952.1DESCRIPTION—This work is the furnishing and installation of a traffic signal controller assembly of
the type indicated.
952.2MATERIAL—
• Class A Cement Concrete. Section 704
• Caulking Compound. Section 705.8(b)
• Traffic Signals-General. Section 950.2
• Traffic Signal Systems and Communications. Section 953.2
• Electrical Distribution. Section 954.2
• Signal Heads. Section 955.2
• Certification. Section 106.03(b)3
• Provide high resolution controller event logging conforming to the Indiana Traffic Signal Hi Resolution Data Logger Enumerations.
• Allow log files to be retrievable by a remote connection or a local connection. Provide and enable functionality to automatically back up the log files to Universal Serial Bus (USB) flash drive or Secure Digital (SD) card. Log files must be retained within the controller’s local memory for a minimum of 24 hours and archived on external storage within the cabinet for a minimum of 365 days. Log files must be provided in comma separated text (CSV) format containing the event timestamp, event code and event parameter on each line. If the log files are in a different format, the manufacturer must provide a translator tool which converts the log files to CSV format. The translator tool must be able to be run from the command line for files to be batch converted.
• Current NTCIP 1202. Object Definitions for Actuated Traffic Signal Controllers (ASC)
• Signal Circuits. 12 minimum or as indicated.
1.a Standards.
• TS 1, Section 2, Environmental Standards and Test Procedures.
• TS 1, Section 13, Interface Standards.
• TS 1, Section 14, Solid-State Traffic Signal Controller Units.
• TS-2, Section 2, Environmental Standards and Test Procedures.
• TS-2, Section 3, Controller Standards and Coordination.
• TS-2, Section 5, Interface and Electrical Standards.
• TS-2, Section 8, Bus Interface Unit Requirements.
• NEMA Standards Publication TS 2-“Current Edition”.
1.b Controller Requirements.
• All hardware and software must be according to NEMA TS-1, TS-2 standards, and as directed.
• All cabinets require a plug-in hand control with cord and a method of switching the signal controller between automatic and manual control.
• Include ability to accept a contact closure or open controller output to reset clock on controller at a predetermined hour each day.
• Provide communication equipment as indicated and as specified in Section 953.2.
• Controller must be IP/Ethernet enabled for communications on IP networks.
1.c Conflict Monitor/Malfunction Management Unit.
• TS 1, Section 6, Conflict Monitor.
• TS 2, Section 2.3, Malfunction Management Unit Test.
• TS 2, Section 4, Malfunction Management Unit.
• Conflict monitor must monitor absence of red indications and be compatible with Flashing Yellow Arrow permitted left turn operation.
• IP/Ethernet enabled for communications on IP networks.
A minimum of one input channel for each load switch socket as specified in Section 952.2(c)1.e.
1.d Flasher Unit.
• TS 1, Section 8, Solid State Flasher.
• TS 2, Section 2.6, Flasher Tests.
• TS 2, Section 6.3, Solid-State Flasher.
1.e Load Switches.
• TS 1, Section 5, Solid-State Load Switches.
• TS 2, Section 2.5, Load Switch Tests.
• TS 2, Section 6.2, Three-Circuit Solid State Load Switch
• Operational Features: Provide Light Emitting Diode (LED) indicators to display operation. Isolate signal load from load switch input using optic couplers. Furnish a minimum of one load switch for each of the following active controller unit functions:
ͦ Vehicle Phase. ͦ Overlapping Vehicle Phase. ͦ Pedestrian Phase.
1.f Cabinet. Furnish a weatherproof controller cabinet, large enough to suitably house the traffic signal controller unit and auxiliary equipment, and conforming to the following requirements:
1.f.1 Enclosure.
• Material. Sheet or cast aluminum.
• Wall Thickness. 1/8-inch minimum, reinforced where required.
• Minimum Size. As shown on the Standard Drawings and as follows: Position equipment in the cabinet to provide access to all terminal strips and equipment from the front without removing other equipment. Provide an unobstructed view of all equipment having visual indicators. Place all equipment in an upright position and not on top of other equipment.
Provide Department approved controller cabinet with adequate room for all necessary equipment and cable. Provide stainless steel 5/8 -inch handle designed for the door(s) and a full height, continuously welded, piano hinge. Continuously weld all joints of the cabinet. Provide a pull-out shelf to double as a storage container for wiring diagrams, plans, and timing sheets.
Provide a twist lock receptacle and transfer switch for power provided by an emergency generator during power outages. Access to the twist lock receptacle and the transfer switch thorough the use of a locked police door using a No. 2 key or standard police key.
Provide generator adaptor kit as specified in Section 954.2(i).
Provide door with continuous stainless-steel door hinge on right side, door stop at 90 degrees and 180 degrees, ± 10 degrees, for all doors over 22 inches wide, auxiliary door for access to police panel, pocket for prints.
• Type I Cabinet Extension . Provide cabinet with a base extension of not less than 18 -inches nor more than 36-inches or as indicated. If an Uninterruptible Power Supply is to be provided include a shelf for the Uninterruptible Power Supply unit and associated batteries.
• Auxiliary Cabinet. At locations where traffic signal equipment is to be installed in an existing controller assembly where physical space constraints preclude installation in the existing cabinet, provide auxiliary cabinet assembly, either:
ͦ Attached to existing Ground Mounted Controller cabinet with bottom of auxiliary cabinet resting on top of existing cabinet foundation; or ͦ Pole-mounted, located adjacent to the existing pole-mounted cabinet.
Provide cabinet that meets or exceeds applicable specifications herein for a traffic signal controller assembly.
• Hardware. Vandal and corrosion resistant.
• Finish. Natural with external welds free of irregularities and a maximum bead height of 1/8-inch.
• Gaskets. Neoprene, attached with an oil resistant adhesive.
• Mountings. As indicated, pole or foundation.
• Locks. Brass, tumbler type for main door and standard police lock for auxiliary door; two keys for each lock.
• Latching Mechanism. One point-through mechanism for doors less than 22 -inches in width; three point-through mechanism for doors -22 inches or wider.
• Interior. Shelf-mounted equipment unless rack or panel-mounted.
• LED light/bar with in-door switch.
• Spring-loaded door switch in the upper right corner of cabinet opening for use as a door open alarm. If the controller cabinet is connected to a RTMC or central system, the door open alarm must place a notification to the RTMC or central system.
• Test Pushbutton Panel. One pushbutton to each input for simulated detector operation of vehicles and pedestrians with type and phase permanently labeled on panel. Mount panel on inside of door.
• Back panels, wiring and terminals must accommodate at a minimum eight phases Actuated. There must be a minimum of 12 to 16 Load Switch Sockets, with a minimum of two unused sockets per unit.
1.f.2 Fan and Ventilation.
• Fan and vent system providing 200 cubic feet of free air delivery per minute (CFM), 2x100 CFM fans, for type I or dark painted controller assemblies or 100 CFM for type II controller assemblies.
• Vents equipped with standard-size, replaceable fiberglass filters.
• Vents that prohibit the entrance of rain and snow.
• Cabinet equipped with an adjustable thermostat connected to control the fans.
• Manually adjustable thermostat with a calibrated scale. Thermostat adjustable within the range of at least 55F to 140F.
• Thermostat with contacts rated for at least eight amperes at 120 volts AC.
• Thermostat capable of turning the fan on at the set temperature and turning the fan off when the temperature is 5F below the set temperature. The activation temperature must be set by the cabinet manufacturer based on their recommendations.
• A temperature sensor must provide an alarm for cabinet overheating. Activate the alarm at 150F. If the controller cabinet is connected to an RTMC or central system, the temperature alarm must place a notification to the RTMC or central system.
2.a Standards. Comply with current Type 2070 controller industry standards.
2.b Controller Requirements.
• Program module as approved.
• Communications module as approved
• Processor module as approved
• Power supply module as approved
• The 2070 microcomputer is to have a vertical board design with separate input and output boards.
• Include ability to accept a contact closure or open controller output to reset clock on controller at a predetermined hour each day.
• Equip the controller with four serial communication ports and one Ethernet port, each capable of communicating at speeds up to 9600 bits/sec. The port assignments are to be as follows:
ͦ Port 1: Internal Modem ͦ Port 2: PC Laptop Connection ͦ Port 3: Conflict Monitor Communication ͦ Port 4: Future Use ͦ Port 5: Ethernet
• Provide 2070-1E or 2070-1C prom module.
ͦ Data retention in the absence of Controller Voltage (Vcc). ͦ Data is automatically protected during power loss. ͦ Directly replaces 8K x 8 volatile static RAM or EEPROM. ͦ Unlimited write cycles. ͦ Low-power CMOS. ͦ Over 50 years of data retention. ͦ Standard 28-pin JEDEC pin out. ͦ 200 ns read access time. ͦ Read cycle time equals write cycle time. ͦ Lithium energy source is electrically disconnected to retain freshness until power is applied for the first time. ͦ Industrial temperature range of -40F to 185F.
• Furnish all controller assemblies so that the controller returns to normal operation from time clock flash automatically.
• All cabinets require a plug-in hand control with cord and a method of switching the signal controller between automatic and manual control.
• Provide for automatic return to flashing operation when lost electrical service has been restored.
• The "Flash Sense", "Stop Time", and "Cabinet Door Open" functions to be optically isolated but capable of operating without a Model 242 DC isolator.
• Provide pre-wired input file with a minimum of eight inputs and equipped with Model 242 Two- Channel DC isolators. Supply the required number of Model 242 DC isolators, plus one spare, for each intersection. Also, provide slots and internal wiring for two future model 224 four - channel loop sensing units.
• Provide Fiber Modem for the communication between local controller and master controller. Clean and connect fiber -optic cable to the new controller using procedures described in current Department and industry guidelines – FOA.
• Provide software as directed by special provision unless provided by the municipality.
• Controller must be IP/Ethernet enabled for communications on IP networks.
2.c Conflict Monitor. Provide Model 2070 Malfunction Management Unit. Exception: If mounted in a 336 cabinet, provide conflict monitor using serial datalink communication line (SDLC) interface. Equip the conflict monitor with a programmable SDLC interface capable of communicating with the 2070 Microcomputer. The conflict monitor, if polled by a system compatible 2070 Microcomputer, is to return information including, but not limited to, the status of all monitored inputs and events stored in non-volatile memory. Also monitor the absence of a red indication along with normal conflicts, and perform all the functions required by a conflict monitor, including the following features:
• Monitoring the absence of signal on any channel.
• Include three preemption inputs to disable red monitoring.
• Include red signal monitoring interface through front panel connector.
• Detect simultaneous display of Green and Yellow on a channel.
• Detect simultaneous display of Green and Red on a channel.
• Detect minimum Yellow display following a Green on a channel.
• Store of up to 64 events.
• Inform 2070 controller of a resetting via a communication port.
• Monitor incoming line voltage.
• Conflict monitor must monitor absence of red indications and be compatible with Flashing Yellow Arrow permitted left turn operation.
• IP/Ethernet enabled for communications on IP networks.
A minimum of one input channel for each load switch socket as specified in Section 952.2(c)3.e.
2.d Flasher Unit.
• TS 1, Section 8, Solid State Flasher.
• TS 2, Section 2.6, Flasher Tests.
• TS 2, Section 6.3, Solid-State Flasher.
2.e Load Switches.
• TS 1, Section 5, Solid-State Load Switches.
• TS 2, Section 2.5, Load Switch Tests.
• TS 2, Section 6.2, Three-Circuit Solid State Load Switch.
• Provide compatible Load Switches or Packs.
• Provide a minimum of 12 pre-wired switch positions as indicated.
• Provide a load switch is to be of a repairable, modular type construction.
• Provide a minimum of four flash transfer relays.
• Operational Features: Provide LED indicators to display operation. Isolate signal load from load switch input using optic couplers. Furnish a minimum of one load switch for each of the following active controller unit functions:
ͦ Vehicle Phase. ͦ Overlapping Vehicle Phase. ͦ Pedestrian Phase.
2.f Cabinet. Furnish a weatherproof controller cabinet, large enough to suitably house the traffic signal controller unit and auxiliary equipment, and conforming to the following requirements:
2.f.1 Enclosure.
• Material. Sheet or cast aluminum.
• Wall Thickness. 1/8-inch minimum, reinforced where required.
• Minimum Size. As indicated and as follows:
Position equipment in the cabinet to provide access to all terminal strips and equipment from the front without removing other equipment. Provide an unobstructed view of all equipment having visual indicators. Place all equipment in an upright position and not on top of other equipment.
Provide Department approved Type 2070 controller cabinet with adequate room for all necessary equipment and cable. Provide a stainless steel 5/8 -inch handle designed for the door(s) and a full height, continuously welded, piano hinge. Continuously weld all joints of the cabinet. Provide a pull-out shelf to double as a storage container for wiring diagrams, approved plans, and timing sheets.
Provide a twist lock receptacle and transfer switch for power provided by an emergency generator during power outages. Access to the twist lock receptacle and the transfer switch through the use of a locked police door using a No. 2 key or standard police key.
Provide generator adaptor kit as specified in Section 954.2(i).
The latching mechanism will be a three -point draw roller. Equip the large cabinet door with a spring lock, which can be opened only by a key. Equip the smaller compartment door with a similar spring lock, which can be opened only by a standard police box key.
An approved plug-in hand control is required in all cabinets and a method to switch the signal controller from automatic to manual control.
• Type I Cabinet Extension . Provide cabinet with a base extension of not less than 18 -inches nor more than 36-inches or as indicated. If an Uninterruptible Power Supply is to be provided include a shelf for the Uninterruptible Power Supply unit and associated batteries.
• Auxiliary Cabinet. At locations where traffic signal equipment is to be installed in an existing
controller assembly where physical space constraints preclude installation in the existing cabinet, provide auxiliary cabinet assembly, either:
ͦ Attached to existing Ground Mounted Controller cabinet, with bottom of auxiliary cabinet resting on top of existing cabinet foundation; or ͦ Pole-mounted, located adjacent to the existing pole-mounted cabinet.
Provide cabinet that meets or exceeds applicable specifications herein for a traffic signal controller assembly.
• Hardware. Vandal and corrosion resistant.
• Finish. Natural with external welds free of irregularities and a maximum bead height of 1/8 -inch.
• Gaskets. Neoprene, attached with an oil resistant adhesive.
• Mountings. As indicated, pole or foundation.
• Locks. Brass, tumbler type for main door and standard police lock for auxiliary door; two keys for each lock.
• Police Panel. Furnish with the following switches:
ͦ Auto. Flash ͦ Lights (On/Off) ͦ Auto. Manual ͦ Provide 12-inch hand control cable in panel. The police panel must be large enough to adequately store the hand control cable.
• LED light/bar with in-door switch.
• Spring-loaded door switch in the upper right corner of cabinet opening for use as a “door open” alarm. If the controller cabinet is connected to an RTMC or central system, the “door open” alarm must place a notification to the RTMC or central system.
• Test Pushbutton Panel . One pushbutton to each input for simulated detector operation of vehicles and pedestrians with type and phase permanently labeled on panel. Mount panel on inside of door.
2.f.2 Fan and Ventilation.
• Fan and vent system providing 200 CFM, 2x100 CFM fans for type I or dark painted controller assemblies or 100 CFM for type II controller assemblies.
• Vents equipped with standard-size, replaceable fiberglass filters.
• Vents that prohibit the entrance of rain or snow.
• Cabinet equipped with an adjustable thermostat connected to control the fans.
• Manually adjustable thermostat with a calibrated scale. Thermostat adjustable within the range of at least 55F to 140F.
• Thermostat with contacts rated for at least eight amperes at 120 volts AC.
• Thermostat capable of turning the fan on at the set temperature and turning the fan off when
the temperature is 5F below the set temperature. The activation temperature must be set by the cabinet manufacturer based on their recommendations.
• A temperature sensor must provide an alarm for cabinet overheating. Activate the alarm at 150F. If the controller cabinet is connected to an RTMC or central system, the temperature alarm must place a notification to the RTMC or central system.
3.a Standards. Provide a controller cabinet assembly that includes an Advanced Transportation Controller (ATC) timer unit and a cabinet meeting the specifications as described below:
• For the purposes of interfacing with the Department's unified command and control system, provide one of the following:
ͦ The complete Management Information Bases (MIB) for the controller firmware to ensure compatibility of both ends of the communications link. Notify PennDOT when new MIBs are released and provide them when requested for the life of the controller at no additional cost to the Department. Controller manufacturer must retain ownership of the MIB and grant PennDOT and its contractors a license to use the MIB for interfacing with the controller through the unified command and control system. PennDOT will keep the MIB confidential, proprietary, and will not redistribute or reuse the MIB for other purposes. ͦ MIBs which match the objects provided by the Department’s unified command and control system. Controller manufacturer must provide validation testing of the MIB mapping to the unified command and control system.
- Provide future controller firmware updates to PennDOT for testing with the unified command and control software before being installed on controllers.
• Provide functionality to back up the controller database to USB flash drive or SD card after any programming change.
• Obtain IP address as required by the latest PennDOT Traffic Signal Remote Communication Policy and Guidance Document.
• 4GB (minimum) USB drive with tether or SD card.
3.b Controller Requirements.
• Program module as approved.
• Controller unit meets ATC 5201 v06.25 according to AASHTO/ITE/NEMA.
• Provide the following minimum memory:
ͦ Minimum of 128 megabyte (MB) of dynamic random-access memory ( DRAM) for application and Operating System (OS) program execution. ͦ Minimum of 64 MB of Flash memory for storage of OS software and user applications. ͦ Minimum 1MB of static random-access memory (SRAM) for non-volatile parameter storage. - Rack- mounted configuration - Display model, serial number, and program information on exterior in an easy to find location.
• USB Ports.
ͦ Minimum of two USB 2.0 ports to be used for updating software, uploading or downloading configurations, or uploading logged data via USB flash drives.
• Label the IP address on the timer unit according to ANSI/TIA-606-B standard as a guideline and the following:
ͦ Laminated ͦ High strength ͦ Resistant to extreme environmental conditions such as UV fading, high temperature fluctuations, and high humidity ͦ Adheres to aluminum, polycarbonate, and other materials standard in roadside cabinet environment. ͦ Text is bold, legible (Arial font, 24 pt. minimum), and fade resistant.
• Firmware Options.
ͦ Provide the ability for peer -to-peer communication once per second minimum between controllers of the same model type using Ethernet protocol communication. ͦ Such communication will not require the use of any external device or software and will not require routing to or from any external program. ͦ Configuration and saving of peer -to-peer setup information will not require restart of the controller to take effect. ͦ Provide controller capable of acting as either the source or the destination of Boolean & Peer statements. ͦ Provide a minimum of 24 peer-to-peer statements available to the user at each controller.
• Connected Vehicle Requirements.
ͦ Provide a controller that generates signal phasing and timing (SPaT) status in NTCIP 1202 format every 1/10 of a second to a user -configurable IP address via a user -configurable UDP port. ͦ Provide necessary hardware to broadcast signal phasing and timing in SPaT format according to SAE J2735 messaging or provide firmware to be installed on a Dedicated Short-Range Communication (DSRC) Roadside Unit (RSU) to translate the message into J2735 format. Do not use an additional component between the controller and DSRC RSU for the purpose of SPaT data translation. If SPaT format is used directly from the controller, map the phases to lanes via the controller’s menu-driven interface or external program running on a PC.
• Railroad Preemption Requirements.
ͦ Provide the railroad preemption operation as indicated. Before approval of controller catalog cuts for the project, any controller unit proposed for use on a PennDOT contract project is required to be bench-tested along with the PennDOT Traffic Unit representative for any traffic signals with railroad preemption. The controller proceeds immediately to railroad preemption operation upon receiving call without any delay. ͦ Provide interface and/or interconnect as specified in Section 953.2(l).
3.c Cabinet. Final cabinet design must be agreed upon by the District Traffic Engineer or designee, as specified in Section 952.2(c)2.f. and as follows:
• AASHTO/ITE/NEMA ATC 5301 v02.02 or latest approved version.
• LED light bars, 800 lumens minimum.
• Provide a stainless steel 5/8 -inch handle designed for the door(s) and a full height, continuously welded, piano hinge. Continuously weld all joints of the cabinet.
• Sliding aluminum “laptop shelf” with piano hinged lid capable of holding the cabinet manuals and intersection condition diagram.
• IP-addressable Cabinet Monitor Unit (CMU) compatible with Flashing Yellow Arrow permitted left
turn operation.
• One NEMA L5-30P receptacle for external generator connection.
• An automatic transfer relay to engage the generator power.
• Component and cable labels conforming to the following:
ͦ Laminated ͦ High in strength ͦ Manufactured for extreme environmental conditions with respect to UV, temperature, and humidity. ͦ Capable of adhering to all types of surfaces ͦ Bold, legible and fade resistant text ͦ Band or flag type
• Clear plexiglass cover/protection on any open area with live electrical fee
• One rack-mounted IP-addressable rear-facing six-outlet (minimum) power strip with 120V 15-amp, capable of resetting upon failed IP ping or via remote web interface.
• A rack-mounted test button panel that allows calls to be placed on each individual vehicle and pedestrian phase.
• Auxiliary Display Unit.
• 16 channel output minimum.
• 24 channel input minimum.
• One front-facing duplex convenience receptacle (120V, 15amp), or two receptacles integrated to the front of the power supply.
• Full cabinet electrical schematic(s) including all location-specific field terminal connections.
• Copy of the PennDOT traffic signal permit drawing for the intersection and for the system (if applicable). Detector mapping information to indicate which detector is on which channel and phase.
• A police cord of at least twelve feet in length in the police switch compartment.
• Type I Cabinet Extension . Provide cabinet with a base extension of not less than 18 -inch nor more than 36-inch or as indicated. If an Uninterruptible Power Supply is to be provided include a shelf for the Uninterruptible Power Supply unit and associated batteries.
• Provide generator adaptor kit as specified in Section 954.2(i).
• Fan and Ventilation.
ͦ Fan and vent system providing 200 CFM, 2x100 CFM fans. ͦ Vents equipped with standard-size, replaceable fiberglass filters. ͦ Vents that prohibit the entrance of rain or snow. ͦ Cabinet equipped with an adjustable thermostat connected to control the fans. ͦ Manually adjustable thermostat with a calibrated scale. Thermostat adjustable within the range of at least 55F to 140F. ͦ Thermostat with contacts rated for at least eight amperes at 120 volts AC.
ͦ Thermostat capable of turning the fan on at the set temperature and turning the fan off when the temperature is 5F below the set temperature. The activation temperature must be set by the cabinet manufacturer according to their recommendations. A temperature sensor must provide an alarm for cabinet overheating. Activate the alarm at 150F. If the controller cabinet is connected to an RTMC or central system, the temperature alarm must place a notification to the RTMC or central system.
1.a Light Duty Relay. Mounted in a clear, plastic cover, permanently marked to indicate coil voltage rating, and as follows:
• Usage. Logic, Preemption or Interconnection.
• Voltage. 115 V (ac) or 24 V (dc).
• Switch Type. TPDT or DPDT.
• Contact Rating. 2 A.
• Contact Material. Fine Silver or Silver Alloy.
1.b Heavy Duty Relay. Mounted in a clear, plastic cover, permanently marked to indicate coil voltage rating, and as follows:
• Usage. Continuous Duty-Transfer of signal indications from normal operation to flashing and the reverse.
• Voltage. 95V to 135 V (ac), 57 Hz to 63 Hz.
• Switch Type. DPDT.
• Contact Reading. 20 A.
• Contact Material. Fine Silver or Silver Alloy.
• Standard Socket. 8 Pin, Jones Type.
load center, police panel switches, signal load switches, signal cable terminals, controller unit, conflict monitor, detectors, and relays, and as follows:
• Wiring. Arrange and lace or enclose in a raceway or in plastic tubing.
• Terminal Blocks . Barrier-type, with marker strips and nickel -plated brass screws, 8 -5/16-inch minimum for detector leads, 10-5/16-inch minimum for signal leads, rated for 20 A at 1000 V (rms).
3.a Breakers and Receptacles.
• Circuit Breakers. 15 A minimum, flashing circuit and duplex receptacle. 15 A minimum, traffic control equipment.
• Duplex Receptacle . National Electrical Code (NEC) -Type, Ground Fault Interrupter, with test buttons. 15 A minimum.
3.b Radio Frequency Interference (RFI). UL-Listed, RFI filter, according to NEMA standard testing procedures, TS-2 chapter 5, and as follows:
• Line Voltage. 95 V to 135 V (ac).
• Line Frequency. 200kHz to 75MHz with minimum attenuation of 50dB.
• Line Current. 125% of the total connected load, 30 A minimum.
• Operating Temperature. -29F to 165F.
• Insulation Resistance. 6,000 megaohms.
• Line to Ground Rating. 1500 V (ac), one minute.
• Line to Line Rating. 1450 V (dc), one minute.
• Humidity Range. 5% to 95%, relative.
• Overload. 360 A, for 8 minutes.
3.c Surge Protection. Provide serial surge protection that has multi -strike capability, UL listed, and line to neutral clamping voltage to be no more than 395 V at 20,000 amps. Provide model that is plug interchangeable with wired -in based with plug removable arrester. Provide terminals for AC Line, AC Neutral, AC Equipment In, AC Equipment Out, neutral equipment out, and ground. Filtering surge protector is not to exceed 5.0 -inches x 3.5 -inches x 7.5 -inches, not including studs or mounting flange. Spark gap arrestors are not allowed. All surge protection devices must be approved. The cabinet and content must, as an assembly, pass all NEMA TS-2 voltage spikes test for the AC line.
• Total Peak Current (8 x 20ms) 40,000 Amps
• Life Test 5% Change
• (Voltage clamp before and after 25 surges of 20 kA waveshape)
ͦ Clamp voltage 395 V type @ 20kA
ͦ Response time less than 5.0 nS
ͦ Continuous Service Current (120 VAC, 20 Amps Maximum 60 Hz)
ͦ Operating Temperature -40F to 185F
Provide surge suppressor that is UL listed and has dual pair (four wire) module implementing three stage hybrid technology or equivalent type as approved, for communications cable to 10 kA (2500 A per line).
• Peak Surge Current (10 times):
ͦ 8 x 20 ms 50 kA
ͦ 10 x 700 ms 500 A per line
• Life Expectancy:
ͦ 8 x 20 ms >100 occurrences
ͦ 10 x 700 ms
• Response time < 1 nanosecond
• Technology SAD Hybrid
• Operating Temperature -40F to 185F
Provide composite Transient Voltage Surge Suppression (TVSS) for all pedestrian pushbutton circuits, each load switch. And on the detector panel for all loop lead-ins.
3.d Grounding Requirements. Provide each controller with its own grounding rod in addition to the other grounding requirements for signal supports. Grounding and Grounding Rods will be installed as shown on the Standard Drawings and as follows: Place a minimum of two grounding rods at the base of the controller, the grounding system is required to provide 8 ohms or less to the earth as a system. Test all grounding rods used for controllers, mast arms, and supports for their resistance to ground in accordance with the NEC; with resistance less than 25 ohms. For grounding rods failing the above-mentioned test, relocate grounding rod(s) to a suitable location or install additional grounding rods at locations as approved. When suitable, place a grounding grid utilizing shielded copper wire and grounding rods at each corner, around the intersection. Documentation regarding grounding resistance and as -built plans of grounding grid must be verified by the Representative.
• Auto. Flash
• Lights. (On/Off)
• Auto. Manual
Provide 12” hand control cable in panel. The police panel must be large enough to adequately store the hand control cable.
Provide an auxiliary cabinet assembly, either:
• Attached to an existing ground mounted controller cabinet; or
• Ground-mounted, located adjacent to the existing ground-mounted cabinet; or
• Pole-mounted, located adjacent to the existing pole-mounted cabinet.
Refer to the traffic signal plans for specific lock and key instructions.
easy to read high contrast Liquid -crystal Display (LCD) screen for mounting in the traffic controller enclosure. The base unit must indicate the GPS time and other configuration settings on the LCD screen. The system must have a contact closure or open controller output to reset the controller clock. The GPS receiver must be connected directly to the contact closure and continuously reset the controller clock. However, if the controller limits this ability, the base unit must reset the controller clock at a predetermined hour each day (typically 3:00 AM). The system must have a Daylight Savings Time (DST) adjustment and zone adjustment entries as well as time setting. The GPS must maintain the accuracy of the controller clock within 1 microsecond of Universal Time, Coordinated/Greenwich Mean Time (UTC/GMT). The system must have an environmental temperature range of -68F to +158F, power requirements of 5-40 volts DC, 100 mA, and be capable of monitoring a minimum of eight channels .
952.3CONSTRUCTION—Sections 950.3, as shown on the Standard Drawings, and as follows:
indicated. For base -mounted controller assemblies, construct the foundation as specified in Sections 951.3(a) and (b) and seal all conduits as specified in Section 954.3(c). Place cabinet to provide full access to all doors and to not obstruct vehicle sight distances or block pedestrian facilities. Connect field wiring for signals, interconnect, and preemption. Connect service to the input/output terminals of the controller assembly. Neatly bundle, tie-wrap, and organize all loose wiring. Connect to the equipment safety ground. Ground loop detector lead -ins in cabinet only. Terminate all spare signal conductors collectively and cover with electrical tape. Label all detector lead -ins appropriately and map into timer unit to collect appropriate data. Install one LED light/bar inside the top of the cabinet at each door. If a two -door cabinet (one front and one rear) provide two lights/bars. If a four -door cabinet (two front and two rear) provide four light/bars. Install the lights/ bars such that the center of the light/bar is in front of and illuminating the component faces. Illuminate the lights with door-open switch. Provide switches, controls, and indicators that are operable without the use of tools. Clearly and permanently identify the switches, controls, and indicators. Label the load switch sockets and cable connectors for detector amplifiers, in the controller assembly, according to function. When the signal controller becomes operational, and during initial turn-on, demonstrate that all functions are operating in accordance with all the design documents and the applicable standards for the installed unit. Conduct the demonstration, as directed, in the presence of the Representative. Upon successful demonstration that all functions are operating properly the controller will be subject to a 30-day system test. If a fault occurs during the 30 -day test period correct the problem and restart the test. Once the 30 -day period has expired with no recordable system faults and meets the approval of the Representative the system will be considered for final acceptance. Connect the conflict monitor or malfunction management unit to function as specified in Section 952.2(c). When the controller assembly becomes operational, and during initial turn-on, demonstrate that the conflict monitor or malfunction management unit will cause transfer of the signals to flashing operation upon sensing all possible conflicting signal indications. Conduct the demonstration, as directed, in the presence of the Representative. The 30 -day system test must not begin until the conflict moni tor or malfunction management unit is functioning properly. Before or during the initial turn-on, connect output from shutdown relay to the output and power input of the signal load switches. Connect relay to controller assembly to provide flashing operation with the traffic signal controller unit installed or removed. Provide activation of the shutdown relay from any of the following sources:
• Removal of controller voltage, when indicated
• Police panel switch
• Output from conflict monitor or Malfunction Management Unit
Label IP address on all devices in the cabinet that are assigned an IP address. Provide surge suppression for any Ethernet cable leaving the cabinet. Provide municipality with the name and telephone number of
the person to be notified if failures or malfunctions occur during the guarantee period as specified in Section 950.3(d)10. Place all schematics, plans, detector mapping information and any other provided paperwork in the sliding drawer. Mount the exhaust fan(s) in such a way that it does not protrude to the outside of the cabinet and can be easily removed for servicing. Connect systems and communication control equipment as specified in Section 953.3 and as indicated. Before the 30-day system test, field test for the indicated operation as specified in Section 953.3(r).
• Configure the cabinet as follows from top to bottom:
ͦ Fiber patch panel ͦ Auxiliary Display Unit ͦ Controller unit - Laptop shelf ͦ Input file(s) ͦ Output file(s) ͦ Battery back-up and batteries (if specified). ͦ Ethernet switch (if specified) mounted to DIN rail on wall of cabinet in rear and accessed through rear door. ͦ Power supply
• Provide cabinet documentation and labeling as follows:
For signal controller, fiber optic cable, sensor devices, ITS, communications, connected vehicle, and any additional components provide interconnection diagram showing cable and port connections. Label all components and cables using the ANSI/TIA-606-B standard as a guideline and the following:
• Label each component with an identifier that corresponds to the interconnection diagram.
• Label cables at both ends. Provide information on each cable end to indicate the near and far end connections.
• The cable end with the label is considered the near end; the opposite cable end is considered the far end.
• Label all detector lead -ins as per the PennDOT Automated Traffic Signal Performance Measures
• Label text:
ͦ Indicate the near end component identifier and port connection on the first line. ͦ Indicate the far end component identifier and port connection on the second line. ͦ Indicate the system or network title on the third line. ͦ Abbreviations are acceptable if they are consistent between the interconnection diagram and the component identifier.
• Submit for approval any adjustments or modifications to labeling convention.
• Install the IP-addressable power strip in the rear rack. Plug the following auxiliary devices into the IP-addressable outlets and other components as directed:
ͦ Communications equipment (e.g. Ethernet switch, cell modem, router/firewall, etc.) ͦ Detection equipment (e.g. video, radar)
ͦ Adaptive system processor
• Install test button panel in the front rack.
• Operate SDLC Port 1 on Serial Bus #2 as needed.
• Provide and program a spring-loaded door switch in the upper right corner of the cabinet opening for use as a “door open” alarm. If the controller cabinet is connected to an RTMC or central system, the “door open” alarm must place a notification to the RTMC or central system.
• Provide a spare SIU and a spare high-density switch pack.
• Tether USB drive to a shelf or other permanent piece of the cabinet.
Record the existing timing of each controller. Make two copies placing one in the controller cabinet while retaining the other. The record consists of a copy of the timing and phasing diagram and includes the date, the change made, the name of the person authorizing the change, and the name of the person making the change. Before making a timing change, check the existing timing settings and verify that they are as indicated on the most recent record. Notify the Representative if unauthorized timing changes have been made. Provide a copy of each change of record.
controller cabinet using a waterproof sealant. Install the time clock base unit (if needed) in the controller cabinet and c onnect to input/output terminals to the controller according to the manufacturer’s recommendations. Connect to the equipment safety ground. Program the controller as needed to receive the GPS signal and reset the controller clock a minimum of once per day. Field test for indicated operation.
is wired for the maximum phase capability of the controller unit.
coded controller terminals as directed by the Representative. Crimp-type connectors are not to be used for traffic control cable or interconnection cable. All wiring and cable connections are to be neat and with all such cables tie-wrapped. Spare conductors of signal cable and interconnection cable are to be neatly wrapped in the cabinet and of the same length as the active conductors. Connect all communication cable conductors to the terminal block. Mount on the inside of the lower left cabinet wall a communication cable terminal block. The terminal block is to have a sufficient number of connections to splice two 12-pair communication cables together. If applicable, mount on this panel an RS-232 interface for connecting a portable PC to the 2070 Microcomputer. The RS-232 interface is to consist of a shielded cable with a DB9 connector at one end, and a 2070 C2 type connector at the other. Plug the DB9 connector into the C2 port of the 2070 controller.
internal diameter conduit as specified in Section 954. Run a continuous conduit segment from the base of the pole, through the bottom entry hub of the junction box, and into entry hub in the bottom of the Controller Cabinet. Place conduit to maintain the minimum bend radius of fiber optic cable. The conduit from the cabinet to the closest junction box or manhole is incidental to this item. The cabinet is to have the means to hold service loops, each 20 feet in length, of each of the jacketed fiber optic cables entering and leaving the cabinet. Secure each service loop to the bottom of the lowest rack in the cabinet in such a way as to ensure the minimum bend radius of the cable(s ) and prevent interference of any kind. However, the service loops are to be easily removed and reattached during fiber maintenance. Carefully route the fiber optic cable(s) to the patch panel for termination. The cabinet is to have a patch panel as necessary, mounted on an easily removable aluminum panel, to house all internal fiber splices; mount the aluminum panel in an appropriate location inside the cabinet. Secure the fiber optic cable(s) to the panel before entering the patch panel. Terminate all field fibers in the
cabinet as specified in Section 953.3(i) . If applicable, mount on this panel an RS -232 interface for connecting a portable computer to the 2070 microcomputer. The RS-232 interface is to consist of a shielded cable with DB9 connect at one end, and a 2070 C2 type connector at the other. Mount the DB9 connector on the panel for easy access, and the C2 type connector plugged into the C2 port of the 2070 controller.
power supply according to NEC requirements. If applicable, pour the new concrete foundation for the supplemental cabinet against the existing controller cabinet foundation and/or connect the supplemental cabinet to the existing controller cabinet with rigid galvanized 3-inch steel conduit and fittings sufficiently sized to accommodate all associated equipment cables, and to ensure that cables will not fray. Seal conduit between supplemental cabinet and existing controller cabinet with waterproof sealer. Ensure that the cabinet does not interfere with access to the existing controller cabinet.
the parts at location either as indicated or as specified by the District Traffic Engineer. Store parts in a secure location in the manufacturer’s approved packaging. Shelter t he parts sheltered from weather/environmental conditions. Warranty begins on the turn-on date for the ATC Assembly that the parts serve.
952.4MEASUREMENT AND PAYMENT—
The price includes required controller assembly with controller unit, detector card rack assembly (if necessary), generator adapter kit, police panel , cabinet extensions and concrete foundation for Type I assemblies, and all required controller assembly hardware for a fully operational system. Also includes time for manufacturer representative to be on site for the initial controller assembly setup and for any changes needed during the 30 -day test. 50% paid on installation. Thirty-five percent paid upon energize and controller turn-on. 15% paid on completion of the 30-day test or end of system test.
The price includes programming new timings as indicated and on field timing adjustment as necessary in the existing controller unit.
The price includes required materials and labor to add a new controller to an existing cabinet. Also includes time for manufacturer representative to be on site for the initial controller setup and for any changes needed during the 30 -day test. Removal of the existing controller and applicable wiring connection is incidental.
The price includes all necessary material and labor , including programming new timings, to modify existing controller assembly to provide operation as indicated.
The price includes the cabinet, cabinet fan, mounting hardware, concrete foundation (if applicable), and additional items necessary to connect the auxiliary cabinet to the existing cabinet and/or traffic signal pole, as well as any modifications required to existing cabinet and/or traffic signal pole to support the supplemental cabinet.
The price includes the cabinet and mounting hardware. Price includes any mounting hardware and additional items necessary to connect the auxiliary cabinet to the existing cabinet and/or traffic signal pole, as well as any modifications required to existing cabinet and/or traffic signal pole to support the supplemental cabinet.
The price includes all equipment identified as spare parts as indicated. The cost includes all necessary packaging and transporting of the equipment to the approved specified location.
The price includes mounting hardware, cable/harness assembly, power supply, receiver, and controller programming.