211.03 CONSTRUCTION METHODS. Stabilized stone pads employed as construction entrances
shall be constructed as indicated on the Plans. 211.03.1 Entrance Dimensions.
a.Thickness. The thickness of the stabilized stone pad shall be a minimum of 5 inches.
b.Width. The width shall not be less than the full width of the respective points of ingress or egress.
c.Length. The length of construction entrances shall be at least 50 feet where the soils are sands or gravels, except where the traveled length is less than 50 feet. Where soils are clays or silts, the length of construction entrances shall be at least 100 feet except where the traveled length is less than 100 feet. 211.03.2 Installation Requirements. The area of the construction entrance shall be cleared of all vegetation, roots, stumps, or other objectionable material. The area shall then be excavated to subgrade and graded. Filter fabric shall be plac ed on the prepared subgrade prior to the placement of the stone pad. The stone shall be placed according to the specified dimensions. 211.04 METHOD OF MEASUREMENT. "Construction Accesses" will be measured by the number of square yards of stabilized stone pads actually installed for this purpose in accordance with the Plans and/or as directed by the Engineer. 211.05 BASIS OF PAYMENT. The accepted quantity of "Construction Accesses" will be paid for at the contract unit price per square yard as listed in the Proposal. The price so-stated constitutes full and complete compensation for all labor, material and equipment including excavating, filter fabric, stabilized stone pad, and subsequent removal of same, and all incidentals required to finish the work complete and accepted by the Engineer. SECTION 212 MAINTENANCE AND CLEANING OF EROSION AND POLLUTION CONTROLS
212.01 DESCRIPTION. This work consists of the maintenance and cleaning of erosion and
pollution control facilities in accordance with these Specifications and as directed by the Engineer. 212.01.1 Applicable Controls. The specific erosion and pollution control facilities to be cleaned and maintained under this Section consist of the following:
a.Perimeter Controls.
1.Baled Hay Erosion Checks; Subsection 206.01.1
2.Silt Fence; Subsection 206.01.2