714.01Description

This work shall consist of the construction of a cast-in-place or precast reinforced concrete box structure and such parts of similar structures composed of concrete in accordance with these specifications and 105.03.

The Contractor may be allowed to substitute a three-sided structure in accordance with 723 which shall be subject to a revision of the waterway permits, and shall be as approved by the Engineer. 10

MATERIALS

714.02Materials

Materials shall be in a ccordance with the following:

Chemical Anchor System ............................................ 901.05 Coarse Aggregates, Class A or Higher, Size No. 91 ... 904.03 Epoxy Coated Rein forcing Bars .................................. 910.01 20 Geotextile .................................................................... 918.02(b) Hydrated Lime ............................................................. 913.04(a) Joint Membrane for Pr ecast Reinforced Concrete Box and Three-Sided Structure Sections .............. 907.07 Masonry Ceme nt ......................................................... 901.01(c) Mortar Sand ................................................................. 904.02(e) Natural Sand ................................................................ 904.02(a) Non-Epoxy PCC Sealer ............................................... 909.10 Pipe Joint Sealant ........................................................ 907.11 30 Portland Ceme nt .......................................................... 901.01(b) Precast Reinforced Concrete Headwalls, Wingwalls, Footings, and Sp andrel Walls ............................... 907.06 714.02

Precast Reinforced Concrete Structure Sections ......... 907.05 Reinforci ng Bars .......................................................... 910.01 Structure Backfill ........................................................ 904.05 WWR, Smooth and Deformed..................................... 910.01

Cast-in-place concrete for a reinforced co ncrete box structure, or splices between 40 an existing culvert structure and a precast reinforced concrete box structure section extension shall be class A or higher in acco rdance with 707.04(c). It shall have a 28- day minimum concrete compre ssive strength of 5,000 psi. Cast-in-place concrete for headwalls or wingwalls shall be class A or higher in accordance with 707.04(c). It shall have a 28-day minimum concrete compressive strength of 4,000 psi.

When the Contractor elects to provide a cast-in-place structure, acceptance of the structure will be based on tests for relative yield, air content, slump, water/cementitious ratio, and compressive strength. Relative yield and air content shall be in accordance with 702.05. The slump and concrete temperature shall be in 50 accordance with 707.04(c). The amount of time from the introduction of mixing water to the cement and aggregates to the completion of the discharge of the concrete shall not exceed 90 minutes. The water/cementitious ratio shall be in accordance with

707.04(d). The 28-day compressive strength shall be equal to or greater than the

specified concrete compressive strength an d shall otherwise be in accordance with

(c)3. The Contractor shall provide the necessary 6 in. diameter by 12 in

cylinder molds for the Department’s use.

For plastic concrete sampling, acceptance testing procedures and casting cylinders will be in accordance with 505.01. Except for footings, concrete flexural strength or 60 results from beam breaks will not be accepted in lieu of concrete compression cylinder test results.

Cast-in-place concrete used to seal existi ng culverts shall be class A. Cast-in-place concrete for footings shall be class B.

Unless otherwise specified herein, reinforcement may consist of either reinforcing bars or WWR. If specified to be coated, WW R shall be coated with either galvanized coating or epoxy coating. Reinforcing bars shall be coated with epoxy coating. For WWR, material with minimum yield strength of 65 ksi shall be used. 70

CONSTRUCTION REQUIREMENTS

714.03General Requirements

Unless otherwise specified, the applicable requirements of 702 and 703 shall apply to the construction of box structures, structure extensions, and concrete parts of similar structures. Excavation and disposal shall be in accordance with the applicable requirements of 206. Areas designated for waterproofing shall be waterproofed in accordance with 702.23. All underground dr ains encountered during excavation for 714.03

the structure shall be perpetuated as dictated by field conditions. Drainage openings 80 through masonry shall be in accordance with 702.16. Handling of box structures shall be in accordance with 907.05. Handling of wingwalls shall be in accordance with

907.06

When riprap is specified, geotextile shall first be placed on the in-situ soil in accordance with 616.11. Riprap shall then be placed in accordance with 616.

The box structure, headwalls, wingwalls, and footings shall be designed and constructed in accordance with the dimensions shown on the contract plans. Construction joints shall not be used within the cross-section of precast box structures. 90

714.04Design Requirements

Where reinforcing bars are used, reinforcing bar splicing and spacing shall be in accordance with the AASHTO LRFD Bridge Design Specifications, except as modified herein.

(a)Box Structure

A box structure may be designed in accordance with ASTM C1577 if the box section is listed therein. A box structure section not listed therein shall be designed in accordance with the AASHTO LRFD Bridge Design Specifications with the following 100 exceptions.

The box structure shall be designed in accordance with the soil parameters shown in the contract documents.

Minimum structural reinforcement area shall be at least 0.002 of the gross concrete area, A g, or 0.125 sq in./ft, whichever is greater. The allowable variation in diameter of reinforcement shall be in accordance with the tolerances prescribed in the AASHTO specification for that type of reinforcement.

If coated reinforcement is specified, reinforcement, including support devices, in that structure shall be coated. In lieu of coating, the support devices may be manufactured of a non-corrosive material.

(b)Concrete Headwalls, Wingwalls, and Footings

Headwalls, wingwalls, and footings may be precast or cast-in-place. Headwalls and wingwalls shall be designed based on a minimum equivalent fluid pressure of 40 lb/cu ft. If flowable backfill is to be us ed, the Contractor shall consider the effects of hydrostatic pressure on the wingwalls. Weep holes shall be provided in all wingwalls. Horizontal pressures shall be increased for sloping backfill surfaces and 120 live-load surcharge. Headwall connections and wingwall footings shall be checked for sliding and for overturning.

Wingwalls and wingwall footings shall be designed in accordance with the soil parameters shown in the contract documents. 714.04

For headwalls with guardrail mounted on top, the anchorage of the headwall to the box structure section, or a moment slab with bridge railing shall be designed for the bridge railing test level shown on the plans.

Reinforcement in headwalls shall consist of reinforcing bars and shall be epoxy coated. Tension splices in circumferential reinforcement shall be made by lapping. Where reinforcing bars are used in wi ngwalls, the maximum spacing for wingwall reinforcing bars shall be 18 in. for horizontal bars and 12 in. for vertical bars.

Concrete cover for headwall and wingwall reinforcement shall be a minimum of 2 in. Concrete cover for footing reinforcement shall be 3 in. for the top and sides, and 4 in. for the bottom.

(c)Working Drawings 140

Working drawings shall be submitted in accordance with 105.02 for:

1.fabrication of a precast reinforced concrete box structure

greater than 12 ft span,

2.a box structure of a size not shown in ASTM C1577, Table 1,
3.headwalls,
4.wingwalls, and
5.footings.

Design calculations shall be submitted with the working drawings. Design 150 calculations will not be required for box structures of a size shown in Table 1 of ASTM C1577. Detailed plans for falsework and centering will not be required. Working drawings shall include notes indicating design assumptions, applicable design codes, and material requirements, all details, dimensions, and quantities necessary to construct the structure, headwalls, wingwalls, or footings and shall include, but not be limited to, the following information.

1.Structure span and rise.
2.Structure section details showing all concrete dimensions, joint 160

details, locations and details of lifting devices or inserts, locations and details of pre- or post-installed anchorages, concrete clear cover, size and spacing of reinforcing bars or WWR, and reinforcing bar bending diagrams.

3.Headwall details, showing all concrete dimensions, elevations,

reinforcing bar sizes, reinforcing bar bending diagrams, lengths, spacings, and anchorage details. Headwall elevation and section views shall be provided.

4.Wingwall design calculations and details showing all concrete

dimensions, elevations, reinforcement sizes, bending diagrams, 714.04

lengths, spacings, and anchorage details. Wingwall plan, elevation, and section views shall be provided.

5.Wingwall backfill type and limits.
6.Footing details showing all concrete dimensions, elevations,

reinforcing bar sizes, reinforcing bar bending diagrams, lengths, and spacings indicated. Footing plan and section views 180 shall be provided. The actual soil bearing pressure shall be shown on the footing detail sheets.

7.Structure backfill type and limits for the structure and

wingwalls.

8.Minimum concrete strength for all concrete portions of the

structure.

9.Bridge load rating calculations and load rating summary shall 190

be submitted with the working drawings where the structure span length measured along the roadway centerline is greater than 20 ft, except where the height of cover is greater than 8 ft and exceeds the perpendicular span length. The structure shall have a load rating greater than 1.0 for the loading described herein or as shown on plans. The load rating methodology shall be in accordance with the AASHTO Manual of Bridge Evaluation using the LRFR methodology.

714.05Erection Requirements 200

The soils in the bottom of the excavati on shall be compacted in accordance with

203.23

An 8 in. layer of coarse aggregate No. 8 in accordance with 301 shall be placed under the full width of the footing. All cast- in-place footings shall be given a smooth float finish. The footing concrete shall r each a compressive strength of 2,000 psi or flexural strength in accordance with 702.24(c) before placement of the wingwalls. The surface shall not vary more than 1/4 in. in 10 ft if tested with a 10 ft straightedge.

Structure backfill shall be placed a nd compacted in accordance with 211. 210 Structure backfill shall be placed and compacted on each side of the structure to the fill line shown on the plans. During the backfill operation, the difference in elevations of the fill on each side of the structure shall not exceed 24 in.

Unless otherwise specified by the manufacturer on the working drawings, once the level of structure backfill reaches the top of the structure, two lifts shall be spread and hand compacted over the structure without traversing the structure with heavy

714.05

728

equipment. Compaction with heavy equipment will not be allowed until a minimum

of two lifts have been placed, hand compacted, and accepted.

220

The operation of equipment over a structure shall be in accordance with the

structure manufacturer’s recommendations.

714.06Precast Concrete Headwalls, Wingwalls, and Footings

(a)Headwall Reinforcement Placement Relative to Top of Structure

The headwall shall be a single precast piece which spans from sidewall to sidewall

of a span. The vertical headwall reinforcement shall be attached to the top of the

structure by either drilling holes or precasting holes. A chemical anchoring material,

if used, shall be from the QPL of Chemical Anchor Systems.230

(b)Wingwall Placement

Each wingwall that is not precast as one unit with the footing shall be set on

masonite or steel shims. A minimum gap of 1/2 in. shall be provided between the

footing and the bottom of each wingwall. Once the wingwalls are placed, the space

underneath the wingwall section to the top of the keyway sides shall be filled with

prepackaged grout in accordance with ASTM C1107, or conventional or self-

consolidating fine grout in accordance with ASTM C476, except as modified herein.

If conventional fine grout is used, it shall be troweled into the keyway and mounded

on one side of the wingwall. The mound of conventional fine grout shall be vibrated240

until it passes through to the other side of the wingwall. After completing this process

on one side, if the conventional fine grout has not passed through to the other side, the

process shall be repeated on the other side. Conventional or self-consolidating fine

grout shall be from a prepackaged source or composed of one of the following

mixtures.

1.930 lb/cu yd Type I portland cement with No. 23 natural

sand or mortar sand.

2.930 lb/cu yd Type M masonry cement with No. 23 natural250

sand or mortar sand.

3.828 lb/cu yd Type I portland cement and 75 lb/cu yd

hydrated lime with No. 23 natural sand or mortar sand.

The maximum water/cement ratio shall be 0.446 for both conventional and self-

consolidating fine grout. An air-entraining agent from the QPL of PCC Admixtures

and Admixture Systems may be used. A Type F or Type G chemical admixture from

the QPL of PCC Admixtures and Admixture Systems shall be used in self-

consolidating fine grout to achieve the slump flow and visual stability index260

requirements. Filling procedure B of ASTM C1611 will be used for measuring slump

flow. Appendix X1 of ASTM C1611 will be used for determining the visual stability

index value.

714.06

729

Acceptance of conventional fine grout will be based on an air content of 12%

±4%. Acceptance of self-consolidating fine grout will be based on tests for air content,

slump flow, and visual stability index. Air content shall be 12% ±4%. Slump flow

shall be 27 in. ±3 in. Visual stability index value shall not exceed 1.

A Type C certification in accordance with 916 shall be provided for the270

prepackaged grout.

Wingwalls shall be connected to the outside box structure sections with bolted

steel plates.

714.07Rejection

Structure sections, headwalls, wingwalls, or footings will be rejected due to the

following conditions:

(a)fractures or cracks passing through the section or wall, except for a280

single end crack which does not exceed one-half the thickness of the

section or wall,

(b)defects which indicate proportioning, mixing, or molding which are

not in accordance with this specification,

(c)honeycombed or open texture, or
(d)damaged section ends, where such damage prevents making a

satisfactory joint.290

714.08Repairs

Structure sections, headwalls, wingwalls, and footings shall be repaired, if

necessary, due to imperfections in manufacture, or damage caused by handling or

construction. Repairs will be acceptable if it is determined that the repairs are sound,

properly finished and cured, and if the repaired structure section, headwall, wingwall,

or footing is in accordance with the requirements herein.

714.09Extension of Existing Structure

All applicable requirements of this specification shall apply to the extension of an300

existing box structure, slab-top structure, or arch structure. Such portions of the

existing structure designated for removal shall be removed. All portions of the existing

structure which are to remain in place and are damaged shall be repaired or replaced

as directed. Those portions left in place which are wholly or partially filled with debris

shall be cleaned out. Material removed shall be disposed of in accordance with the

applicable requirements of 202.02.

Before removing concrete from an existing structure with wingwalls, the

Contractor shall saw around the perimeter of the removal area on the interior and

714.09

730

exterior of the existing structure a depth of 1 in. All existing reinforcement in the top310

slab, bottom slab, and sidewalls exposed after concrete removal shall be cleaned and

straightened in preparation for lapping with reinforcement from adjacent new work.

Where existing reinforcement has deteriorated or been damaged during the removal

operation, holes shall be drilled into the face of the existing structure to provide

embedment for replacement reinforcing bars. The holes shall be of the diameter and

depth required by the manufacturer of the chemical anchor system. The holes shall be

cleaned prior to placing the chemical anchor system and the reinforcing bars.

No concrete shall be removed from an existing structure that has a headwall but

no wingwalls. Reinforcing bars used to tie the existing structure to the new structure320

section shall be installed by drilling holes into the face of the existing structure to

provide embedment for reinforcing bars. The diameter and depth of the holes shall be

according to the recommendations of the manufacturer of the chemical anchor system.

The holes shall be cleaned prior to placing the chemical anchor system and the

reinforcing bars.

An existing structure shall be extended by one of the following methods.

(a)Precast Reinforced Concrete Box Structure Extension

A cast-in-place concrete splice shall be constructed as a transition between the330

existing structure and the precast structure extension. The splice reinforcement in the

precast structure extension section that will abut the existing structure shall be exposed

18 in. on the tongue end of the precast structure extension section. It shall be lapped

18 in. with either exposed existing structure reinforcement, in the case of an existing

structure with wingwalls, or newly installed reinforcing bars in the existing structure,

in the case of an existing structure with a headwall only as shown on the plans. Existing

exposed structure reinforcement from an existing structure with wingwalls shall be cut

off 1 in. from the face of the new precast extension.

If the existing tongue or groove joint end is acceptable and matches the mating340

joint on the new precast reinforced concrete box structure extension, the new extension

may be installed using the mating joint of the existing box structure. No cutting of the

box structure or splicing of reinforcement is then required. The joint between the new

precast box structure extension and the existing structure shall be sealed as directed

below.

(b)Cast-In-Place Concrete Structure Extension

The reinforcement for the structure extension shall be lapped with the exposed

reinforcement of the existing structure as shown on the plans.

350

714.10Precast Reinforced-Concrete Box Structure Section Joints

(a)Between Structure Sections

Joints between precast reinforced concrete box structure sections shall be sealed

with pipe joint sealant as shown on the plans. The sealant shall be applied once the

714.10

731

concrete surface temperature is above 40°F or above the minimum application

temperature recommended by the pipe joint sealant manufacturer. The concrete

surfaces shall be clean and dry prior to application of the pipe joint sealant. Heat may

be applied to the concrete surfaces until they are in accordance with the temperature

and dryness requirements.360

(b)Exterior Surface Treatment

After sealing with pipe joint sealant and assembling the box sections, the outside

surfaces of the top slab and both walls of every joint between structure sections shall

be covered with a joint membrane in accordance with 907.07 that is centered on the

joint. The exterior concrete box surface shall be clean and dry before the joint

membrane is applied. The outside surfaces of the top slab and both walls of every joint

shall be completely covered for the entire length of each joint. Where joining two

sections of joint membrane material, or where two ends meet, a 3 in. overlap shall be

provided. The overlapping strip shall be firmly pressed onto the end of the underlying370

strip to seal the joint. Joints between structure sections and wingwalls, between

wingwalls and spandrel walls, and between structure sections and headwalls or

spandrel walls shall also be covered with joint membrane. The manufacturer’s

application instructions shall apply in addition to the above requirements.

The joint membrane shall be maintained in its installed location centered on the

joint and shall not be damaged or dislodged during the backfilling operation.

714.11Method of Measurement

Precast reinforced concrete box structures or structure extensions, precast coated380

reinforced concrete box structures or structure extensions, precast headwalls, precast

wingwalls, cast-in-place reinforced concrete box structures or structure extensions,

cast-in-place coated reinforced concrete box structures or structure extensions, cast-

in-place headwalls, and cast-in-place wingwalls will not be measured. The accepted

quantities for payment will be the quantities shown on the plans.

Geotextile and riprap will be measured in accordance with 616.12. Structure

backfill will be measured in accordance with 211.09. Flowable backfill will be

measured in accordance with 213.08. Field drilled holes will be measured in

accordance with 702.27.390

Plain or coated reinforcement or WWR used in precast reinforced concrete box

structures or structure extensions, precast headwalls, precast wingwalls, cast-in-place

reinforced concrete box structures or structure extensions, cast-in-place headwalls, or

cast-in-place wingwalls will not be measured for payment.

If the Contractor elects to provide a three-sided structure in lieu of the box

structure shown on the plans, it will be measured in accordance with 723.17.

Additional geotextile and riprap placed within the limits of the three-sided box

structure will not be measured for payment.400

714.11

732

Additional excavation required for a culvert when the culvert is placed at an

elevation more than 1 ft below the elevation shown on the plans will be measured to

include the entire width needed to comply with OSHA or IOSHA requirements.

714.12Basis of Payment

The accepted quantities of precast reinforced concrete box structures or structure

extensions, precast coated reinforced concrete box structures or structure extensions,

cast-in-place reinforced concrete box structures or structure extensions, and cast-in-

place coated reinforced concrete box structures or structure extensions of the size410

specified will be paid for at the contract unit price per linear foot.

Geotextile or riprap will be paid for in accordance with 616.13. Structure backfill

will be paid for in accordance with 211.10. Flowable backfill will be paid for in

accordance with 213.09. Field drilled holes will be paid for in accordance with 702.28.

If the Contractor elects to provide a three-sided structure in lieu of the box

structure shown on the plans, the Department will not incur additional cost for

allowing the Contractor to substitute a three-sided structure for the box structure

shown on the plans.420

Payment will be made under:

Pay Item Pay Unit Symbol

Structure Extension, Coated Reinforced Concrete,

Box Sections, ____ ft x ____ ft .......................................... LFT

span rise

Structure Extension, Reinforced Concrete,

Box Sections, ____ ft x ____ ft .......................................... LFT430

span rise

Structure, Coated Reinforced Concrete,

Box Sections, ____ ft x ____ ft .......................................... LFT

span rise

Structure, Reinforced Concrete,

Box Sections, ____ ft x ____ ft .......................................... LFT

span rise

The cost of excavation except as provided in 206.11(a), expansion joint material,

perpetuation of existing drains shown on the plans, removal of portions of existing440

structures, cleaning out old channels or structures, chemical anchor system, precast

reinforced concrete structure joints, pipe joint sealant, joint membrane, and necessary

incidentals shall be included in the cost of the structure or structure extension.

The cost of precast concrete headwalls, precast concrete wingwalls, cast-in-place

headwalls, or cast-in-place wingwalls shall be included in the cost of the structure or

structure extension.

714.12

733

The cost of plain or coated reinforcement or WWR used in precast reinforced

concrete box structures or structure extensions, precast headwalls, precast wingwalls,450

cast-in-place reinforced concrete box structures or structure extensions, cast-in-place

headwalls, or cast-in-place wingwalls shall be included in the cost of the structure or

structure extension.

The cost of concrete used in a cast-in-place splice shall be included in the cost of

the structure extension.

The cost of designing a box structure, box structure extension, headwalls, and

wingwalls shall be included in the cost of the structure or structure extension.

460

The costs of coring, testing, excavation, repairs, plugging core and handling holes,

mortar, grout, sealer, cylinder molds, and necessary incidentals shall be included in

the cost of the structure. The cost of wingwall footing and the aggregate base shall be

included in the cost of the structure or structure extension.

No additional payment will be made for carrying an underground drain through a

structure or structure extension. However, no deduction will be made for the volume

of concrete occupied by the drain pipe in a cast-in-place structure or structure

extension.

470

No additional payment will be made for the repair or replacement of existing

concrete damaged by Contractor operations.