LOOP DETECTOR SECTION 846
529 SECTION 846 — LOOP DETECTOR
846.1Description.
This work consists of providing and placing loop detectors.
846.2Materials.
846.3Construction.
846.3.1 Loop Wire Installation.
compressed air to remove loose material before sealing.
cover.
the saw cut.
of the loop detector installation and before sealing saw cuts. If the resistance to ground is less than 100 megaohms, remedy the work.
the manufacturer’s directions. Protect the saw cut area from traffic until the sealer has set. Place a minimum of 1 inch of sealer on top of the loop detector wire and finish flush with the pavement. Seal any drilled holes in the pavement.
wires from the end of the saw cut to a junction well. Twist the wires a minimum of 5 wraps per LOOP DETECTOR SECTION 846
530 foot in a parallel direction, and tape every 12-inches to 18-inches from the end of the saw cut to a junction well up to the splice.
inch rotary drill hole between the edge -of-pavement, curb, or sidewalk and the junction well, in accordance with the contract. Install loop detector lead -in wire through the rotary drill hole into the junction well and splice acc ordingly.
length of 1 1/2 -inch galvanized rigid metal conduit and weatherproof fitting between the rotary drill hole and junction well, in accordance with the contract . Install the loop detector lead -in wire through the rotary drill hole, 1 1/2 -inch conduit, and junction well and splice accordingly.
through the saw cuts and through the conduit. 846.3.2 Home -run Wire Installation.
the contract for details. 846.3.3 Splicing.
contract. Solder conductors side -by-side, with the exposed copper aligned. Twist the copper clockwise to achieve a mechanical connection. Coat the splice with flux , heat with a soldering iron, and solder with a rosin core solder. Insulate each soldered connection with heat -shrink tubing.
splicing kit. Install an approved splice kit in accordance with the manufacturer’s instructions. The Department will perform a continuity test at the cabinet after application of the splicing kit.
Department’s ITS technician will make the determination if the splice is watertight or not or if wires are crossed or mislabeled.
shrink tube or the open end of the end cap of heat -shrink tubing after contraction.
846.4Method of Measurement.
The Department will measure the quantity of loop detector wire or conduit as the number of linear feet of saw cut where loop detector wire is placed, sealed, and accepted. The Department will include the length of loop wire installed between the saw cut and the junction well in this measurement.
846.5Basis of Payment.
accepted at the contract unit price. Price and payment constitutes full compensation for:
LOOP DETECTOR SECTION 846
531 d. sealer accelerant or retarder.
with loop wire provided, placed, and accepted at the contract unit price. Price and payment constitutes full compensation for:
ITEM DESCRIPTION UNIT 846001 PROVIDE AND INSTALL LOOP WIRE 1 -CONDUCTOR #14 AWG ENCASED IN 1/4” FLEXIBLE TUBING IN A LOOP SAWCUT LF 846002 PROVIDE AND INSTALL A 1 1/2 -INCH GALVANIZED RIGID METAL CONDUIT DETECTOR SLEEVE WITH LOOP WIRE LF
LIGHTING CONTROL CABINETS SECTION 847
532 SECTION 847 — LIGHTING CONTROL CABINETS
847.1Description.
This work consists of providing and installing lighting control cabinets.
847.2Materials.
847.3Construction.
may include mounting to an existing pole or existing cabinet base.
847.3.A.3, above.
box (LB) conduit fitting. After installing the photoelectrical control and LB conduit fitting, seal the area around the hole in the cabinet. Photoelectrical control can also be installed inside of the cabinet behind a plexi -glass shield, if required by the contract and as directed by the engineer.
847.4Method of Measurement.
The Department will measure the quantity of lighting control cabinets as the number provided, installed, and accepted.
847.5Basis of Payment
The Department will pay for lighting control cabinets at the contract unit price per each. Price and payment constitute full compensation for providing and installing all materials. ITEM DESCRIPTION UNIT 847001 INSTALL OR REMOVAL OF POLE OR POST MOUNTED CABINET EACH 847002 INSTALL OR REMOVAL BASE OR PAD MOUNTED CABINET EACH 847003 LIGHTING CONTROL CABINET – 200 A, 277/480V EACH 847004 LIGHTING CONTROL AND DISTRIBUTION ENCLOSURE (120/240; 100 AMP) EACH 847006 LIGHTING CONTROL CABINET – 100 A EACH 847007 LIGHTING CONTROL CABINET – 200 A, 240/480V EACH