Electrical Systems Materials

3838Junction Boxes

MN · 2025 Standard Specifications✓ Full text on BuildSpecBook pages 1031–0 Save this section

Ask about Section 3838

Get a cited answer from the section text. Click the citation to check it.

One cited answer a day is free. Start a 14-day trial for unlimited, no card required.

3838.1SCOPE

Provide junction boxes on electrical systems when required for the following reasons:

(1)Accessing wiring
(2)Facilitating installation of wiring
(3)Changing from field cable wiring to individual conductors

3838.2REQUIREMENTS

A Underpass Luminaire System Junction Boxes Furnish and install approved PVC coated GRFX Body Type Hot Dipped Galvanized Ferroalloy Junction Boxes listed on the APL, Lighting, “PVC coated RMC” for underpass luminaire systems as shown on the Plans or when specified in the Contract. B Lighting System Junction Boxes Furnish and install junction boxes on bridges used for lighting systems other than underpass luminaire systems, meeting the following: Hot dip galvanized coated metal, PVC coated hot dip galvanized metal, or stainless steel Sized in accordance with NEC Article 314 NEMA Rated 3R or better NRTL Listed and Labeled

Installed with approved junction box drains and breathers (drilling a hole is not an approved drain and breather) Ensure junction boxes fit at specified locations under bridge decks, between bridge beams, and between bridge beams and abutments. C Wood Pole Junction Boxes Provide and install junction boxes on wood poles as shown on the Plans and meeting the following: Hot dip galvanized coated metal, PVC coated hot dip galvanized metal, or stainless steel Sized in accordance with NEC Article 314 NEMA Rated 3R or better NRTL Listed and Labeled Installed with drains and breathers Submit shop drawings of proposed junction boxes and mounting details in accordance with 3838.3 “Sample and Testing.”

3838.3SAMPLING AND TESTING

Submit three sets of shop drawings of the proposed metal junction boxes and mounting details to the Engineer for approval.

Get an email when 3838 changes

Minnesota revises spec sections through supplementals and new editions. We check this one every week and email you the day it changes. Free, no account.

Source: Minnesota Standard Specifications for Construction, 2025 Edition. Pages 1031–0 of 1,081. View official source ↗