3804.1SCOPE

Provide liquid tight flexible non-metallic (LFNC-B) conduit and fittings for electrical systems.

3804.2REQUIREMENTS

Use liquid tight flexible non-metallic conduit meeting the following:

(1)Type LFNC-B
(2)Listed and labeled by NRTL as meeting the requirements of UL 1660, Liquid-Tight

Flexible Nonmetallic Conduit

(3)Listed for 176°F in a dry location
(4)Listed for 140°F in a wet location
(5)Listed for 158°F in an oily location
(6)Sunlight resistant
(7)Rated for outdoor use
(8)CSA certified for use at 167°F in dry and oily locations and for 0°F low temperature

applications Do not provide conduit using a metallic integral reinforcement within the conduit wall.