Effective with the December 2018 Letting 412 2019 Standard Spec ifications Section 633 Delineators and Markers
633.1Description
of-way markers.
633.2Materials
633.2.1 Steel Posts
coating, and made of steel with the following properties: Minimum tensil e strength ...................................... ............................................................... ....................... 50 ksi Minimum tensile yield st rength ................................ ............................................................... .................... 36 ksi Minimum elongation ............................................................... ........................................... 5.0 percent in 2 in ches
posts are symmetrical, well rolled, and free from defects that impair their strength or appearance.
coating according to ASTM A123. 633.2.2 Flexible Delineators and Markers
indicates. If the contract requires reflective sheeting, furnis h posts with shop-applied reboundable type H reflective sheeting from the department's APL and of the size plan details show. 633.2.3 Hardware
specifies otherwise. 633.2.4 Delineator Brackets
SH reflective sheeting from the department's APL . Furnish stainless steel st ud bolts, self-locking nuts, and washers conforming to 513.2.1 . 633.2.5 Delineator Reflectors
type SH reflective sheeting from the department's APL. 633.2.6 Right-of-Way Marker Plaques
633.3Construction 633.3.1 General
application the bid item indicates unless the plans show otherw ise. Ensure that the curved side of single curvature posts has the required marking and faces traff ic.
otherwise damaged by con tractor operations. 633.3.2 Delineators
concrete barriers or other structures. Set posts and brackets i n the locations and at the offsets the plans show or the engineer directs.
633.3.3 Temporary Delineators
the engineer approves, the contractor may furnish serviceable u sed posts. Maintain during construction by replacing damaged materials. Remove and dispose of temporary delineators when no longer needed.
Effective with the December 2018 Letting 413 2019 Standard Spec ifications 633.3.4 Right-of-Way Markers
the plans show, or to the dept h required to provide adequate su pport, whichever is greater. If encountering rock above the minimum embedment depth, install as the plans show unless the engineer allows otherwise.
633.3.5 Culvert End Markers
non-reflective sign tape to both sides of the top nine inches.
approaching highway traffic. Use only one marker where two or m ore apron endwalls are adjacent to each other. 633.3.6 Crossover Markers
with white reboundable sheeting. Attach posts to bases using a locking pin or other engineer-approved system. Add 633.3.7 to specify construction requirements for median markers. 633.3.7 Median Markers
with yellow reboundable sheeting. Attach posts to bases using a locking pin or other engineer-approved system. 633.3.8 Salvaging Material
designates. Take care to minimize damage to reusable materials. Restore the site, and dispose of unusable and surplus materials.
may place hardware and smaller pa rts in clearly labeled crates or plastic buckets. Stockpile reusable components in engineer-approved locations on the project.
633.4Measurement
completed except as follows: - The department will measure the Salvaged bid it ems as each in dividual installation including the post and associated reflector, brackets , sheeting, marking, or plaque. - The department will measure Markers Crossover as each installation including the post and base.
633.5Payment
Revise 633.5 to add a new bid item for median markers.
items: ITEM NUMBER DESCRIPTION UNIT
633.0100 Delineator Posts Steel EACH
633.0200 Delineators Flexible EACH
633.0500 Delineator Reflectors EACH
633.1000 Delineator Brackets EACH
633.1100 Delineators Temporary EACH
633.5100 Markers ROW EACH
633.5200 Markers Culvert End EACH
633.5300 Markers Crossover EACH
633.5400 Markers Median EACH
633.9000 - 9100 Salvaged (type) EACH
erecting the posts; and for removing and disposing of surplus m aterials, contractor-damaged posts,
Effective with the December 2018 Letting 414 2019 Standard Spec ifications and debris. Reflectors for use on steel delineator posts are pa id for separately under the Delineator Reflectors bid item while reflective sheeting for flexible deli neators is incidental to the Delineators Flexible bid item.
washers, screw-nails, or other c onnectors required for installation.
including anchors, bolts, and gaskets.
delineators. The department will not pay for replacing temporar y delineators damaged during construction.
grout, and backfill; and for splicing.
tape and soil anchor.
the marker pole and base.
delineators or markers; for rest oring the site; and for disposi ng of damaged and surplus material.
Effective with the December 2018 Letting 415 2019 Standard Spec ifications Section 634 Wood and Tubular Steel Sign Posts
634.1Description
634.2Materials
634.2.1 Wood
having 4 sides surfaced (S4S). U se either beam and stringer gra de or structural joist and plank grade material with a minimum stress grade rating of 1200 fb at 19 pe rcent maximum moisture.
634.2.2 (Vacant) 634.2.3 (Vacant) 634.2.4 (Vacant) 634.2.5 Tubular Steel 634.2.5.1 General
A1011, grade 50 with an average minimu m yield strength, after cold-f orming, of 55,000 psi. Punch holes on all 4 sides for the fu ll length as the plans show. Pro vide corner radii of approximately 5/32 inches and conform to other dim ensions and tolerances as follows: TABLE 634-1 TUBULAR POST DIMENSIONS AND TOLERANCES[1]
COMPONENT OUTSIDE DIMENSIONS inches OUTSIDE DIMENSION TOLERANCE inches ALLOWABLE TWIST[2] inches/3 feet UPPER TUBE 2.00 x 2.00 +/-0.008 +/-0.062 INSIDE ANCHOR TUBE 2.25 x 2.25 +/-0.010 +/-0.062 OUTSIDE ANCHOR TUBE 2.50 x 2.50 +/-0.010 +/-0.075 [1] Measure at least 2 inches from the ends of the tubes. [2] Hold one side on a flat surface plate and measure the twist at the corner 3 feet away.
cold-galvanized organic zinc pai nt as manufacturer recommends.
together without damaging the coatings. Replace scratched or otherwise damaged components at no expense to the department. 634.2.5.2 Upper Tube
and phosphate before painting with an acrylic paint using an electrodeposition process followed by baking. 634.2.5.3 Anchor System
3-inch, grade 5 zinc plated bolt and nut. Ensure the holes of t he 2 tubes match. For installations in poured concrete use an 18-inch inner tube and an 18-inch outer tube with no soil stabilization fins. For other installations use a 36-inch inner tube and an 18-inch out er tube with soil stabilization fins.
634.3Construction
install sign posts until the finished grade is established.
true vertical position. Orients ign posts as the plan details show to ensure that pos ts will yield or break on impact as designed. For installations in concrete or asphalt, use box-outs as the plan details show.