1603 - WELDED STEEL WIRE FABR IC FOR CONCRETE REINFORCEMENT
1600-8 It is the option of the Bureau Chief of Construction and Materials to grant prequalified status to a plant
based upon the qualification test and inspection resu lts of the transportation agencies of other states. A plant will be notified by written documentation in th e event of any change in their prequalified status. The Bureau of Construction and Materials will maintain a list of all plants that are prequalified to provide fabric to KDOT projects.
1600-9 Table 1603-1: Welded Steel Wire Fabric Comparison Testing
Property Individual Specimen Test Results Average Test Results for the Heat or Lot Tensile Strength 10% 5% All variations and differences are absolute value based. A heat or lot that fails the comparison requirements may be resampled one time only, and on a 2 to 1 basis. It is preferable that the resample be removed from the same heat or lot that failed. The initial test results will be replaced by those of the resample specimens. A lot that fa ils the weld shear test requirements may be resampled in accordance with the procedures of subsection 1603.2b .
1600-10 Table 1603-2: Welded Steel Wire Fabric Verifi Cation Testing
Property Requirement Unit Weight, Deformed Wire only: 98% of the specified minimum Weld Shear Strength, Average 95% of the specified minimum Tensile Strength 95% of the specified minimum Reduction of Area,%, Non-deformed Wire only: Specified minimum minus 2 No annual verification sample from a prequalified plant will be permitted to fail the bend test. In the event that the verification sample fails to co mply with the preceding, the Engineer’s representative may resample the failing lot one time only on a two to one basis or reject the failing lot. The contractor is to replace the rejected lot at no add itional cost to the KDOT. The initial test results will be replaced by those of the resample specimens. Failure of the verification sample fabric from a plant to comply with the sample requirements of subsection 1603.5d(3)(b) will result in disqualification of the plant and remova l from the prequalified source list. In the event of disqualification, the plant is subject to subsection 1603.5 . A plant that fails to comply with subsection 1603.5d(3)(b) 2 times, consecutive or otherwise, will be permanently disqualified. 1603.6 BASIS OF ACCEPTANCE The plant must be currently prequalified. Receipt and approval of a Type C certification as specified in DIVISION 2600 . Single sections, bound sections or rolls, or otherwise grouped fabric must be tagged or otherwise marked in a durable manner. At a minimum, this identification must list the fabric manufacturers corporate identification and plant location, the heat, lot, job, or mill order number, and display a copy of the of the identification markings attached to the delivered materials. The final disposition of the fabric will be completed at the final destination as the result of inspection for the quality of workmanship and the delivery condition. 1604 - HELICAL REINFORCEMENT
1600-11 Section 1604
HELICAL REINFORCEMENT 1604.1 DESCRIPTION This specification covers steel wi re and steel bars intended for use in helical reinforced members. 1604.2 REQUIREMENTS Provide materials that comply with AASHTO M 32 fo r plain, uncoated wire, or AASHTO M 31 for carbon steel bars. 1604.3 TEST METHODS Test methods as cited in the AASHTO references. 1604.4 PREQUALIFICATION Manufacturers desiring to provide material under this specification must be prequalified under the provisions of: Steel bars ........................................................................................................ SECT ION 1601 Uncoated wire ................................................................................................ SECT ION 1603 Epoxy coated reinfor cement ........................................................................... SECTION 1602 1604.5 BASIS OF ACCEPTANCE Prequalification as required by subsection 1604.4 . Submit for approval a Type A certification ( certified mill test report), as specified in DIVISION 2600 , that governs the analysis of all bar or wire steel heats delivered to the project. Receipt and approval by the Engineer of a copy of the shipping orde rs or invoice sh owing the project number, heat or lot number, steel size and quantity in the shipment. Tag each bundle of helical reinforcement sent to the pr oject with a plastic or metal tag which lists the plant name and the heat or lot number, or other identification tyi ng the material to the certifica tions and invoices as stated above in this subsection. 1605 - REINFORCING STEEL SPLICES
1600-12 Section 1605
REINFORCING STEEL SPLICES 1605.1 DESCRIPTION This specification covers devices and systems for splicing steel bars for concrete reinforcement. Thermomechanical splices are produced by a process that introduces molten filler metal into an annular space around the bars created by a high strength st eel sleeve of larger diameter than the bars. Make the mechanical splices with any mechani cal device or system which will meet the physical requirements cited below. 1605.2 REQUIREMENTS When tested in tension, develop all splices to at least 125% of the minimum yield strength specified for the bars being spliced. After loading in tension to 30 ksi then relaxing to 3 ks i, the total slip of the bar within the splice sleeve shall not exceed 0.01 inch for #14 bars and smaller, and 0.03 inch for #18 size bars. Displacements will be measured between gage points clear of the splice sleeve. For those splicing systems to be prequalified in the “fatigue resistant” group, provide splices capable of withstanding a load range of 12 ksi (3 ksi to 15 ksi, tension) for a minimum of 1,000,000 cycles. Prepare and mount splices on bars in a fabricator's shop for ship ment to the project that meet SECTION 1601 including prequalified plant status. 1605.3 TEST METHODS Splicing devices or systems will be tension tested according to the procedures of AASHTO M 31, “Deformed and Plain Carbon Steel Bars for Concrete Reinforcement” and slip tested according to subsection 1605.2 . 1605.4 PREQUALIFICATION Prepare 3 fully assembled test specimens each for bar sizes number 4, 6 and 8, and forward them to the Engineer of Tests along with the following information: Name, address and telephone number of the manufactur er. Include the name of the preferred contact person. Brand name of the splice. Type and description of the splice. Information regarding recommended usage and splicing instructions. Material Safety Data Sheets (if applicable). For those splicing systems to be prequalified in the “fatigue resistant” group, submit test results from an independent testing laboratory demonstrating that the splice meets the fatigue requirements described above. Test splices for #4, #8, and # 11 size, Grade 60 reinforcing steel. These sizes represent the small, medium, and large sizes common in construction. Exceptions to the bar sizes specified above ma y be authorized by th e Engineer of Tests. The samples provided will be tested to destruction and test reports prepared. During testing, the Engineer of Tests will determine if operator prequalification is require d for field and/or fabricator shop splicing, and enter that information on the test reports. The test reports and the information supplied will be reviewed by the Bureau Chief of Construction and Materials. The manufacturer will be a dvised as to whether or not the product is prequalified. The Bureau of Construction and Materials will mainta in a list of prequalified splicing systems. Products will remain prequalified as long as the manufacturing pr ocesses remain unchanged, a nd field experience indicates that the product functions appropriately. Changes in manufacturing processes require new prequalification testing. Failure of the product to function appropriately in the fi eld will be cause for removal from prequalified status. Products removed from prequalified status will be consid ered for requalification if the manufacturer can provide