of approximately 0.10 in. (2.5 mm).

2.Additional Requirements for Loose Tube Cable
a.Use only cable that is all dielectric, loose tube design. Ensure buffer tubes are stranded around a central

member using the reverse oscillation, or “SZ”, stranding process.

3.Cable Performance

Ensure all OSP cable meets or exceeds the requirements of the Fiber Optic Test Procedure (FOTP) criteria

referenced in 7 CFR 1755.900. Upon the request of the Department, provide certification from an independent

testing laboratory certifying the cable conforms to the specifications and test procedures.

a.Pulling Tension: Ensure the cable can withstand a maximum pulling tension of 600 lbf (2.7 kN) during

installation (short term) and 200 lbf (890 N) installed (long term).

b.Temperature Range: Provide only OSP cable designed to endure exposure to shipping, storage, and

operating temperatures of -30 °F to +158 °F (-34 °C to +70 °C). Provide only OSP cable designed to

endure exposure to installation temperatures of -20 °F to +140 °F (-30 °C to +60 °C).

C.Inside Plant (IP) Cable

This section sets forth the general standards for fabrication and design of inside plant fiber optic cable.

1.IP Cable Construction
a.Strength Members: For the strength member, use a high modulus U.S. manufactured aramid yarn. Ensure

non-toxic, non-irritant talc is applied to the yarn to allow the yarns to be easily separated from the fibers

and the jacket. For all IP cables used in plenum structures, use only IP cable that meets NEC UL-910

requirements for plenum rated cables.

b.Cable Jacket: Ensure the jacket to be continuous, free from pinholes, splits, blisters, or other

imperfections. Ensure the jacket is smooth, as is consistent with the best commercial practice. Ensure the

jacket provides the cable with a tough, flexible, protective coating, able to withstand the stresses

expected in installation and service.

c.Use yellow cable jackets for single mode.

1883

SECTION 935 — Fiber Optic System
d.Design the cable jacket for easy removal without damage to the optical fibers by incorporating a ripcord

under each cable jacket. Ensure that a non-toxic, non-irritant talc is applied to the aramid/fiberglass yarns

to allow the yarns to be easily separated from the fibers and the jacket.

e.Ensure the nominal thickness of the cable outer jacket is sufficient to provide adequate cable protection

while meeting the mechanical, flammability, and environmental test requirements of this document over

the life of the cable.

f.Color: Use color coded individual fibers for identification. Ensure color coding complies with EIA/TIA-598-

B Optical Fiber Cable Color Coding as stated in 935.2.B.1.e.

g.Marking: Mark the outer cable jacket at least every 3 ft. (1 m) with the manufacturer's name or UL file

number, date of manufacture, fiber type, flame rating, UL symbol, and sequential length marking (e.g.

62.5/125 MICRON Type OFNR - UL). Use print color that contrasts to the color of the jacket and is

permanent and legible for the life of the cable.

2.Fabrication by Cable Type
a.Interconnect Cables: Use interconnect cable to connect the distribution panels of a fiber optic cable plant

with the actual electronic devices. Fabricate interconnect cable by surrounding the 900 μm tight buffered

fibers with layered U.S. manufactured aramid yarns and a jacket of PVC or Copolymer depending on NEC

requirements. Use the aramid yarns as tensile strength members.

b.FDC Interconnect Cable: Use this cable to splice a factory connectorized multifiber pigtail cable on to an

OSP cable end, routing that cable within an FDC and its splice cabinet, and connecting to the termination

panels of the FDC. Construct FDC interconnect cable of 900 μm tight buffered fiber (single mode or

multi-mode optical fiber) surrounded with U.S. manufactured aramid fibers, and jacketed with flame

retardant jacket material. Match the fiber count and buffer tube configuration of the FDC interconnect

cable to be exactly equivalent to the OSP cable being terminated in the FDC, unless additional fibers

(using other buffer tube colors) are required for an FDC that is larger than the OP cable. Use a yellow

exterior jacket for the FDC interconnect cable for single-mode.

3.Temperature Range
a.Ensure the cable is designed to endure exposure to a storage temperature range of -30° F to +158° F (-34

°C to +70 °C) while stored on the original shipping reel. Ensure riser cables are designed to endure an

operating temperature range of 0 °F to +158 °F (-18 °C to +70 °C). Ensure plenum cables are designed to

endure an operating temperature range of 32° F to +160° F (0 °C to 71 °C).

4.Crush Resistance Requirements
a.Ensure the cable can withstand a minimum compressive load of 0.061 plf (0.89 N/m) applied uniformly

over the length of the compressive plate. Use only cable that has been tested in accordance with FOTP-

41, Compressive Loading Resistance of Fiber Optic Cables.

5.Impact Resistance Requirements
a.Use only cable that can withstand a minimum of 20 impact cycles. Use only cable that has been tested in

accordance with FOTP-25, Repeated Impact Testing of Fiber Optic Cables and Cable Assemblies.

6.Flammability
a.Use only cables that are UL-listed in accordance with NEC, Article 770. Use only Riser cables (OFNR) that

pass UL-1666. Use only Plenum cables (OFNP) that pass UL-910. 1884

SECTION 935 — Fiber Optic System
D.Patch Cords and FDC Interconnect Cables/ Pig Tails
1.Patch Cords

Use patch cords consisting of a length of fiber optic cable terminated on both ends. For all IP cables used in

plenum structures, use only IP cable that meets NEC UL-910 requirements for plenum rated cables.

a.Fabrication: Ensure all factory preconnectorized assemblies adhere to the applicable cable, cordage, and

fiber specifications stated in these Specifications.

b.Ensure all inside plant (IP) patch cords meet NEC jacketing requirements.
c.Use orange outer jackets for multimode and yellow jackets for single mode.
d.Use connector boots of two (2) colors for all duplex patch cords, zip cord or round. Use white or off white

for one leg of the duplex cord (non-printed zip leg) and red for the opposite leg (printed zip leg) of the

duplex cord.

e.For all assemblies for outside plant (OSP) where loose tube is used, include a fan-out kit installed at each

connectorized end.

f.No splices of any type are allowed within a patch cord assembly.
g.Factory testing: Fully test each assembly and place those test results on a test tag for each mated pair of

connectors. Attach the tag to one end of each pair within the assembly.

h.Individually package each assembly within a plastic bag and clearly mark on the outside of that bag the

submitted manufacturer's part number.

2.Factory Connectorized FDC Interconnect Cables/Pig Tails
a.Use FDC interconnect cables/pig tails consisting of a length of fiber optic cable of one single fiber

terminated on one end. Use only FDC interconnect cables/pig tails with factory installed connectors in

accordance with Subsection 935.2.F. Provide FDC interconnect cables/pig tails with 900 micron tubing or

3 mm fan out tubing as required for the application. Use FDC interconnect cables/pig tails with 900

micron tubing only when fully enclosed within an FDC. Ensure that the other end of the cable is properly

prepared for splicing to another cable. Provide FDC interconnect cable/pig tail in conformity with the

same construction and testing requirements as patch cords.

E.Drop Cable Assembly – Outside Plant

Drop cable assembly is defined as a connectorized fiber optic cable (drop cable) and appropriate fan out (if

required) used for connectivity between a primary fiber trunk or feeder cable and field devices such as signal

controllers, closed circuit television cameras, video detection system cameras, changeable message signs, etc.

1.General Requirements

Provide a loose tube design drop cable in the drop cable assembly meeting the requirements for outside plant

cable as specified in Subsection 935.2.B. Provide the drop cable assembly type (multimode, single-mode or

hybrid) and fiber count specified in the plans.

2.Assembly Fabrication

Provide a drop cable assembly as specified in the plans and meeting the following requirements. Use only

drop cables that are factory pre-terminated, use splice-on factory-connectorized pigtails/FDC interconnect

cables, or are included in pre-terminated FDCs. For factory pre-terminated drop cable assemblies, label each

individual fiber with its drop cable fiber number (“1,” “2,” etc.) on a self-laminating clear overwrapping label on

the fan-out tubing within 2 in. (50 mm) of the terminating fiber connector.

a.Pre-terminated Drop Cable Assembly: Install pre-terminated drop cable assemblies with loose tube

design fiber optic cable, factory-installed fiber optic connectors in accordance with Subsection 935.2.F

on each drop cable fiber, and factory-assembled fan outs with 3 mm fan out tubing. 1885

SECTION 935 — Fiber Optic System
b.Field-spliced Drop Cable Assembly: Install field-spliced drop cable assemblies with loose tube design

fiber optic cable, fusion spliced factory-connectorized pigtails/FDC interconnect cables, in accordance

with Subsection 935.2.D and Subsection 935.2.F on each drop cable fiber.

c.Fan Out - Loose Tube Cable Design: Install field-installed fan outs with 3 mm fan out tubing in

accordance with Subsection 935.3.05.J. Additionally, secure the fan out tubing to the main cable sheath

in a hard epoxy plug transition that extends a minimum of 2.0 in (50 mm) onto the cable and 2.0 in (50

mm) onto the 3 mm tubing.

F.Fiber Optic Connectors

Furnish and install LC compatible connectors unless otherwise specified, Use ceramic ferrule ultra polish

connectors (UPC) for single-mode applications for all connector types. Install connectors as per manufacturer

application and recommendations, including proper termination to the outer-tubing.

Use UPC connectors rated for an operating temperature of -40 °F to +167 °F (-40 °C to +75 °C).

Use only factory-installed UPC connectors for all applications except where shown in the plans for specifically

permitted applications in accordance with 935.2.E.2. Use factory-installed UPC connectors installed with a

thermal-set heat-cured epoxy and machine polished mating face. Do not use field-installed fiber optic connectors.

Where barrel couplers are used in passive termination applications such as FDCs, use only ST compatible

ceramic-insert couplers. Use only manufacturer recommended single-mode couplers for single-mode connector

applications. Provide dust caps for both sides of couplers at all times until permanent connector installation.

Provide connectors listed below that do not exceed the maximum loss listed for each connector.

Connector Type Installation Max. Loss Typical Loss Optical Return Loss

Single-mode Factory 0.50 dB 0.25 dB >55 dB

G.Splice Closure - Underground
1.Use

Provide closures designed for use under the most severe conditions such as moisture, vibration, impact,

cable stress and flex temperature extremes. Ensure splice closures meet or exceed minimum physical

requirements listed in the following subsection:

2.Physical Requirements
a.Use cylindrical closures or rectangular dome type closures with cable entries at one end only and sealed

one-piece high-density polyethylene dome bodies.

b.Ensure splice closures are suitable for ECB or pull box applications as shown in the plans.
c.Ensure splice closures prevent the intrusion of water without the use of encapsulate.
d.Ensure splice closure cable entry ends have flexible thermoplastic rubber end seals with pre-template

cable ports.

e.The closure size shown in the plans specifies the number of splices to be accommodated by the closure.

With the closure, provide all materials to accommodate the number of splices specified by the closure

size, including splice tray, storage, and organizing materials.

f.Provide splice closures capable of accommodating splice organizer trays that accept mechanical, fusion,

or multi-fiber array splices. Use splice closures having provisions for storing fiber splices in an orderly

manner, mountings for splice organizer assemblies, and space for excess or non-spliced fiber. Use splice

organizers that are re-enterable and re-sealable. 1886

SECTION 935 — Fiber Optic System
g.Use only UL rated splice cases. Where high fiber count (144 to 432) splice cases are required, use cases

that have an external pressurization port for optional pressurization.

h.Provide splice closures that do not require the use of specialized tools, equipment, or additional parts for

re-entry and subsequent reassembly.

i.Provide splice closures with provisions for controlling fiber bend radii to a minimum of 1.5 in. (38 mm).
H.Splice Closure - Aerial
1.Use
a.Provide splice closures designed for use in aerial applications and conform to the requirements below:
2.Physical Requirements
a.Use cylindrical closures or rectangular dome type closures with cable entries at one end only and sealed

one-piece high-density polyethylene dome bodies. Provide splice closures designed for free breathing

splice protection without the use of encapsulate. Provide splice closures designed as fully assembled

weather tight closures. Ensure splice closure cable entry ends have flexible thermoplastic rubber end

seals with pre-template cable ports.

b.Provide splice closures utilizing corrosion resistant aluminum or stainless steel hardware. Provide splice

closures designed in such a way as to allow complete splice access after closure placement, without

requiring removal of the closure or electrical bonds from the cable. Provide splice closures suitable for

straight, butt or branch splices. Provide splice closures that include provisions for strain relief, both

around the cable jacket and to internal cable strength members. Provide aerial closures designed in such

a manner that shall eliminate the need for drip collars and sealing collars.

c.The closure size shown in the plans specifies the number of splices to be accommodated by the closure.

With the closure, provide all materials to accommodate the number of splices specified by the closure

size, including splice tray, storage, and organizing materials.

d.Ensure all closures are the appropriate size to accommodate the number and type of fiber cables used

and fit within the space available.

3.Optical Fiber Organizer

The fiber organizer is a system that holds splice or organizer trays in such a way as to protect and support

cable splices within an environmentally protected area. Provide organizer trays capable of storing all common

splices; fusion and mechanical, in all configurations; butt, inline and branch (with up to four branch cables).

Ensure all trays are completely re-enterable. Ensure organizers themselves accept a minimum of four trays,

and provide bonding and grounding hardware.

I.Mechanical Lab Splice

Insertion Loss:

Single Mode < 0.30 dB

Operating Temperature:

-23 °F to 77 °F (-31 °C to 25 °C)

J.Fiber Distribution Center (FDC)
1.Use rack-mount, wall-mount, or pre-terminated FDCs as specified in the plans. Use rack-mount, wall-mount,

or pre-terminated FDCs in all field cabinets, including all types of ITS and traffic signal cabinets, unless

specifically excepted in the plans.

2.Use rack-mount and wall-mount FDCs and FDC splice cabinets with enclosures and mounting components of

metallic construction. Use FDC interconnect cable for all OP cable terminations in rack-mount and wall-mount

FDCs unless otherwise specified in the plans. 1887

SECTION 935 — Fiber Optic System
3.Use FDCs that fit standard 19 in. EIA equipment racks or cabinets.
4.Use rack-mount FDCs of specified sizes 6-fiber through 24-fiber having front-opening swing-out drawers for

access to fiber splicing trays and fiber termination couplers. When closed, ensure swing-out drawers provide

dust-tight seals completely enclosing fiber splicing trays, fiber termination couplers, and connecting ends of

fiber patch cords connected to couplers.

5.Use rack-mount FDCs of specified sizes 36-fiber through 60-fiber having fixed-mounted front-facing fiber

termination couplers accessible behind a removable transparent plastic dust cover.

6.Use FDC’s that are sized to fit within the available space of the cabinet.
7.Use rack-mount FDCs of specified sizes 60-fiber through 144-fiber that include a separate FDC splice cabinet

installed adjacent to the FDC. Alternately, rack-mount FDCs with splice cabinets integral to the overall FDC

enclosure but contained in a separated compartment either above or below the FDC termination couplers.

8.Provide rack-mount or wall-mount FDCs with appropriate quantities of couplers, panels, splice trays,

organizers, factory-connectorized pigtails/FDC interconnect cables, and ancillary materials to terminate the

number of fibers as specified by the FDC size, regardless of the cable size to be terminated as shown in the

plans. Use only FDC interconnect cables for FDCs 30-fiber and larger. Where factory pre-terminated drop

cable assemblies are permitted and to be used, do not provide splice trays.

9.Use pre-terminated FDCs that are factory manufactured assemblies of fiber optic drop cable with factory-

installed fiber connectors and integral ruggedized fiber connector enclosures. Use pre-terminated FDCs of the

sizes specified in the plans. Use ruggedized fiber connector enclosures of thermally stable rigid plastic

housings fully potted with a thermally stable epoxy filling that encapsulates the drop cable fan out, fibers and

connector bodies. Use permanent labels on the enclosure with contrasting color to identify each connector

body by its associated fiber number.

10.For FDCs of all types, provide couplers with dust caps in accordance 935.2.F. Use only LC compatible

couplers unless otherwise specified.

K.Fiber Optic Snowshoes

Use industry standard fiber optic snowshoes that are factory-manufactured fiber optic cable storage brackets

designed for aerial installation on messenger wire cable support spans.

935.2.01 Delivery, Storage, and Handling

Package the cable for shipment on reels. Each package shall contain only one continuous length of cable. Construct

the packaging so as to prevent damage to the cable during shipping and handling.

Seal both ends of the cable to prevent the ingress of moisture.

Attach to each reel, a weatherproof reel tag identifying the reel and cable in such a manner to ensure the

manufacturing history of the cable and the fiber can be traced by the manufacturer.

Include with each cable a cable data sheet containing the following information:

• Manufacturer name

• Cable part number

• Factory order number

• Cable length

• Factory measured attenuation of each fiber

• Bandwidth specification (where applicable)

• Index of refraction 1888

SECTION 935 — Fiber Optic System

935.3Construction Requirements

Ensure all fiber optic parts, materials, components and equipment installed on this contract are consistent and

compliant with the latest version or edition of the standards and industry practices specified in Section 935.1.02.B. If a

conflict of difference exists between the requirements contained in the specified standards and practices and the

requirements contained in these Specifications, use the most stringent material requirement for this contract. Notify

the Engineer of any such conflicts or differences prior to procurement of materials and components.

935.3.01 Personnel

General Provisions 101 through 150.

935.3.02 Equipment

Furnish a portable fiber optic light source and power meter test set for testing the fiber optic cable. Provide a test set

matched, calibrated and referenced to work as a synchronized test system.

Retain ownership of this equipment.

935.3.03 Preparation

General Provisions 101 through 150.

935.3.04 Fabrication

General Provisions 101 through 150.

935.3.05 Construction

A.OSP and IP Cable Installation

Secure from the cable manufacturer the construction and installation procedures to be used on the project.

Produce a detailed construction and installation procedure (SOP) covering all aspects of the construction and

installation process for each and all specific cable to be used on this project. Submit the SOP to the Engineer for

review and approval.

B.Cable Installation Procedures and Standards
1.Safety Precautions

Follow all appropriate OSHA and industry standards related to safety when working in manholes or

underground vaults and when handling optical fibers.

2.Cable Handling

Install all fiber optic cable according to the manufacturer’s recommended procedures and these

specifications.

3.Pulling Tension

Do not exceed the maximum recommended pulling tension during installation as specified by the cable

manufacturer.

4.Allowable Bend Radius

Do not violate the minimum recommended bend radius during installation as specified by the cable

manufacturer. Unless the manufacturer’s recommendations are more stringent, use the following guidelines

for minimum bend radius:

20 X Cable Diameter Short Term - During Installation

10 X Cable Diameter Long Term - Installed

5.Cable Installation Guidelines

Before the installation begins, carefully inspect the cable reels for imperfections such as nails that might cause

damage to the cable as it is unreeled.

Take all necessary precautions to protect reeled cable from vandals or other sources of possible damage

while unattended. Any damage to the cable sections may require replacement of the entire section. 1889

SECTION 935 — Fiber Optic System

Whenever unreeled cable is placed on the pavement or surface above a manhole, provide means of

preventing vehicular or pedestrian traffic through the area in accordance with Section 150 of the

specifications.

Use the "figure-eight" cable lay configuration to prevent kinking or twisting when the cable is unreeled or

backfed. Do not coil fiber optic cable in a continuous direction except for lengths of 100 ft. (30 m) or less.

When "figure-eighting" cable, exercise care to relieve pressure on the cable at the crossover of the eight. This

may be done by placing cardboard shims at the crossover or by forming a second "figure-eight".

Keep the cable continuous throughout the pull. Cable breaks are allowed only at designated splice points.

Where messenger cable is required, as shown in the plans, lash aerial fiber optic cable to a steel strand wire

messenger cable of the size specified in the plans that conforms to Georgia Department of Transportation

specification 915.02.

6.Cable End Sealing

Where a cable ends without termination in a fiber optic closure, seal the end of the cable by re-using a cable

end cap shipped with a cable reel, or use a cap that is size-matched to the cable to be sealed. Clean the end

of the cable. Partly fill the cap with a waterproof silicone adhesive sealant and press the cap fully onto the

cable end, rotating the cap to fully encapsulate the cable end with the sealant in the cap. Apply a full sealant

bead between the end of the cap and the cable jacket.

C.Cable Storage

At designated intervals throughout the cable plant, pull and store excess cable for slack for future terminations or

splicing.

Properly store all cable to minimize susceptibility to damage. Maintain proper bend radius, both short and long

term, during cable storage.

Communication and Pull Boxes: Store the excess or slack cable in the pull box or communication box in

accordance with the plans details.

Hub/TMC/TCC: Properly store the cable in cable troughs and plenum applications which meet NEC requirements.

Aerial Installations: Store the excess or slack cable at storage loops in a “bow tie” configuration on the messenger

strand using two fiber optic snowshoes (aerial fiber cable storage brackets) that maintain the proper bend radius in

the fiber cable. Install one fiber optic snowshoe for drop cable and trunk cable storage at aerial splice closures to

maintain the proper bend radius in the fiber optic cable.

In Cable Storage Requirements - Underground (OSP) & IP

Unless otherwise noted on the plans, the following are the requirements for cable storage for underground and IP

applications:

a.Pull Box – (Types 4, 4S, 5, 5S, 6, and 7) Apply the following storage requirements for the indicated

cable/closure situations.

• Drop cable with no closure – 10 ft. (3 m)

• One or more trunk cables with no closure – 110 ft. (34 m) of each cable

• Two or more trunk cables with one closure – store 55 ft. (17 m) of each trunk cable so that the closure

can be removed from the pull box approximately 55 ft. (17 m). If a drop cable is spliced to the trunk

cable at this point, store 55 ft. (17 m) of each drop cable.

• One trunk cable with one closure – 110 ft. (34 m) Install closure in the center of the 110 ft. (34 m)

cable loop, so that the closure can be removed from the ECB approximately 55 ft. (17 m). If a drop

cable is spliced to the trunk cable at this point, store 55 ft. (17 m) of each drop cable.

• One trunk cable with one closure and trunk cable ends – 95 ft. (30 m). Install closure on the trunk

cable at 55 ft. (17 m) from the pull box. If a drop cable is spliced to the trunk cable at this point, store

55 ft. (17 m) of each drop cable.

• Trunk cable ends with no closure – 95 ft. (30 m) 1890

SECTION 935 — Fiber Optic System
b.Hub Building (interior) – Do not store slack cable inside the hub building.
c.Hub Building (exterior adjacent ECBs) – 180 ft. (55 m)
d.Traffic Control Center & Transportation Management Center (OSP splice vault) – 180 ft. (55m).
e.Traffic Control Center & Transportation Management Center (IP at equipment room) – cable entrance to

distribution panel bay plus 20 ft. (6 m)

f.Electrical Communication Box (ECB) - (Types 3, 4, 5, and 6) Apply the following storage requirements for

the indicated cable/closure situations. More than one situation may occur in a single electrical

communication box, in which case apply each appropriate requirement.

• Trunk cable with no closure – 110 ft. (34 m)

• Trunk cable with one closure – 110 ft. (34 m). Measure the storage amount from the top of the ECB

manhole opening. Install closure in the center of the 110 ft. (34 m) cable loop, so that the closure can

be removed from the ECB approximately 55 ft. (17 m). If a drop cable(s) is spliced to the trunk cable

at this point, store 55 ft. (17 m) of each drop cable.

• Trunk cable with one closure and trunk cable ends – 95 ft. (30 m). Install closure at 55 ft. (17 m) from

the ECB on the trunk cable. If a drop cable(s) is spliced to the trunk cable at this point, store 55 ft. (17

m.of each drop cable.

• Trunk cable ends with no closure – 95 ft. (30 m)

7.Minimum Cable Storage Requirements - Aerial Applications

Unless otherwise noted on the plans, the following are the minimum requirements for cable storage for aerial

applications:

a.Install a minimum 150 ft. (45 m) storage loop approximately one half the distance between every

equipment drop or as shown in the plans. Where equipment drops are greater than 1000 ft (300 m) apart,

install a minimum 150 ft. (45 m) storage loop for every 1000 ft. (300 m)of uninterrupted cable length.

b.At aerial splice closures, install 75 ft. (23 m) of drop cable storage and 150 ft. (45 m) of trunk cable

storage, unless otherwise noted in the plans, to allow the fully assembled closure, including the trunk

cable and drop cable, to be lowered to ground level for maintenance purposes.

D.Cable Splicing

Splice together each individual reel of fiber optic cable to provide the continuous length of installed cable called

for on this Project. Splice cable only at splice points designated on the plans or at locations approved by the

Engineer. Make no splices within a patch cord assembly or drop cable.

E.Mid Span/Drop Access

At points where mid span/drop access is required, keep all fibers intact except those being accessed for the

equipment drop. Use a suitable tool for removing fibers from the buffer tube to prevent damage to the fibers

remaining intact.

F.Connector Termination Procedures

Only use procedures for the termination of the connectors meeting the process set out in that connector

manufacturer's standard operating procedure (SOP) for the field installation.

G.Cable Marking
1.Materials
a.Use 2-1/2 in. (63.5 mm) wide, 4 in. (100 mm) long, wrap-around type cable markers suitable for

underground and aerial use. Use UV stabilized marker material and printing inks to provide an aerial

durability of at least five years. 1891

SECTION 935 — Fiber Optic System
b.Print text in bold black type on orange or yellow PVC markers, as specified in Section 935.3.05.G.2.

Fabricate markers from PVC base material with a minimum thickness of 0.015 in. (0.38 mm). Pre-print the

following text, or alternate text shown in the plans, legibly on markers used for all cables:

c.Cable ID: XXXXXXX

GA DOT

Optical Cable

d.Where XXXXXXX is the appropriate cable ID as defined in the plans. Print the text specified above twice

on every cable marker with the text of the second image reversed and abutting the first image. in such a

manner to ensure the text “reads right” when either short edge of the cable marker is held horizontally

upright.

2.Installation
a.Clean the installed cable of all dirt and grease before applying any marker. Follow the marker

manufacturer’s recommended procedure for applying cable markers. Mark all cables in or at every

communications hub, electrical communications box, pull box, handhole, equipment cabinet, aerial or

underground splice closure, pole attachment, aerial storage bracket, and pole conduit riser entrance. At

every trunk cable termination, reel end-to-reel end splice, electrical communications box, pull box,

handhole, equipment cabinet, aerial splice closure, and aerial storage bracket, record the cable distance

markings from the printline for the cable entry and exit, along with the exact location by Station Number

or location name. Record the cable distance markings in a tabular format approved by the Engineer or on

a documentation form provided by the Department.

b.Place cable markers in the following locations:

• within 18 in. (460 mm) of every cable entry to a pull box, handhole, ECB and hub building

• within 6 in. (150 mm) of every cable entry or termination in an equipment cabinet

• within 18 in. (460 mm) of every splice closure at cable entry points

• within 6 in. (150 mm) of every FDC or splice cabinet in a hub building in which a cable terminates or

enters

• every 20 ft. (6 m) for the length of a cable in maintenance coils in electrical communications boxes or

pull boxes

• within 12 in. (0.30 m) of every pole attachment, aerial storage bracket, and pole conduit riser entrance

c.Use orange markers at all locations, except as noted below:
d.Where a trunk cable enters and leaves a closure (mid-span cable entry or end-to-end splice), use orange

markers for one leg of the trunk cable and yellow for the other leg, placing corresponding color labels at

the closure end of a leg and at the conduit entrance (underground installation) or span attachment (aerial

installation).

e.Where two drop cables terminate in a closure, use orange markers for one drop cable and yellow markers

for the other drop cable, throughout the entire drop cable’s length to its other termination.

H.Fusion Splicing
1.Use
a.Unless otherwise noted, fusion splice all fiber optic splices in accordance with industry codes and the

latest version of the manufacturer’s recommended guidelines.

2.Procedure
b.Perform all fusion splicing and install all splice enclosures according to the manufacturer’s recommended

guidelines. 1892

SECTION 935 — Fiber Optic System
3.Splice Protection
4.Adequately protect all fusion splices in splice trays or organizers in an enclosure. When splicing inside a

building; use a splice center where rack or wall space is available.

5.Provide the splice with strain relief and protection of the stripped fiber splice in a manner recommended by

the splice tray or organizer manufacturer. Use splice types compatible with the tray design.

6.Protect fusion splices with a heat shrink tubing that protects the splice and extends over the fiber coating. Do

not leave bare fiber exposed.

I.Mechanical Splicing
1.Use

Do not use mechanical splices for any purpose other than a temporary connection to fiber optic test

equipment. Obtain the Engineer’s prior approval for any other use of a mechanical splice.

2.Procedure

Make all mechanical splices as strain relief/locking types requiring no adhesive or polishing of the fiber ends.

Ensure the fibers are self-aligning upon the closing of the mechanical splice. Ensure the splice consists of one

piece construction. Ensure there is no stress on the fiber in the alignment area.

Install all splice closures according to the manufacturer’s recommended guidelines.

3.Lab Splice

Use a mechanical fiber optic lab splice when a temporary joining of two fibers is required, such as in the

testing of non-terminated fiber. Ensure the lab splice is re-usable for up to 50 matings. Ensure the lab splice

accommodates optical fibers with cladding diameters between 120 and 145 μm.

J.Splice Closures

Install splice closures according to all manufacturers’ recommendations. Install splice closures where shown in the

plans and in the approximate center of fiber cable storage coils. Securely mount all splice closures in ECBs or pull

boxes to cable rack hooks or mounting brackets.

K.Fiber Optic Cable Fan Out
1.Inside Plant

Provide all inside plant cable with a fan out in accordance with the manufacturer’s recommended guidelines.

L.Temporary Fiber Optic Cable
1.Furnish and install temporary fiber optic cable systems as shown in the plans. Furnish temporary fiber optic

cable as continuous length cable; do not splice remnant cables together. Terminate cables and patch cords

as required in the plans. Splice the cable along cable route at the points indicated in the plans.

M.External Transceivers
1.Shelf mount external transceivers in a manner that does not restrict the replacement of other components in

the cabinet housing. In Type 170 traffic cabinets, mount the transceiver on an aluminum shelf permanently

attached to the EIA 19 in. cabinet rack in the rear of the cabinet.

N.Fiber Distribution Center (FDC)
1.Do not install mechanical splices or field installed connectors. Equip unused panel slots with blank panels.

Provide inter-cabinet and inter-bay bend radius and jumper management on each side of the FDC. Install all

hardware according to the manufacturer’s recommended procedures and Department standards. Determine

specific hardware sizing from the project documents.

2.For rack-mount and wall-mount FDCs, array connectors in a vertical pattern with number one being at the top

left position.

3.Prior to manufacture of pre-terminated FDCs, verify the final installed location of all portions of each drop

cable route from the splice closure to the equipment cabinet (including but not limited to the cabinet location, 1893

SECTION 935 — Fiber Optic System

all conduit and pullboxes, and the splice closure location) to determine the required length of drop cable,

including all splice closure and storage coils, to be factory manufactured with each FDC. Mount the pre-

terminated FDCs with the connectors horizontal or facing downward, and route the drop cable up or down as

necessary. Route and secure the drop cable beside or behind the cabinet side panel such that it is fully strain-

relieved, does not violate the manufacturer’s recommended bending radius, and does not interfere with the

operation of or access to any cabinet equipment or electrical components.

935.3.06 Quality Acceptance

A.Fiber Optic Cable
1.Installation Test
a.Test the fiber optic cabling installed on this project according to the fiber’s assigned use as shown in the

plans and as specified below:

b.Upon completion of the cable installation, splicing, and termination, and a minimum of fourteen days

before equipment hookup, test all terminated fibers and spare fibers for continuity, events above 0.10 dB,

and total attenuation of the cable. In the event that fiber optic cable installed on the project is connected

to existing fiber optic cable, perform installation testing on both terminated fibers and spare fibers of the

new cable and existing fibers to which the new fibers are spliced or connected. Submit both printed and

electronic optical time domain reflectometer (OTDR) traces as specified in Subsection 935.1.03.

2.Test Requirements
a.OTDR Test: For all fiber links, test and document the installation using OTDR testing.
b.Conduct installation testing with a certified technician using an optical time domain reflectometer (OTDR)

and optical source/power meter. The technician is directed to conduct the test using the standard

operating procedure as defined by the manufacturer of the test equipment. Use an OTDR capable of

performing standard OTDR functions, including the ability to display individual loss/gain in dB per km, as

well as display all 2-point dB loss cursors to allow isolating and viewing any and all points along a given

fiber distance.

a.Use a factory patch cord of a length equal to the "dead zone" of the OTDR to connect the OTDR and the

cable. Optionally, the Technician can use a factory "fiber box" of 325 ft. (100 m) minimum with no splices

within the box.

b.Conduct the tests at 1310/1550 nm for single mode cable.
c.Attenuation Test: For all single mode and multi-mode fiber links, test and document attenuation by a

standard power-meter test.

d.For every fiber installed or connected to, perform end-to-end attenuation test. For the test, use a

calibrated optical source and power meter using the standard three-stage procedure. Determine

acceptable link attenuation by the cumulative value of standard losses based on length, number and type

of splices and connectors.

3.Fiber Optic Cable Acceptance
a.Use the following criteria for acceptance of the cable:
b.Provide test results demonstrating the dB/km loss does not exceed +3% of the factory test or 1% of the

cable's published production loss. Consider the error rate for the test equipment in the test.

c.No event can exceed 0.10 dB. If any event is detected above 0.10 dB, replace or repair that event point.
d.The total dB loss of the cable, less events, cannot exceed the manufacturer's production specifications

as follows: 1894

SECTION 935 — Fiber Optic System

Cable Type Max. Attenuation dB/km Test Wavelength

Singlemode 0.30 1550 nm

0.40 1310 nm

e.If the total loss exceeds these specifications, replace or repair that cable run and assume all expenses,

both labor and materials. Elevated attenuation due to exceeding the pulling tension during installation will

require the replacement of the cable run at no expense to the Department for either labor or materials.

f.NOTE: The Department may allow the "bi-directional/averaging" process of OTDR testing, particularly

when splice losses are being unfavorably affected by "mode field diameter misalignment," "core off-set"

or "core misalignment."

B.Fusion Splicing

Ensure that the maximum splice loss for any fusion splice does not exceed 0.10 dB.

C.Mechanical Splicing

Ensure the maximum splice loss for mechanical splices does not exceed 0.70 dB. As noted in this specification,

mechanical splicing is only allowed when approved by the Engineer for temporary applications.

D.Fiber Distribution Center (FDC)

Test all completed and assembled pre-terminated FDCs at the point of manufacture and provide two copies of the

manufacturer test documentation. Test each connecterized fiber in the pre-terminated FDC to demonstrate

compliance with all requirements for cables and connectors as detailed in other subsections of these

specifications. Include in the test documentation the location station number where the FDC is to be installed, the

serial number of the pre-terminated FDC, the drop cable footage markings at each end of the drop cable, and the

total drop cable distance. Place one copy of the manufacturer test documentation in the equipment cabinet

drawer where the pre-terminated FDC is installed, and submit the other copy to the Engineer.

935.3.07 Contractor Warranty and Maintenance

Provide a one year manufacturer support (usual and customary warranties) period for all fiber optic cable materials

furnished and installed as part of the fiber cable system. Include in warranty and support all contractor or

manufacturer activities related to maintenance, removal and replacement of cabling, closures and other fiber optic

system materials during the period of support. Begin the Manufacturer warranty support period upon successful

completion of the Fiber Optic Quality Acceptance testing as outlined in Subsection of 935.3.06. Ensure all

Manufacturer warranties are continuous throughout the period and state that they are subject to transfer to the

Department.

935.4Measurement

Fiber optic system, temporary fiber optic system, testing and training complete, in place, accepted and of the kind,

size, and type specified is measured as follows.

A.Outside Plant Fiber Optic Cable

Outside Plant fiber optic cable is measured for payment by the actual number of linear feet installed, complete,

functional, and accepted. Fiber optic cable shall include but is not limited to all required fiber optic connectors,

fiber optic snowshoes, marking and labeling, patch cords and other ancillary items as required for a complete fiber

optic installation.

B.Inside Plant Fiber Optic Cable

Inside Plant fiber optic cable is measured for payment by the actual number of linear feet installed, complete,

functional, and accepted. Fiber optic cable shall include but is not limited to all required fiber optic connectors,

marking and labeling, patch cords and other ancillary items as required for a complete fiber optic installation. 1895

SECTION 935 — Fiber Optic System
C.Closures

Underground splice closures, aerial splice closures, and FDCs are measured for payment by the actual number of

units installed, complete, functional and accepted. Closures shall include but are not limited to all required

mounting and fastening hardware, fiber optic connectors, FDC interconnect cables/pigtails, marking and labeling,

patch cords and other ancillary items as required for a complete closure installation.

D.Fiber Optic Splice, Fusion

Fiber optic splices, fusion, are measured for payment by the actual number of splices made, complete, and

accepted. Fiber optic splices associated with the use of factory-connectorized FDC interconnect cables/pigtails

on drop cables, in accordance with Section 935.2, will not be measured separately for payment. Mechanical

splicing for temporary applications shall be included in other work and will not be measured separately for

payment

E.Temporary Fiber Optic System

Payment for work on the Temporary Fiber Optic System will be a lump sum project bid price and will be

considered full compensation for all installed materials and labor associated with the Temporary Fiber Optic

System. Specific items include but are not limited to timber poles, guys, anchors, lashing, messenger cable,

conduit directional boring, conduit, fiber optic cable, fusion splicing, hardware attachments, splice enclosures,

equipment rentals, and disposal of materials.

F.Transceivers

External drop and repeat transceivers and external star transceivers are measured for payment by the number

actually installed, complete, functional, and accepted.

For each unit installed, furnish and install all mounting and interconnection materials, including but not limited to

card cages, hardware, fiber and RS-232 jumper cables, RS232/485 converters, and power supply cables at no

separate cost to the Department.

935.4.02 Limits

General Provisions 101 through 150. 1896

SECTION 935 — Fiber Optic System

935.5Payment

Outside and inside fiber optic cable, FDC interconnect cables/pig tails, splice closures, splices, temporary fiber optic

system, transceivers, and testing are paid for at the Contract Unit Price for the various items. All other required items

including; FDC interconnect cables/pigtails, fan-out kits, fiber optic connectors, fiber optic snowshoes, and other

ancillary items for a completed fiber optic system shall be included as part of the below pay items. No separate

payment shall be made for these items. Payment is full compensation for furnishing and installing the items complete

and in place according to this specification.

Payment for all items of this Section is as follows:

Payment will be made under:

Item No. 935 Outside Plant Fiber Optic Cable (type, mode, size) Linear Feet (Linear Meter)

Item No. 935 Inside Plant Fiber Optic Cable (type, mode, size) Linear Feet (Linear Meter)

Item No. 935 Fiber Optic Closure (type, size) Per Each

Item No. 935 Fiber Optic Closure, FDC Pre-Terminated (type, size) Per Each

Item No. 935 Fiber Optic Splice, Fusion Per Each

Item No. 935 External Transceiver (mode) Per Each

Item No. 935 External Star Transceiver (mode) Per Each

Item No. 935 Temporary Fiber Optic System Lump Sum

935.5.01 Adjustments

General Provisions 101 through 150.. 1897