3842.1SCOPE

Provide the required electrical systems compounds and lubricants to Materials as specified in the Contract for lubricating and preventing corrosion and oxidation.

3842.2REQUIREMENTS

A Anti-seize and Lubricating Compound “Bridge Grease” Use an approved anti-seize and lubricating compound listed on the APL, Bridge and specified as “Bridge grease.” B Conductor Anti-oxidant Joint Compound Before terminating conductors, coat conductor ends and connectors with anti -oxidant joint compound meeting the following:

(1)Color: Black-Gray
(2)Temperature Range: -22°F to 2,450°F
(3)Thickener Type: Calcium Complex
(4)Particle Size: 3.5 Mil Maximum (75 microns)
(5)Density (G/CM3): 1.31 to 1.39
(6)ASTM D92, Standard Test Method for Flash and Fire Points by Cleveland Open Cup

Tester, Flash Point: >475°F

(7)ASTM B117, Standard Practice for Operating Salt Spray (Fog) Apparatus, Salt Fog Test,

Hours: 4,000

(8)ASTM D130, Standard Test Method for Corrosiveness to Copper from Petroleum Products

by Copper Strip Test, Copper Corrosion Test at 212°F, 24 hours: No Corrosion

(9)ASTM D217, Standard Test Methods for Cone Penetration of Lubricating Grease, Work

Penetration, 60 Strokes at 77°F: 260-310

(10)ASTM D217, NLGI Grade: 1/2
(11)ASTM D566, Standard Test Method for Dropping Point of Lubricating Grease, Dropping

Point: 572°F

(12)Torque Coefficient (K factor): 0.11
(13)ASTM D1264, Standard Test Method for Determining the Water Washout Characteristics

of Lubricating Grease, Water Washout, percent loss at 100°F: <1.00

(14)ASTM D1264, Water Washout, percent loss at 175°F: <2.75
(15)ASTM D1743, Standard Test Method for Determining Corrosion Preventative Properties

of Lubricating Greases, Bearing Rust Test: Pass

(16)ASTM D2596, Standard Test Method for Measurement of Extreme Pressure Properties of

Lubricating Grease (Four Ball Method), Four Ball EP Load Wear Index: 127.3

(17)ASTM D2596, Four Ball EP Last Non-Seizure Load (scar): 100 kgf
(18)ASTM D2596, Four Ball EP Last Seizure Load (scar): 620 kgf
(19)ASTM D2596, Four Ball EP Weld Load: 800 kgf
(20)ASTM D4170, Standard Test Method for Fretting Wear Protection by Lubricating

Greases, Fretting Wear at 73°F, 22 hours, milligram loss: 7.15 C Ferrous Metal Electrically-Conductive Corrosion Resistant Compound Provide a brush on ferrous metal electrically-conductive corrosion resistant compound on metal threaded conduit fittings to prevent corrosion, oxidation, improve conductivity, and the integrity of electrical connections.

(1)Color: Copper
(2)Content: 65 – 70 percent lubricating greases, 25 – 30 percent Copper, and less than

1 percent Zinc

(3)Flash Point: >590°F
(4)Initial Boiling point: >599°F
(5)Blend of pure polished colloidal copper, rust, and corrosion inhibitors
(6)Can be brushed on at – 50°F and 250°F
(7)Meeting NEC Article 300.6

3842.3SAMPLING AND TESTING

The Department reserves the right to sample, test, inspect, and accept or reject electrical systems compounds and lubricants based on its own tests.

Get an email when 3842 changes

Minnesota revises spec sections through supplementals and new editions. We check this one every week and email you the day it changes. Free, no account.

Source: Minnesota Standard Specifications for Construction, 2025 Edition. Pages 1033–0 of 1,081. View official source ↗

Ask about this section

Scoped to Minnesota 2025 Standard Specifications for Construction, Section 3842 — Electrical Systems Compounds and Lubricants. Every answer cites the section it came from, with a verification date — don’t trust a percentage, click the citation.