B
HomeLibrariesCopilotSearchProjectsBookmarks
FeedbackHelp Desk
Libraries
Building Codes
Code LibraryIBC — BuildingIRC — ResidentialIFC — FireIPC — PlumbingIMC — MechanicalIFGC — Fuel GasIECC — EnergyNEC — ElectricalModel Codes
Specifications
CSI SpecificationsDOT SpecsTransit SpecsUSACE
Standards
TransportationRailroadFire SafetyAccessibilityStructural
Tools & References
DiagramsAssembliesProductsCalculatorsChecklistsPermits
PricingLog in
Earthwork (200-299)

204CLASS 2, CLASS 3, CLASS 4, AND EXISTING DITCH CLEANING EXCAVATION

PA · 2026 Standard SpecificationsBook pages 153157View official source ↗

Minimum QC Test Frequency Material Embankment or Fill Subgrade* Pipe Backfill Start -up Frequency One QC test per lift for each 500 square yards placed; minimum six tests per lift per day. In limited or restricted areas the test rate should not exceed the rate for pipe backfill. One QC test per lift for each 400 square yards placed; minimum eight tests per lift per day. For every pipe run conduct one QC test for every 50 cubic yards of pipe backfill; minimum two tests per lift per day. Production Frequency One QC test per lift for each - 3,000 square yards placed; minimum three tests per lift per day. In limited or restricted areas the test rate should not exceed the rate for pipe backfill. One QC test per lift for each 1,600 square yards placed; minimum three tests per lift per day. For every pipe run conduct one QC test for every 200 cubic yards of pipe backfill; minimum two tests per lift per day. *Subgrade consists of the top 3 feet of the material immediately below the pavement section subbase.

3.Moisture, Density, and Acceptance Testing. For materials placed and compacted as specified in

Sections 206. 3(b)1.a and 1.b, determine the in -place moisture and density according to PTM No. 402 using the direct transmission method. All other materials will be accepted based on a condition of non- movement, as determined by the Representative. Provide a Nuclear Density/Moisture Gauge calibrated according to AASHTO T 310. PTM No. 418 may be used if the gauge is manufactured by Troxler (Note: PTM No. 418 is written for Troxler manufactured gauges while AAS HTO T 310 is generic to any nuclear density gauge). Gauges must be calibrated every 12 months. A sheet with the current annual calibration providing the projected monthly decay stand ard with upper and lower limits must be kept with every gauge. Use Form TR -4276A C for recording daily gauge standardization and for recording the results of all nuclear gauge moisture and density test results. At locations directed by the Representative, conduct acceptance testing for moisture and density at the frequencies specified in Table B. If the required density of the compacted material is not obtained, promptly rework, reshape, and recompact or remove and replace damaged or unsatisfactory areas and perform an acceptance retes ts before placement or testing of another area. The extent of the unsatisfactory area is defined by the Representative using one of the following: visual inspection of the s ite, behavior of the material under the compaction equipment originally used to compact the material, delineation us ing the acceptance moisture- density gauge, or any combination of the above methods. When an acceptance retest fails to meet the specified requirements, check standard count of the acceptance test gauge on the reference standard block in accordance

Source: Pennsylvania Department of Transportation Specifications, 2026 Edition. Pages 153157 of 1,522.