850.1Description.
This work consists of providing and installing LED light fixtures (luminaires) on poles (not inclusive in this item) with wattage, lamp type, and distribution type or removing luminaires.
850.2Materials.
Provide a complete fixture with a heavy duty, cast aluminum housing, door with extruded aluminum heat sink, toolless entry, hinged removable power tray door for easy maintenance, and fastening hardware that is stainless steel or zinc plated steel. The fixture shall meet ANSI 136.31
3.0G vibration requirements. Fixture shall have a two bolt slip fitter system for mounting on a 1
1/4-inch to 2 3/8-inch mounting arm connection. A grey powder coat finish shall be applied to the fixture unless otherwise shown on the plans, or as directed by the engineer. Provide electrical materials in accordance with the NEC of the NFPA, and all local and state laws and ordinances governing such installations.
glass lens or acrylic or polycarbonate resin clear globe.
produces an audible click when locked.
sealed and filtered optical assemblies. LED module with robust, heat-dissipating housing and durable electrical connections.
LED drivers, surge protection, luminaire disconnect, and terminal block.
breakable glass finish, removable only by using a screwdriver.
excessive porosity, with all seams welded.
bolts and a clamp.
The fixture shall also meet the following criteria:
5,000K.
Category C.
Luminaire mounting height shall be as indicated on drawings. Luminaire shall provide point illumination of not less than the given values in the table that follows:
Table 850.2-1. Foot-Candle Point Table by HPS Luminaire Equivalent Wattage
Point 1 coordinates are 90 feet longitudinal distance. Point 2 coordinates are 90 feet longitudinal and feet transverse distance. The point values given in the table are based on a 30-foot mounting height with a Light Loss Factor of 1. The point values produced by the submitted fixture shall be included with the fixture submittal. Metal parts shall be free of burrs and sharp corners and edges. Doors, frames, and other internal access points shall be smooth operating and free of light leakage under operating conditions. Factory applied labels shall comply with UL 1598. Labels shall be located where they will be readily visible to service personnel, but not seen from normal viewing angles when lamps are in place. Labels shall include the following lamp characteristics:
tested luminaire before shipping.
of the luminaire to operate as indicated for a period of 5-years from the date of delivery. Transfer all manufacturer warranties to the Department.
850.3Construction.
following installation requirements:
conductor to the grounding screw on the luminaire and the other end to the ground rod conductor in the transformer base of the pole.
NEMA conventions. Ensure the decal is readily visible from the ground and meets ANSI C136.15 2015 Roadway and Area Lighting Equipment Luminaire Field Identification standard. The decal
Luminaire
Point 1 (fc)
Point 2 (fc) Luminaire (LED), 75 Watts HPS Equivalent
0.10
0.11
Luminaire (LED), 150 Watts HPS Equivalent
0.16
0.22
Luminaire (LED), 250 Watts HPS Equivalent
0.27
0.37
Luminaire (LED), 400 Watts HPS Equivalent
0.46
0.55
Luminaire (LED), 640 Watts HPS Equivalent
0.55
0.60
shall be solid white and imprinted with the LED wattage. The high-pressure sodium wattage equivalence may be added to the decal as well.
and LM 80 test reports to the engineer for approval.
indicate the name of the file on the shop drawing.
instrument.
energized, test units to confirm proper operation.
tested for electromagnetic compliance following the measurement protocols specified in ANSI standard C63.4 2003 and required by 47 CFR 15.31.
control device, provide a photocell with each lighting fixture in place of the shorting cap. Provide photoelectric control using solid state circuitry, cadmium sulfide type with hermetically sealed silicone rectifier rated 120-volt, 60-cycle AC and 1000-watts maximum load. Provide photoelectric control with "Fail On" functionality such that in the event of a photocell becoming inoperative, the light fixture will remain in a permanent "On" state through day and nighttime hours. The photoelectric control shall be twist lock type, with suitable mounting bracket with locking type receptacle.
using the following criteria:
National Fire Protection Association, and to all local and state laws and/ordinances governing such installations.
a new location.
850.4Method of Measurement.
provided, installed, and accepted.
removed and accepted.
850.5Basis of Payment.
luminaires.
luminaires and to store luminaires for future re-installation.
ITEM DESCRIPTION UNIT 850001 LUMINAIRE (LED), 150 WATTS HPS EQUIVALENT EA 850002 LUMINAIRE (LED), 250 WATTS HPS EQUIVALENT EA 850003 LUMINAIRE (LED), 400 WATTS HPS EQUIVALENT EA 850004 LUMINAIRE (LED), 640 WATTS HPS EQUIVALENT, HIGH MAST EA 850005 LED WALL PACK, 75 WATTS HPS EQUIVALENT EA 850006 LED WALL PACK, 150 WATTS HPS EQUIVALENT EA 850007 LED WALL PACK, 250 WATTS HPS EQUIVALENT EA 850008 LED WALL PACK, 400 WATTS HPS EQUIVALENT EA 850011 REMOVAL OF LUMINAIRE EA
LED Wattages listed above are based on the equivalent output to HPS lighting. Refer to maximum LED Wattages in Section 850.2.
LUMINAIRE in other states
Get an email when 850 changes
Delaware revises spec sections through supplementals and new editions. We check this one every week and email you the day it changes. Free, no account.