499 The Contractor shall provide cooperative assistance and labor as required to assist the
Division i — n inspecting the thermal wires prior to concreting the shaft. Prior to TIP testing ,
the contractor shall provide shaft installation details to the TIP consultant. Because the method relies on the heat of hydration, tip testing is generally performed between 8 and 48 hours of concrete placement (note the optimum TIP testing time is depe ndent on shaft size and concrete mix and could range from 4 to 72 hours ). 625.7.2.6.2.1 -Criteria to be used for acceptance or rejection of rock socketed drilled shaft using TIP testing: The rating of the shaft integrity using tip shall consider variatio ns in temperature as measured by the thermal wires. Potential local anomalies may be indicated by locally low temperatures relative to the average temperature at that depth, or average temperatures significantly lower than the average temperatures at othe r depths. The criteria for rating the concrete from the TIP test shall be: Satisfactory (s) = 0 to 6% effective radius reduction and cover criteria met Anomaly (a) = effective radius reduction > 6% or cover criteria not met When a tested shaft is categorized as anomaly (a), slices modeled at the area of question may be provided so that a structural evaluation of the shaft can be performed prior to implementing any corrective measures. Core drilling shall be performed to investigate problem areas f ound during TIP testing. 625.7.3 -Evaluation by Core Drilling: A rock socketed drilled shaft that is found to be unacceptable shall be core drilled by the Contractor in accordance with ASTM C42. Cores shall be four ( 4) inch nominal diameter. One or mo re core holes shall be drilled at the location(s) as determined by the Engineer. An accurate log of the core shall be kept, and the core shall be crated and properly marked showing the drilled shaft depth at each interval of core recovery. The core and o ne copy of the coring log shall be provided to the Engineer. The Engineer shall determine if the rock socketed drilled shaft is acceptable. The Engineer will submit to the Contractor in writing within seven (7) calendar days approval to proceed with the work. If the quality of the drilled shaft is determined to be unacceptable, then the Contractor shall proceed in accordance with subsection 625.7.2.6.1.3 . 625.8 -METHOD OF MEASUREMENT : Rock socketed drilled shafts and Rock Socket foundations will be measured by the linear foot. For payment purposes, the drilled shafts are the portion from the finished top of each rock socketed drilled shaft to the top of competent rock. Rock Socket is the portion from the top of competent rock to the bottom of the drilled shaft rock socket as shown in the plans or as directed by the Engineer. Each measured drilled shaft is to be complete in place, accepted, and ready to function. "Top of drilled shaft" is the top of concrete as shown in the plans. "Top of competent rock" is as tabulated in the drilled shaft schedules in the plans unless a difference of one (1) foot or more is found during drilling. 625.9 -BASIS OF PAYMENT : The accepted quantities of rock socketed drilled shaft foundations, measured as provided above, will be paid for at the contract unit price per linear foot; complete in place including excavation, slurry if required, tempora ry or permanent metal casing, steel reinforcing, concrete, curing, and any required forming and finishing. No additional payment will be made for temporary casing that remains in place and pressure grouting due to the Contractor ’s inability to stabilize a drilled excavation, for the need to place concrete by tremie or pumping, for the need to use slurry for drilling, 500 or for extra excavation and concrete that may be required due to drilling diameters larger than the minimum diameters specified. No additiona l payment will be made for methods employed to gain access to rock socketed drilled shaft construction or for means required to provide a dry working environment within the drilled shafts. Tubes for CSL testing, TIP wires, and other responsibilities related to testing and inspection assistance are incidental, with no separate payment being made.
625.10 Pay Items :
ITEM DESCRIPTION UNIT 625001 -* Drilled shaft “D” Diameter Linear Foot 625003 -* “D” Rock Socket Linear Foot * Sequence number D = Diameter of shaft, in inches 501 SECTION 626 RETAINING WALL SYSTEMS 626.1 -DESCRIPTION : This work shall consist of furnishing the design, wall construction plans, materials, and construction of cast -in-place reinforced concrete or Mechanically Stabilized Earth (MSE) walls in accordance with these specifications and in reasonably close conformity with the lines, grades, design, and dimensions shown in the plans. 626.2 -GENERAL : Unless specified otherwise in the contract documents the wall may be, a t the Contractor ’s option, any one of the wall systems on the approved source list corresponding to the applicable Pay Item; this list is posted on the MCS&T web page under the heading Approved Source/Product Listing. The Contractor shall indicate which wall system is to be constructed by the bid alternative chosen in the proposal. No change of the wall system indicated in the bid proposal shall be permitted after the bid opening unless approved by the Engineer. The wall design and detail plans for con struction shall be submitted to the Engineer for approval. The time required for preparation and review of these submittals shall be charged to the allowable contract time. Delays caused by untimely submittals or insufficient data will not be considered justification for time extensions. No additional compensation will be made for any additional material, equipment, or other items found necessary to comply with the project specifications as a result of the Engineer ’s review. The proposed wall design shall be compatible with the Contractor ’s proposed method of construction, and shall be compatible with any method of construction shown in the plans. The Division does not assume nor warrant any wall system ’s compatibility with any particular cons truction methods. 626.3 -DESIGN CRITERIA : 626.3.1 -General: The size of all structural elements shall be determined such that the design load stresses do not exceed the allowable stresses found in the AASHTO LRFD Bridge Design Specifications, latest edition. Analysis of external stability of the in -place retaini ng wall system will be the responsibility of the Division. Any staged or temporary construction affecting wall stability shall be the responsibility of the Contractor. The parapets on any portion of the retaining walls as shown in the plans shall be desi gned to resist traffic loads in accordance with the AASHTO LRFD Bridge Design Specifications, latest edition. 626.3.2 -Mechanically Stabilized Earth: The design for the MSE wall shall consider the internal stability of the wall mass. The design shall co nform to the requirements found in AASHTO LRFD Bridge Design Specifications, latest edition. External loads, which affect the internal stability such as those, applied through piling, bridge footings, temporary construction, etc. shall be accounted for i n the design. A design life of 100 years shall be used throughout the design. The factor of safety for pullout resistance shall not be less than 1.50 based on pullout resistance at ¾ inch deflection. The allowable bearing pressure under the stabilized mass shall be as shown in the plans. The minimum length of the soil reinforcing system, as measured from the back of the front